PM-PRO POWER CONDITIONER/MONITOR

9

Symptom:
Possible Cause:
Action Needed:

Symptom:
Possible Cause:
Action Needed:

Symptom:
Possible Cause:
Action Needed:

Symptom:
Possible Cause:

Action Needed:

PROTECTION OK Indicator not lit.
Protection devices are damaged.
Factory Service.

Ground OK Indicator not lit.
No building ground, bad outlet.
Locate good ground, run ground wire.

Flashing voltmeter display.
Input voltage is marginally high or marginally low.
Correct line voltage. Consider installing a Furman voltage
regulator.

EXTREME VOLTAGE Indicator is flashing.
Input voltage is extremely high or extremely low, causing power
to the PM-PRO's outlets to be shut down.
Correct line voltage. Consider installing a Furman voltage
regulator.

Effects of Lightning

     Lightning is a natural phenomenon of overwhelming force that represents the
most difficult circumstance faced by a power protection product. The degree of
protection a PM-PRO can offer depends on the intensity of the strike. If lightning
strikes a distant power line and causes a relatively small disturbance to reach your
location, the spike suppressors in the PM-PRO will absorb the excess voltage in-
visibly and harmlessly. However, if lightning strikes the actual building where the
PM-PRO is installed (or somewhere very nearby), some damage may be unavoid-
able due to the extremely high voltage and current present. If this does occur, most
likely damage will be limited to the PM-PRO itself and will affect only certain spike
suppression components (called varistors or MOV's.) In this "suicide" mode, the
PM-PRO may sustain minor damage but generally will protect all equipment plugged
into it from much more serious and costly damage as long as that equipment is
properly grounded. Proper grounding requires the use of three-prong AC cords,
and that the building's outlets are actually grounded to earth as specified by the
National Electric Code.

     Any PM-PRO known to have taken a direct lightning hit should be checked by a
qualified technician or the Furman factory to determine whether the MOV's need
replacement. (If the PROTECTION OK indicator is not lit, there is definitely some
damage. Some spike suppression capability may still be available by MOV Bank
#2, but there is no guarantee of this.)

     For optimum protection, you should not rely exclusively on the PM-PRO to pro-
tect against a direct lightning hit. The first line of defense against lightning should
be a lightning arrestor installed on your building's electrical service entrance. If your
building does not have one, contact your local power company or a contractor to
have one installed.

Содержание PM-PRO

Страница 1: ...FURMAN FURMAN FURMAN FURMAN PRO SERIES Power Conditioner Monitor MODELS PM PRO PM PRO E Owner s Manual 3 9844 1998 FURMAN SOUND INC 960112 1407...

Страница 2: ...TVSS rating 400V peak L N 680V peak L G N G 1 nanosecond 11 000 amps 8 x 20mS pulse 550 joules total Differential mode Greater than 40 dB Common mode greater than 60 dB both 1 to 200 MHz 1 75 4 45 cm...

Страница 3: ...uctions for future reference 2 The PM PRO should not be used near water for example near a bathtub washbowl kitchen sink laundry tub in a wet basement near a swimming pool etc 3 The PM PRO should be s...

Страница 4: ...ified service personnel when a The power supply cord or the plug has been frayed kinked or cut b Objects have fallen or liquid has spilled into the unit c The PM PRO has been exposed to rain or other...

Страница 5: ...on can safely absorb and dissipate large spikes from nearby light ning strikes and other sources up to 11 000 amps across any wiring mode hot neutral hot ground or neutral ground as well as highly att...

Страница 6: ...220V where 120V is expected The PM PRO senses voltages that are so high or low that operation would be impossible and shuts the power down before damage can occur For the PM PRO the cutoff voltages a...

Страница 7: ...e power from generators use long extension cords travel internationally or are in an area prone to brownouts you may benefit from the use of one of Furman s AC Line Voltage Regulators LED AMMETER This...

Страница 8: ...lowing chart summarizes how the PM PRO s voltmeter responds to input voltages from extremely low to extremely high AC VOLTS 90 100 110 120 128 Mains Below 80V 80 90 90 104 106 108 110 120 122 124 126...

Страница 9: ...the actual building where the PM PRO is installed or somewhere very nearby some damage may be unavoid able due to the extremely high voltage and current present If this does occur most likely damage w...

Страница 10: ...rization from Furman Furman s liability under this warranty is limited to repair or replace ment of the defective unit Furman will not be responsible for incidental or consequential damages result ing...

Страница 11: ...PM PRO POWER CONDITIONER MONITOR 11...

Страница 12: ...Voltage Regulator 30A 220 230 240V AC Line Voltage Regulator 30A 24 230 220V N America Use AC Line Voltage Regulator 30A 120V Worldwide Use On Line Uninterruptible Power Supply 1KVA Power Distro 100A...

Отзывы: