D1033 

- SIL 2 Switch / Proximity Detector Repeater Transistor Output 

G.M. International ISM0043-11 

D1033 series are isolated Intrinsically Safe Associated Apparatus installed into standard EN50022 T35 DIN Rail located in Safe Area/Non Hazardous Locations or Zone 2, Group IIC, 
Temperature Classification T4, Class I, Division 2, Groups A, B, C, D, Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA Temperature Code T4 Hazardous Area/Hazardous 
Locations (according to EN/IEC60079-15, FM Class No. 3611, CSA-C22.2 No. 213-M1987, CSA-E60079-15) within the specified operating temperature limits Tamb -20 to +60 °C, 
and connected to equipment with a maximum limit for AC power supply Um of 250 Vrms. 

Non-incendive field wiring is not recognized by the Canadian Electrical Code, installation is permitted in the US only. 
For installation of the unit in a Class I, Division 2 or Class I, Zone 2 location, the wiring between the control equipment and the D1033 associated apparatus shall be accomplished 
via conduit connections or another acceptable Division 2, Zone 2 wiring method according to the NEC and the CEC. 
Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground. 
D1033 series must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards 
(e.g. IEC/EN60079-14 Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines), BS 5345 Pt4, VDE 165, 
ANSI/ISA RP12.06.01 Installation of Intrinsically Safe System for Hazardous (Classified) Locations, National Electrical Code NEC ANSI/NFPA 70 Section 504 and 505, 
Canadian Electrical Code CEC) following the established installation rules, particular care shall be given to segregation and clear identification of I.S. conductors from non I.S. ones. 
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area/Hazardous Locations or 
unless area is known to be nonhazardous. 

Warning: substitution of components may impair Intrinsic Safety and suitability for Division 2, Zone 2. 
Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous. 

Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. 
The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided. 

 

Warning 

Operation 

 

D1033 accepts as an input from Hazardous Area/Hazardous Locations a proximity sensor or voltage free electrical contact and repeats their status to Safe Area/Non Hazardous 
Locations by optoisolated open collector transistor. Presence of supply power and status of output (energized or de-energized), as well as integrity or fault condition of sensor and 
connecting line are displayed by signaling LEDs (green for power, yellow for status and red for fault condition). D1033Q (quad channel type) has four independent isolated input channels  
and actuates the corresponding output transistor; two actuation modes can be independently DIP switch configured for each input channel: 
Normally open input / Normally close transistor    or  Normally close input / Normally close transistor 
Contact or proximity sensor and its connection line short or open circuit fault detection is also DIP switch configurable. Fault detection can be enabled (in case of fault de-energizes the 
corresponding output channel transistor (open) and turns ON the fault LED) or be disabled (in case of fault the corresponding output channel transistor repeats the input line open or 
close status as configured). D1033D (dual channel type) has two isolated input channel and four output transistors; the unit has two DIP switch configurable operating modes: 
A)  Input channel actuates in parallel output transistors (providing a DPST type of output). Transistors actuation can be independently configured for each output in two modes: 
    Normally open input / Normally close transistor    or  Normally close input / Normally close transistor 
B)  Input channel actuates output transistor (A) configurable in two modes as above. Output transistor B operates as fault output (in case of input fault, transistor B actuates and the 

  fault LED turns on while transistor A repeats the input line as configured). Actuation can be configured in two modes: 
  No input fault / Close transistor (it de-energizes in case of fault) or No input fault / Open transistor (it energizes in case of fault). 

Note:

 use of voltage free electrical contacts with fault detection enabled requires, near the switch at the end of the line, a 1 K

 series connected resistor and a 10 K

 parallel connected 

resistor in order to allow the fault detection circuit to distinguish between a condition of contact close/ open and a line open/short circuit fault. 

 

D1033 Associated Apparatus

FM Approved

under Entity Concept

and non-incendive field wiring

Unclassified Locations or

Hazardous (Classified) Locations

Class I, Division 2, Groups A, B, C, D, T-Code T4

Class I, Zone 2, Group IIC, IIB, IIA, T-Code T4

FM Approved under Entity Concept,

or third party approval

Hazardous (Classified) Locations

Class I, Division 1, Groups A, B, C, D

Class II, Division 1, Groups E, F, G

Class III, Division 1

Class I, Zone 0, Group IIC, IIB, IIA

Intrinsically 

Safe Equipment

Must not use or generate

more than 250 Vrms or Vdc

Control 

Equipment

Unclassified Locations

Hazardous (Classified) Locations

Class I, Division 2, Groups A, B, C, D

Class II, Division 2, Groups E, F, G

Class III, Division 2

Class I, Zone 2, Group IIC, IIB, IIA

FM Approved under non-incendive field

wiring (permitted only for US installations),

or third party approval

13
14

1
2

+

-

-

+

Power Supply

3
4

16

15

-

+

Intrinsically 

Safe Equipment

Unclassified Locations or

Hazardous (Classified) Locations

Class I, Division 2, Groups A, B, C, D, T-Code T4

Class I, Zone 2, Group IIC, IIB, IIA, T-Code T4

Unclassified Locations

Must not use or generate

more than 250 Vrms or Vdc

6

5

Control 

Equipment

Control 

Equipment

Control 

Equipment

2

6

8

7

Intrinsically 

Safe Equipment

-

+

10

9

Intrinsically 

Safe Equipment

+

-

11

12

+

-

Power Supply

Control 

Equipment

Control 

Equipment

Control 

Equipment

Control 

Equipment

14

9

11

12

10

16

15

13

4

3

2

7

8
6

2

6

5

1

+

-

+

+

-

-

-

+

Non-incendive

Equipment

Non-incendive

Equipment

Non-incendive

Equipment

Non-incendive

Equipment

D1033 Associated Apparatus

FM Approved

under Entity Concept

and non-incendive field wiring

Содержание D1033D

Страница 1: ...L 2 Switch Proximity Detector Repeater Transistor Output ISM0043 11 D1033D D1033Q INSTRUCTION MANUAL INSTRUCTION MANUAL SIL 2 Switch Proximity Detector Repeater Transistor Output DIN Rail Models D1033...

Страница 2: ...zed 1 5 W for 4 channels D1033Q 1 1 W for 2 channels D1033D Isolation Test Voltage I S In Out 1 5 KV I S In Supply 1 5 KV I S In I S In 500 V Out Supply 500 V Out 1 3 Out 2 4 500 V Input switching cur...

Страница 3: ...on negative or positive output both accepted in standard version D1033 Transistor Output for fault detection on dual channel version Line fault detection with common signalling available when using Po...

Страница 4: ...Ch 3 7 Output Ch 4 8 D1033D Input Ch 1 for Proximity or Input Ch 1 for Voltage free Contact HAZARDOUS AREA SAFE AREA Input Ch 1 for Proximity or Input Ch 1 for Voltage free Contact 13 14 Output Ch 1...

Страница 5: ...F IIB C IIA D Ci Ci device C cable Ch1 Ch2 13 14 15 16 Ch3 Ch4 9 10 11 12 Li Li device L cable Ch1 Ch2 13 14 15 16 Ch3 Ch4 9 10 11 12 Li Ri device and L cable R cable Ch1 Ch2 13 14 15 16 Ch3 Ch4 9 10...

Страница 6: ...N HAZARDOUS LOCATIONS CLASS I DIVISION 2 GROUPS A B C D T Code T4 CLASS I ZONE 2 GROUP IIC T4 MODEL D1033Q 13 14 3 4 1 2 Common Channels 1 3 Supply 24 Vdc Out 1 5 6 Common Channels 2 4 Out 2 7 Out 3 8...

Страница 7: ...d actuates the corresponding output transistor two actuation modes can be independently DIP switch configured for each input channel Normally open input Normally close transistor or Normally close inp...

Страница 8: ...5 V resistive load The enclosure provides according to EN60529 an IP20 minimum degree of mechanical protection or similar to NEMA Standard 250 type 1 for indoor installation outdoor installation requi...

Страница 9: ...4 4 3 3 Disabled contact proximity sensor Enabled proximity sensor or contact with terminating line resistor ON CH2 Setting Line fault detection ON IN OUT Operation NO NC or NC NO NO NO or NC NC ON O...

Страница 10: ...roximity sensor or contact with terminating line resistor OFF Input Output Input Output Output Input Output Input 9 NO 10 OR NC 9 10 9 NO 10 OR NC 9 10 7 NO 2 NC 7 2 7 NO 2 NC 7 2 Input Output Input O...

Страница 11: ...witch 8 positions Fault Output 1 OFF ON OFF ON OFF Side B Panel View ON ON NO NC or NC NO NO NO or NC NC Input Output Input Output Output Input Output Input 13 NO 14 OR NC 13 14 13 NO 14 OR NC 13 14 1...

Страница 12: ...NO 6 NC 5 6 NO Mode NC Mode No Fault No Fault 8 NO 6 NC 8 6 Switch 4 positions Input Output Input Output 15 NO 16 NC 15 16 8 NC 6 NO 8 6 Switch 8 positions Input Output Input Output 15 NO 16 OR NC 15...