18
F1000-UPS OWNER’S MANUAL
SPECIFICATIONS
INPUT
Voltage:
85 – 137 Vac
Frequency:
57 – 63 Hz
AC POWER
Surge Protection:
Non-sacrificial
SMP (Series Multi-Stage Protection)
Current Rating:
12 A
Overvoltage Shutoff, fast rise:
150 ± 5 V
Overvoltage Shutoff, slow rise:
132 ± 5 V
Undervoltage Shutoff:
90 ± 5 V
Noise Attenuation:
10 dB @ 10kHz, 40 dB @ 100 kHz, 50 dB @ 500kHz
Linear Attenuation Curve:
From 0.05 - 100 Ohms line impedance
Automatic Voltage Regulation,
Sensitive Mode Capture Range:
99 – 135 V
Automatic Voltage Regulation,
Sensitive Mode Output Range:
120 ± 5%
Automatic Voltage Regulation,
Standard Mode Capture Range:
94 – 142 V
Automatic Voltage Regulation,
Standard Mode Output Range:
120 ± 10%
UPS OUTPUT
Voltage:
120 ± 5 V Simulated Sine Wave
Frequency:
60 Hz ± 1%
UPS Output Capacity:
1000VA, 600W @ 0.6pf
UPS Backup Time:
3 minutes at full load
Transfer Time:
< 10ms
DIMENSIONS
Product:
4” H x 17” L x 13” W (w/feet)
3.5” H x 17” L x 13” W (w/o feet)
Weight:
36 lbs.