G4S M2150 8DC Скачать руководство пользователя страница 2

0V

+12Vdc

Power 

supply input

Use supplied cable

COMMS-

COMMS+

0V

+12V

Ground one end only

Controller

COMMS-

0V

0V

COMMS+

3000ft (1km) max; Belden 9502

Twisted 

pair

COMMS+

COMMS-

Cabinet

Make sure the building ground is 
connected to a ground stud in the cabinet.

Connect to AC MONITOR terminal block 

on power supply board (if used). If this 

connection is not made, a "Power Fail" 

alarm will be generated at the PC each 

time the system re-starts.

Polarity unimportant

Connect to ac input of 

Power Supply Board 

(polarity unimportant)

+

-

TAMP

AC MON+

AC MON -

TAMP

TAMPER SWITCH 
AND POWER 
INDICATOR

- +

OR

450ft (150m) max with Belden 9503, or 900ft 

(300m) by doubling power cores with Belden 9504.

+V

Rx-
Rx+

Tx+

Tx-

0V

20mA

Twisted 

pairs

Cabinet

0V

Rx-

Rx+

Tx+

Tx-

12V

Note:

 Actual output voltage 

nominally 13V at each reader 
terminal block.

12V
Green LED
Data 1

Red LED

Data 0

Ground

Wiegand

Cabinet

0V

0

RED

1

GRN

12V

225ft (75m) max with Belden 9537, or 450ft (150m) 

by doubling power cores with Belden 9539.

READER 4 (20mA/Wiegand)

(500mA

 max)

Two readers at one door -

 

numbered reader for entry reader and next even-
numbered reader for exit reader. Door furniture 
connects to corresponding odd-numbered door.

Use an odd-

20mA

Wiegand

READER 2 

(20mA/Wiegand)

READER 1 

(20mA/Wiegand)

READER 3 

(20mA/Wiegand)

DOOR 2

DOOR 1

DOOR 3

READER 8 

(20mA/Wiegand)

READER 5 

(20mA/Wiegand)

READER 7 

(20mA/Wiegand)

READER 6 

(20mA/Wiegand)

DOOR 8

DOOR 5

DOOR 7

DOOR 6

FIT WIM-8 IF 

USING WIEGAND 

READERS

BYPASS

Bypassed Device 
(optional)
(28Vdc, 3A max)

Door Monitor

Exit Request 
Button 
(optional)

Connect to Normally Open 
(NO) or Normally Closed 
(NC), as appropriate.

Cabinet

Cabinet

DOOR 4

Door Release
(28Vdc, 3A max)

Ensure  release  is 
noise suppressed

+V

0V

Power supply (see 

Access 

Control Design Guide)

NO

NO

C

C

NC

NC

RELEASE

1500ft (500m) max; 24 AWG

1500ft (500m) max; 24 AWG

DOOR-

EXIT-

EXIT+

DOOR+

Reader 6

Reader 5

Reader 3

Reader 4

Reader 2

Reader 7

Reader 8

Reader 1

W

C

Set reader's switch 
to "C" for 20mA or 
"W" for Wiegand.

Note: 

UL compliance requires power-

limited and non-power-limited wiring 
to be separated by at least 0.25” 
(7mm). Please refer to the cabinet 

EXIT-

Note: 

The board contains an 

automatically-resettable fuse for 
each reader

must remove the load completely 
before the fuse resets.

If a fuse trips, you 

Set Address - When the 8DC is connected to a DBU, its address 
can be 1 or 5. When connected to any other database unit, its 
address must be 5. Link the center and left pins to set to address 
1. Link the center and right pins to set to address 5 (readers 9-
16). An 8DC occupies four addresses (i.e. 1-4, or 5-8).

DO NOT LINK THESE PINS 
(RS485 TERMINATION)

Short tamper 
terminals if a 
tamper switch 
is not used.

8DC Connection 

2

Database unit

CONNECTIONS TO DATABASE UNIT AND OTHER 

OPTIONAL REMOTE DOOR/ALARMS CONTROLLERS

Notes:

1). Consult local AHJ (Authority Having Jurisdiction) when installing access control readers and 
locking mechanisms to any portal in an egress path.

2). The use of Fail Closed / secure configuration shall be determined by local building codes and the 
local AHJ.

3). Wiring methods shall be in accordance with NEC (National Electrical Code) ANSI/NFPA 70.

4). This device must be installed within the secure area / perimeter for UL1076 and UL294 Listed 
installations.

5). Installer must provide Network Surge Protection by installing (per manufacturers installation 
instructions) 1 each APC PNet1GB Ethernet surge protection device in line with the RJ-45 Ethernet 
connector on this board prior to connecting this board to the local or wide area network.

6). For Access Control Systems in a “Stand Alone” configuration only, the following Power supplies 
are to be installed: Model MN-PSU-6A and MN-TRANS-150-UL transformer. Any additional power 
supply used (e.g. for door releases and auxiliary outputs) must be power limited, UL listed for Access 
Control Systems and Accessories. All interconnecting devices must be UL Listed.

7). Some devices described in these instructions may not be applicable for sites requiring UL 
compliance. Please refer to the 

Access Control Design Guide 

for details of the controllers, modules 

and features that have been UL tested for use with this device.

WARNING:

 Incorrect connections will 

permanently damage the board.