23
G1
LA
LA
G1
V1
LB
LB
V1
Wiring diagram for ST10/ST20 and IO10
RZ XX / 1
(Master)
ST20
(2x)
IO10
(2x)
IO10 adress 1
Input
Contact
Function
1
I1
Window OPEN
2
I2
Window STOP
3
I3
Window CLOSE
4
I4
Reset RWA alarm - close
Output
Contact
Function
1
R1 (41, 51, 61)
Window closed
2
R2 (42, 52, 62)
RWA alarm
3
R3 (43, 53, 63)
Fault
4
R4 (44, 54, 64)
Maintenance display
Signal description:
4X = NO,
5X = COM,
6X = NC
IO10 adress 2
Input
Contact
Function
1
I1
Rain
2
I2
Wind
3
I3
Timer, edge-triggered
4
I4
No function
Output
Contact
Function
1
R1 (41, 51, 61)
Rain
2
R2 (42, 52, 62)
Wind
3
R3 (43, 53, 63)
RWA push-button pressed
4
R4 (44, 54, 64)
Smoke detector has responded
Signal description:
4X = NO,
5X
=
COM,
6X
=
NC
4.3.3.3 Wiring diagram for ST10/ST20 key switch and IO10 input/output module
Control and signalling functions IO10
Central ventilation push-button
Operation: OPEN / CLOSE (no deadman‘s control, irrespective of the setting in the control unit)
Central weather control
Central timer input
Central alarm reset function