Flexible aluminium pipes, corrosion-protected
sheet metal pipes and 

exhaust air 

pipes whose

material conforms to fire B1 in accordance with 
DIN 4102 can be used. Exhaust air pipes should
have a nominal diameter of 6 ´ ´ / 150 mm.

Pay particular attention to ensuring

that

– the exhaust air ducts and pipes are kept as short

as possible

– the pipes are not laid at an acute angle, but as

bends and that they are inserted into the shaft at
an inclined upward angle and

– there are no cross-sectional constrictions in the

upward direction (this reduces the volume flow).

If long, rough exhaust-air pipes, many pipe
bends or smaller pipe diameters are used, the
air extraction rate will no longer be at an
optimum level and there will be an increase in
noise.

The manufacturer of the extractor hood
accepts no liability for complaints which can
be attributed to the design and layout of the
pipework. 

As standard, the blow-out opening of the extractor
hood is in the upward direction.

To pass exhaust air through the outer wall, we
recommend the use of our telescopic wall box 
TM 150-045 (Ø  6 ´ ´ / 150 mm).

Note:

To prevent the ingress of water, e.g. condensate or
rain water from an uncovered exhaust air shaft, our
condensate separator RV 060-150 must be installed
in the exhaust air line. The condensate separator
must still be accessible after installation.  

The duct units listed below are available
depending on the height of the ceiling:

Installation accessories for 

exhaust air mode

Stainless steel-design ventilation duct:

LK 010-012 

for ceiling heights of 7 ´´ 4 ´ ´ - 8 ´´ 6 ´ ´

LK 010-022 

for ceiling heights of 8 ´´ 6 ´ ´ - 9 ´´ 9 ´ ´

Aluminium-design ventilation duct:

LK 011-012 

for ceiling heights of 7 ´´ 4 ´ ´ - 8 ´´ 6 ´ ´

LK 011-022 

for ceiling heights of 8 ´´ 6 ´ ´ - 9 ´´ 9 ´ ´

Installation accessories for 

circulating air mode

Stainless steel-design ventilation duct:

LK 010-112

for ceiling heights of 7 ´´ 7 ´ ´ - 8 ´´ 6 ´ ´

LK 010-122 

for ceiling heights of 8 ´´ 6 ´ ´ - 9 ´´ 9 ´ ´

Aluminium-design ventilation duct:

LK 011-112

for ceiling heights of 7 ´´ 7 ´ ´ - 8 ´´ 6 ´ ´

LK 011-122 

for ceiling heights of 8 ´´ 6 ´ ´ - 9 ´´ 9 ´ ´

The dimensions above refer to a distance of 5 ´ 3 ´ ´
from the floor to the bottom edge of the hood.

If required, custom made duct units are available at
an extra charge.

The socket must be placed behind the duct cover
on the wall.

To use above gas cooker / gas hob

Important:

do not use all burners on the highest

setting simultaneously over a longer period of time
(max. 15 minutes). This will pose a risk of burns
when touching the hot appliance exterior or parts of
the extractor hood may become damaged.

Switch the extractor hood to the highest setting
when three or more burners of a gas cooker are
used simultaneously.

Содержание AW 200-790

Страница 1: ...Operating and Assembly Instructions AW 200 790 AW 201 790 Extractor Hood...

Страница 2: ...4 5 1 1 For your safety Page 4 1 2 Operating for the first time Page 5 1 3 About use Page 5 2 Features Page 6 3 Operation Page 7 9 4 Cleaning and care Page 10 11 5 Maintenance Page 12 6 Assembly inst...

Страница 3: ...otes on use installation and maintenance of the appliance On the following page you will find important notes on safety and operation These will serve to ensure your personal safety and the lasting va...

Страница 4: ...Always turn hood ON when cooking at high heat or when cooking flaming foods c Clean ventilating fans frequently Grease should not be allowed to accumulate on fan or filter d Use proper pan size Alway...

Страница 5: ...ppliance Do not clean the appliance with a steam cleaning apparatus or with water pressure because this poses a risk of short circuits Isolate the appliance from the mains during every maintenance ope...

Страница 6: ...f children Thoroughly clean the appliance before using it for the first time see chapter Cleaning and care Before operating the appliance for the first time check that the mains connection is in prope...

Страница 7: ...7 4 8 6 LK 011 022 for ceiling heights of 8 6 9 9 Installation accessories for circulating air mode Stainless steel design ventilation duct LK 010 112 for ceiling heights of 7 7 8 6 LK 010 122 for cei...

Страница 8: ...ation by pressing the key see Fig 4 When you briefly press the key the lighting is increased up to the maximum level You can dim the lighting to the required level by keeping the key pressed Fan level...

Страница 9: ...ess the Int key while the hood is running at fan level 1 2 or 3 the electronic control will switch back automatically to the previously selected fan level after 5 minutes see Fig 7 If you would like t...

Страница 10: ...f time for all levels is ten minu tes After these ten minutes the ventilation switches off but the lighting stays on Interval ventilation Interval ventilation is a special feature of this appliance wh...

Страница 11: ...out of the holder repeat the operation for the other grease filters You can clean the stainless steel grease filters in a dishwasher at a maximum temperature of 130 F 55 C where it should be supported...

Страница 12: ...lls in the circulating air mode In normal use 1 to 2 hours daily the activated charcoal filter must be replaced approximately once a year If no activated charcoal filter is installed kitchen smells wi...

Страница 13: ...safety of the appliance Unauthorised tampering with the appliance will invalidate any warranty claims Only ever use original spare parts Lamp replacement Caution disconnect the power supply before re...

Страница 14: ...appli cation and be connected to a GFCI Ground Fault Circuit Interrupter protected branch circuit f NEVER place a switch where it can be reached from a tub or shower WARNING To reduce the risk of fire...

Страница 15: ...t is not in operation During the course of planning a chimney sweep must be consulted if a room air dependent hearth is operated in the same room as the one in which a hood is operated in the exhaust...

Страница 16: ...or RV 060 150 must be installed in the exhaust air line The condensate separator must still be accessible after installation The duct units listed below are available depending on the height of the ce...

Страница 17: ...c Make sure that the hooks lie flatly on the wall In certain circumstances you may have to countersink the drill holes Fit the included dowels a in the other drill holes Note at least one screw must...

Страница 18: ...sitive metal surfaces Fit the top chimney duct unit into the base Make sure that the fastening holes on the side are at the top Put both chimney duct units onto the hood Pull the top chimney duct unit...

Страница 19: ...lish the electrical connection Stainless steel chimney only LK 010 112 122 pull the protective film off the chimney s trims Note avoid damaging the sensitive metal surfaces Fit the top chimney duct un...

Страница 20: ...EN 780 DEDHAM STREET CANTON MA 02021 USA Y 800 828 9165 www gaggenau usa com GAGGENAU HAUSGER TE GMBH CARL WERY STR 34 81739 M NCHEN GERMANY Y 089 45 90 03 FAX 089 45 90 23 47...

Отзывы: