Static Charges 

In many normal installations, a static ac voltage may be read from the conductors of the page and party 
line circuits to ground.  In many cases this voltage may be as high as 50 volts or more.  This voltage is 
induced into the circuits by capacitance to the ac power circuit (generally carried in the same cable, and 
also from power cables paralleling communication cables).  This voltage is inconsequential and can be 
ignored.  Problems would only occur if one side of the page or party circuit becomes grounded. 

Audio Voltage 

In a properly operating system, audio voltage read across any of the page or party circuits (L1 or L2) is 
0.5 to 0.75 volts ac on peaks when an audio signal is present: i.e., someone speaking into a handset.  The 
voltage is proportional to the loudness of the person’s voice using the handset. 

One Inoperative Station in a Working System 

Except for a wiring error, an inoperative station indicates a defect in the amplifier at the station.  This is 
checked quickly by installing a spare amplifier or exchanging amplifiers with a properly operating station. 

Special Note Regarding Installation 

GAI-Tronics Corporation Page/Party

®

 system equipment does 

not

, in normal operation, produce arcs, 

sparks or heat that would ignite industrial gases or dusts.  Many standard GAI-Tonics products are 
approved by Factory Mutual (USA) and certified by CSA (Canada) for intended use in specified Division 
2 areas if properly installed and maintained. 

Proper installation is defined as (1) mounting and wiring per factory directions without unauthorized 
modification and (2) following all requirements of the U.S. National Electric Code (NFPA - 70) or the 
Canadian Electric Code (CSA Standard C22.1).  Installers must be familiar with these codes and consult 
them as required.  The most applicable parts of the N.E.C. code are in articles 500-503.  The most 
applicable parts of the Canadian code are in Section 18.  Some, but not all, significant points are: 

1.

 

Conduits in a Class I, Division 2 area to or from a non-hazardous area or an adjacent Class I, Division 
1 area must have approved seals in the boundary. 

2.

 

Conduits or raceways in a Class II, Division 2 or Class III area must have dust seals at entrances to 
dust-tight equipment and at boundaries to other areas unless such conduits or raceways are also dust-
tight. 

3.

 

Explosion-proof (Division 1) equipment may be installed in a Division 2 area but must have the same 
conduit and cable seals as if installed in the corresponding Division 1 area. 

4.

 

Sealing of multi-conductor cables or conduits containing multi-conductor cables in Class I, Division 1 
or 2 areas must be around each conductor of the cable - except where type MI cable is used. 

Содержание 700 Series

Страница 1: ...ation of paging speakers must be carefully considered particularly in areas of high ambient noise or reverberation The speaker amplifier built into each station drives one horn loaded page speaker If...

Страница 2: ...elded cables reduce capacitive coupling between SCR power supply cables and Page Party audio cables 3 Isolation Two methods of power source isolation can be used to avoid electrical noise A Use a low...

Страница 3: ...te are recommended A drill template is supplied with each enclosure CAUTION Use caution when drilling holes to avoid damaging internal electrical components and wiring Suggested mounting height for al...

Страница 4: ...to the terminal strip s in the enclosures GAI Tronics cable is considered to be a Class 1 cable maximum voltage is less than 600 V In a cable tray Class 1 cable may only be grouped with other Class 1...

Страница 5: ...the handset from the adjacent handset hook and press the push to page button 3 From the normal speaking distance approximately inch blow steadily into the handset microphone and adjust the control to...

Страница 6: ...e Party line circuits Remove these resistors after completion of the tests FeedbackorDistortionontheSystem Each page and party circuit must be loaded to the optimum 33 ohms using the line balance asse...

Страница 7: ...uipment does not in normal operation produce arcs sparks or heat that would ignite industrial gases or dusts Many standard GAI Tonics products are approved by Factory Mutual USA and certified by CSA C...

Страница 8: ...disconnect switch can be located in a non hazardous area outside the Division 2 area Either method will allow the use of the switch at all times Connect field wiring as detailed in instructions for t...

Страница 9: ...Pub 42004 139D GAI Tronics 700 Series Page Party Systems Page 9 of 10 s_eng gtcproddocs standard ioms current release 42004 instr manuals 42004 139d doc 11 99...

Страница 10: ...Pub 42004 139D GAI Tronics 700 Series Page Party Systems Page 10 of 10 s_eng gtcproddocs standard ioms current release 42004 instr manuals 42004 139d doc 11 99...

Отзывы: