Step 3. Install the Communications Software
After applying power to the computer, install the Galil software that enables communication between the I/O
board and your PC. It is strongly recommended to use the Galil software “GalilTools” when communicating
to the RIO unit. Please see the GalilTools Manual for a complete description of how to install and connect to
Serial or Ethernet controllers.
http://www.galilmc.com/products/software/galiltools.html
Step 4. Establish Communications between RIO and the Host PC
Communicating to the RIO using Galil Software
RS-232:
To use serial communication, connect a 9pin
straight-through RS-232 cable
(CABLE-9-PIND) between the
serial port of the RIO and the computer or terminal communications port. The RIO serial port is configured
as DATASET.
Ethernet:
Connect the RIO Ethernet port to your computer via a crossover Ethernet cable, or to a network hub with a
straight through Ethernet cable.
Using Non-Galil Communication Software
RS-232:
The RIO serial port is configured as DATASET. The computer or terminal must be configured as a for full
duplex, no parity, 8 data bits, one start bit and one stop bit. A standard Windows HyperTerminal session can
connect to the controller using a straight-through serial cable.
Check to insure that the baud rate jumpers have been set to the desired baud rate as described above. Also,
the hardware handshake lines (RTS/CTS) need to be connected. See Chapter 3 for more information on
‘Handshake Modes.’
Ethernet:
Connect the RIO Ethernet port to your computer via an Ethernet crossover cable, or to a network hub by a
straight through Ethernet cable. An IP address needs to be assigned via a DHCP server, through Galil
software, or via a serial cable using the IA command. See Chapter 3 for more information on how to
establish an IP address. Once an IP address is established, a standard Windows Telnet session can connect to
the controller.
* Note that the RIO-471x2 supports auto-crossover detection (auto MDIX)
Sending Test Commands to the Terminal after a successful Connection
After connecting to the computer or terminal, press <carriage return> or the <enter> key on the keyboard. In
response to carriage return {CR}, the controller responds with a colon, :
Now type
RIO-47xxx