G.M. International D5231E Скачать руководство пользователя страница 7

 

D5231 

- SIL 2 Switch/Proximity Detector Repeater, O.C. Output 

G.M. International ISM0172-1 

CONFIGURATION 

Configuration parameters can be read and written from the module or from saved file. 

It is also possible to reset the module configuration to factory default settings. 

A report sheet containing complete configuration can be printed.

 

INPUTS 1 to 8: 

Sensor Type:

  

 Proximity 

 Voltage free contact 

Note: To enable line diagnostic on Voltage free contacts, configure sensor as 

“Proximity” and follow instructions in Section “Operation”. 

TAGS 1 to 8:

 

16 alphanumerical characters. 

OUTPUTS 1 to 8: 

Source: 

 Input 1 

Output represents Input 1, 

 Input 2 

Output represents Input 2, 

 Input 3 

Output represents Input 3, 

 Input 4 

Output represents Input 4, 

 Input 5 

Output represents Input 5, 

 Input 6 

Output represents Input 6, 

 Input 7 

Output represents Input 7, 

 Input 8 

Output represents Input 8, 

 Logical function  Output represents AND/OR function of selected inputs. 

Contact:

 normal condition of output contact 

 NC 

Normally Closed, 

 NO 

Normally Open. 

In case of fault: 

Output behaviour when Input fault is detected.

 

 Ignore 

Ignore, 

 Go On 

Switch to ON status (Open when NC, Closed when NO), 

 Go Off 

Switch to OFF status  (Closed when NC, Open when NO). 

Fault repeater: 

Output represents Input Fault status 

Logical Function: 

visible only when selected in “Output source”. 

Select 2 or more (up to 8) Inputs to connect logically. 

 AND 

Output represents AND logical function of selected Inputs, 

 

- NO: On AND On = Close; On AND Off = Open; Off AND Off = Open 

 

- NC: On AND On = Open; On AND Off = Close; Off AND Off = Close 

 OR 

Output represents OR logical function of selected Inputs 

 

- NO: On OR On = Close; On OR Off = Close; Off OR Off = Open 

 

- NC: On OR On = Open; On OR Off = Open; Off OR Off = Close 

 

MONITOR 

Allows the real-time monitoring of every Input and Output status. 

Note that configuration is disabled when Monitoring is active. 

INPUT STATUS: 

The status of each input is shown

 

 Open circuit 

Open circuit fault (only for Proximity Inputs), 

 Off 

Off, 

 On 

On, 

 Short circuit 

Short circuit fault (only for Proximity Inputs). 

OUTPUT STATUS: 

The status of each output contact is shown

 

 Open 

 

 Closed 

 

 

DATA LOGGER 

The status of all Inputs and all Outputs is acquired at constant chosen intervals and 

saved to user selected file in Comma Separated Value format (.csv).  

Note that configuration is disabled when Data Logger is active.

 

PARAMETERS SETUP: 

Days: 

Number of days to acquire. 

Hours: 

Number of hours to acquire. 

Minutes: 

Number of minutes to acquire. 

Scan rate: 

Frequency interval for acquisitions. 

 

General Notes:  

SWC5090 Software can be downloaded for free at www.gmintsrl.com 

PPC5092 Adapter is needed to interface PC to D5231E module. 

The PC supplies the module via USB, therefore operating power supply (24 Vdc) is not 

strictly needed when configuring the module. 

Each channel has completely independent configurations. 

See ISM0154 Manual for details on SWC5090 software. 

SWC5090 Software and PPC5092 USB Adapter 

Input / Output configuration 

Input / Output status real-time monitor 

Real-time data logging to file 

Configurating and Monitoring via Software: 

Screenshots: 

Содержание D5231E

Страница 1: ...h Proximity Detector Repeater O C Output G M International ISM0172 1 SIL 2 Switch Proximity Detector Repeater Open Collector Output DIN Rail and Termination Board Model D5231E D5231E INSTRUCTION MANUAL INSTRUCTION MANUAL ...

Страница 2: ...y 500 V Input switching current levels ON 2 1 mA 1 9 to 6 2 mA range OFF 1 2 mA 0 4 to 1 3 mA range switch current 1 65 mA 0 2 mA hysteresis Fault current levels open fault 0 2 mA short fault 6 8 mA Input equivalent source 8 V 1 KΩ typical 8 V no load 8 mA short circuit Output voltage free SPST optocoupled open collector transistor solid state relay photo MOS Open collector rating 100 mA at 35 V 1...

Страница 3: ...y or Voltage free Contact Terminal block connections HAZARDOUS AREA SAFE AREA Input Ch 2 for Proximity or Voltage free Contact Input Ch 3 for Proximity or Voltage free Contact Input Ch 4 for Proximity or Voltage free Contact 13 14 15 16 Output 1 1 Output 2 2 Model D5231 8 channels E Power Bus and DIN Rail accessories Connector JDFT049 Cover and fix MCHP196 Terminal block male MOR017 Terminal block...

Страница 4: ... effective group See parameters indicated in the table below D5231 Terminals 21 13 21 14 22 15 22 16 23 17 23 18 24 19 24 20 D5231 Terminals D5231 Associated Apparatus Parameters Cenelec US Ci Ci device C cable IIC A B Co Ca 1 84 µF Co Ca 12 6 µF Co Ca 54 µF IIB C IIA D Co Ca 49 µF Co Ca 12 6 µF I iaD E F G IIC A B Lo La 253 mH Lo La 1009 mH Lo La 2017 mH IIB C IIA D Lo La 3309 mH Lo La 1009 mH I ...

Страница 5: ...tact required for line fault detection 23 17 18 24 19 20 In 5 In 6 In 7 In 8 Termination board connector MODEL D5231E 14 2 Out 2 3 Out 3 22 15 16 Common positive connection In 2 In 3 In 4 21 13 11 1 Out 1 In 1 Proximity voltage free Contact 5 6 Out 6 Out 7 Out 8 7 8 Out 4 4 9 10 Supply 24 Vdc Common Ch 1 to 8 Out 5 F Power and Fault Bus Modbus RS485 A B Modbus 12 R2 R1 R2 R1 R2 R1 R2 R1 R2 R1 R2 R...

Страница 6: ...5 KΩ range resistor in parallel to the contacts in order to allow the fault detection circuit to distinguish between a condition of contact close open and a line open short circuit fault Installation D5231 series modules are housed in a plastic enclosure suitable for installation on T35 DIN Rail according to EN50022 with or without Power Bus or on customized Termination Board D5231 unit can be mou...

Страница 7: ...ected Inputs NO On AND On Close On AND Off Open Off AND Off Open NC On AND On Open On AND Off Close Off AND Off Close OR Output represents OR logical function of selected Inputs NO On OR On Close On OR Off Close Off OR Off Open NC On OR On Open On OR Off Open Off OR Off Close MONITOR Allows the real time monitoring of every Input and Output status Note that configuration is disabled when Monitorin...

Страница 8: ...535 65535 65535 65535 65535 65535 65535 65535 3 Tags are composed of 16 characters Each address contains 2 chars starting from left 4 All configurations must be confirmed via Addr 464 see details on the right Notes Supported functions Code Name Notes 03 read holding registers reads a stream of words from memory 04 read input registers reads a stream of words from memory 06 write single register wr...

Отзывы: