MCT-CM
215
*B29
Parameter
Value
Description
Bit0
Digital Output 16 On
Bit1
Digital Output 17 On
Bit2
Digital Output 18 On
Bit3
Digital Output 19 On
Bit4
Digital Output 20 On
Bit5
Digital Output 21 On
Bit6
Digital Output 22 On
Bit7
Digital Output 23 On
Bit8
Digital Output 24 On
Bit9
Digital Output 25 On
Bit10
Digital Output 26 On
Bit11
Digital Output 27 On
Bit12
Digital Output 28 On
Bit13
Digital Output 29 On
Bit14
Digital Output 30 On
Bit15
Digital Output 31 On
*C1
The ‘wait setpoint’ does not have units of measure. It is a raw numerical value, i.e., it is compared
directly to the numerical value of any loop or monitor input
selected as a ‘wait for’ input. The wait for
setpoint uses an implied decimal point of 1 for all comparisons regardless of the decimal point
configuration of the loop or monitor input.
*C2
The units of measure and range of a loop or monitor input is dependent upon the configuration of the
input and/or the units of temperature selection (Celsius or Fahrenheit) of the MCT. The decimal point
position for the loop or monitor input is an implied value based on the configuration of the input. Thus,
a register value of 345 can represent an actual process value of 345, 34.5, 3.45 or 0.345 depending
upon the decimal point configuration of the loop or monitor input.
A.1.2.2 Automatic Program Registers
The automatic program parameters are a separate group of registers that are used to load programs to the
MCT. The manner in which the program steps are configured and sent to the MCT is specific and must be
followed exactly.
Each program step consists of 28 data registers. The program must be written one step at a time, using a
multiple write command (0x10) to write the data for all 28 registers at once. This allows programs to be stored
as two-dimensional arrays, of which code can be written to simply index through the array step-by-step and
transmit the program file to the MCT.
Содержание MCT-CM
Страница 1: ...MCT CM User Manual MCT CM User Manual Rev C August 2022 V1 2eCM30 V1 3eCM22 Supersedes May 2021...
Страница 20: ...MCT CM 20...
Страница 24: ...MCT CM 24...
Страница 45: ...MCT CM 45...
Страница 187: ...MCT CM 187...
Страница 227: ...MCT CM 227 A 4 Control Module Specifications Main CPU...
Страница 228: ...MCT CM 228...
Страница 229: ...MCT CM 229...
Страница 230: ...MCT CM 230...
Страница 231: ...MCT CM 231 Analog I O Card...
Страница 232: ...MCT CM 232...
Страница 233: ...MCT CM 233 Digital Input Card...
Страница 234: ...MCT CM 234...
Страница 235: ...MCT CM 235 Digital Output Card...
Страница 236: ...MCT CM 236...
Страница 237: ...MCT CM 237 Dual Communications Card Barcode and Remote Display Communication Cartridges...
Страница 238: ...MCT CM 238 A 5 Power Supply Specifications...
Страница 239: ...MCT CM 239...
Страница 240: ...MCT CM 240 A 6 Power On Delay Relay Specifications GE1A C10HA110...
Страница 241: ...MCT CM 241...