15

Flexible aluminium pipes, corrosion-protected
sheet metal pipes and 

exhaust air 

pipes whose

material conforms to fire B1 in accordance with 
DIN 4102 can be used. Exhaust air pipes should
have a nominal diameter of 6 ´ ´ / 150 mm.

P

ay particular attention to ensuring

that

– the exhaust air ducts and pipes are kept as short

as possible

– the pipes are not laid at an acute angle, but as

bends and that they are inserted into the shaft at
an inclined upward angle and

– there are no cross-sectional constrictions in the

upward direction (this reduces the volume flow).

If long, rough exhaust-air pipes, many pipe

bends or smaller pipe diameters are used, the
air extraction rate will no longer be at an
optimum level and there will be an increase in
noise.

The manufacturer of the extractor hood
accepts no liability for complaints which can
be attributed to the design and layout of the
pipework. 

As standard, the blow-out opening of the extractor

hood is in the upward direction.

To pass exhaust air through the outer wall, we
recommend the use of our telescopic wall box 
TM 150-045 (Ø  6 ´ ´ / 150 mm).

Note:

T

o prevent the ingress of water, e.g. condensate or

rain water from an uncovered exhaust air shaft, our
condensate separator RV 060-150 must be installed
in the exhaust air line. The condensate separator
must still be acciessible after installation.

The duct units listed below are available
depending on the height of the ceiling:

Installation accessories for 

exhaust air mode

Stainless steel-design ventilation duct:

LK 010-016 

for ceiling heights of  7

´´ 4 ´ ´ - 7 ´´ 11 ´ ´

LK 010-026 

for ceiling heights of  7

´´ 11 ´ ´ - 9 ´´

LK 010-036 

for ceiling heights of  9

´´ - 9 ´´ 9 ´ ´

Aluminium-design ventilation duct:

LK 01

1-016 

for ceiling heights of  7

´´ 4 ´ ´ - 7 ´´ 11 ´ ´

LK 01

1-026 

for ceiling heights of  7

´´ 11 ´ ´ - 9 ´´

LK 01

1-036 

for ceiling heights of  9

´´ - 9 ´´ 9 ´ ´

Installation accessories for circulating 

air mode

Stainless steel-design ventilation duct:

LK 010-126

for ceiling heights of  7

´´ 11 ´ ´ - 9 ´´

LK 010-136 

for ceiling heights of  9

´´ - 9 ´´ 9 ´ ´

Aluminium-design ventilation duct:

LK 01

1-126

for ceiling heights of  7

´´ 11 ´ ´ - 9 ´´

LK 01

1-136 

for ceiling heights of  9

´´ - 9 ´´ 9 ´ ´

The dimensions above refer to a distance of 5 ´ 3 ´ ´
from the floor to the bottom edge of the hood.

If required, custom made duct units are available at
an extra charge.

The electrical socket must be placed within the
ventilation duct on the ceiling.

T

o use above gas cooker / gas hob

Important:

do not use all burners on the highest

setting simultaneously over a longer period of time
(max. 15 minutes). This will pose a risk of burns
when touching the hot appliance exterior or parts of
the extractor hood may become damaged.

Switch the extractor hood to the highest setting
when three or more burners of a gas cooker are
used simultaneously.

Содержание AI 200-700

Страница 1: ...Operating and Assembly Instructions AI 200 700 Extractor Hood...

Страница 2: ...1 For your safety Page 4 1 2 Operating for the first time Page 5 1 3 About use Page 5 2 Features Page 6 3 Operation Page 7 9 4 Cleaning and care Page 10 11 5 Maintenance Page 12 6 Assembly instructio...

Страница 3: ...otes on use installation and maintenance of the appliance On the following page you will find important notes on safety and operation These will serve to ensure your personal safety and the lasting va...

Страница 4: ...Always turn hood ON when cooking at high heat or when cooking flaming foods c Clean ventilating fans frequently Grease should not be allowed to accumulate on fan or filter d Use proper pan size Alway...

Страница 5: ...pliance Do not clean the appliance with a steam cleaning apparatus or with water pressure because this poses a risk of short circuits Isolate the appliance from the mains during every maintenance oper...

Страница 6: ...f children Thoroughly clean the appliance before using it for the first time see chapter Cleaning and care Before operating the appliance for the first time check that the mains connection is in prope...

Страница 7: ...of 7 4 7 11 LK 011 026 for ceiling heights of 7 11 9 LK 011 036 for ceiling heights of 9 9 9 Installation accessories for circulating air mode Stainless steel design ventilation duct LK 010 126 for ce...

Страница 8: ...ation by pressing the key see Fig 4 When you briefly press the key the lighting is increased up to the maximum level You can dim the lighting to the required level by keeping the key pressed Fan level...

Страница 9: ...ess the Int key while the hood is running at fan level 1 2 or 3 the electronic control will switch back automatically to the previously selected fan level after 5 minutes see Fig 7 If you would like t...

Страница 10: ...f time for all levels is ten minu tes After these ten minutes the ventilation switches off but the lighting stays on Interval ventilation Interval ventilation is a special feature of this appliance wh...

Страница 11: ...out of the holder repeat the operation for the other grease filters You can clean the stainless steel grease filters in a dishwasher at a maximum temperature of 130 F 55 C where it should be supported...

Страница 12: ...ilter must be replaced approximately once a year If no activated charcoal filter is installed kitchen smells will not be eliminated The activated charcoal filter KF 001 010 is available through your s...

Страница 13: ...safety of the appliance Unauthorised tampering with the appliance will invalidate any warranty claims Only ever use original spare parts Lamp replacement Caution disconnect the power supply before re...

Страница 14: ...ropriate for the appli cation and be connected to a GFCI Ground Fault Circuit Interrupter protected branch circuit f NEVER place a switch where it can be reached from a tub or shower WARNING To reduce...

Страница 15: ...chimney that is not in operation During the course of planning a chimney sweep must be consulted if a room air dependent hearth is operated in the same room as the one in which a hood is operated in...

Страница 16: ...air line The condensate separator must still be acciessible after installation The duct units listed below are available depending on the height of the ceiling Installation accessories for exhaust air...

Страница 17: ...20 Note this hood has been approved for installations as low as 30 and as high as 36 above the cooktop Circulating air mode only there are four brackets which fix the circulating air switch module to...

Страница 18: ...ust be on the same side as the control panel after installation Circulating air mode only assemble the circulating air switch module and fix it to support frame Fig 22 and 23 Cut the flexible air pipe...

Страница 19: ...ey duct unit which has no magnetic strips with 2 screws on the top of the support frame Fig 26 14 The second top chimney duct which has magnetic strips should be slightly bent open in order to slide o...

Страница 20: ...551 McFADDEN AVENUE HUNTINGTON BEACH CA 92649 USA Y 800 828 9165 FAX 714 901 0979 www gaggenau usa com GAGGENAU HAUSGER TE GMBH CARL WERY STR 34 81739 M NCHEN GERMANY Y 089 45 90 03 FAX 089 45 90 23 4...

Отзывы: