635-SERIES HARDWARE M ANUAL
Chapter-Page
2-29
635-DSI MAX NO. OF DEVICES & DEVICE COUNT (per Section)
Table 19: DSI Max. Number of Devices and Device Count for each Section
Use of section
Hardware
Max Devices
*
per Section
Valid IDs
Device Count
Remote Readers
**
with a 635 DRM Board
(Wiegand and ABA can
be mixed on the section)
635-CPU
635-DSI
(1)
635-DRMs
**
(1)
Max. 16 Readers
(
requires from 8 to 16 DRMs,
based on whether you enable one
or both reader ports on the DRM
via the DRM dipswitch Option-B).
1 thru 16 –
This is calculated by the
SG software based on
DRM board
address
– see
Step-11 for board
addressing.
Each
READER
counts
as 1 device.
Wireless Readers
using an RS-485 PIM or
Node. (Schlage, Assa,
Salto, etc.)
635-CPU
635-DSI
(1)
3
rd
party PIMs
(1)
Max. 16 Readers
(using from 1 to 16 PIMs based
on
signal strength
&
physical
topography
of the building).
1 thru 16 –
3
rd
Party software is
used to set reader ID.
(PIM must have valid ID
also)
Each
READER counts
as 1 device.
AD300 Hardwired
(NO PIMs)
635-CPU
635-DSI
Max. 16 Readers
1 thru 16 –
3
rd
Party software is used
to set reader ID.
Each
READER counts
as 1 device.
AD300/AD400 MIXED
635-CPU
635-DSI
(1)
3
rd
party PIMs
(1)
Max. 16 Readers
AD400s require PIMs
1 thru 16 –
PIMs need valid ID
Each
READER counts
as 1 device.
Clocks or LCD Units
(you cannot mix clocks &
LCDs same section)
635-CPU
635-DSI
(1)
Clock/LCD
(1)
Max. 16 CLOCKS
1 thru 16 –
This is a physical setting
configured manually
within the CLOCK or LCD.
Each
DSI SECTION
counts as 1 device.
(
IN THIS CASE YOU DO NOT
COUNT THE CLOCK OR
LCDs)
Max. 16 UNITS
635-Input Modules
(you cannot mix inputs and
outputs on same section)
635-CPU
635-DSI
(1)
635-Input Mod.
(1)
Max. 16 Input Modules
-with max 16 inputs per Input
Module.
1 thru 16 –
This is a binary dipswitch
address on the input
board.
One
INPUT MODULE
counts as 1 device.
DO NOT COUNT EVERY
INPUT.
600-Output Relay Brd
(
you cannot mix inputs and
outputs on same section)
635-CPU
635-DSI
(1)
600-Output Brd
(1)
Max. 3 Output Boards
(General Outputs)
-
max 8 Relays per board
.
- max 24 Relays per DSI Section
1 thru 3 –
Set via binary dipswitch
address on the input board.
One
Output Board
counts as 1 device.
DO NOT COUNT EVERY
RELAY
Max. 15 Output Boards
(Elevator Control Relays)
-
max 8 Relays per board
.
- max 120 Relays per DSI Section
1 thru 15 –
Set via binary dipswitch
address on output board.
*
At the actual job site, the “max devices per section” can be less than what the system supports, due to physical factors such as
signal strength, physical topography of the building, or total line distance (4,000 feet).
**
R
emote readers
can be up to 500 feet from the DRM board. You can have any mix of reader types or card format.
The DRM Boards must be within the 4,000 ft max line distance for the DSI Board.
(1)
Install
Terminal Resistors
(or onboard Termination Jumpers)
at the extreme end of the RS-485 wire run
. When installing
resistors at the device, get as close to the device as possible. DSI board and Input Board have onboard jumpers - leave them open
unless the board is truly at the extreme end of the line.