10
Tes
�ng and t
r
oubl
e
shoo�ng
The mo
s
t important factor f
or s
a
�s
factor
y
e
xplosion p
rot
ec�on is th
at the gr
ounding of the equipme
n
t is
in good c
ondi�on. Check this by m
ea
suring the
re
sis
t
ance with an accu
rate ohmmet
er b
etween the
gr
ound
c
onnec�ons
a
t the b
rac
k
et
/
c
onnec�on
to the e
x
tr
ac�on duct and suc�on h
ead. The re
sis
tance
b
etw
een the suc�on h
ead and the gr
ound
c
onnec�on/air duct mus
t not e
x
ceed 100
Ω
.
The re
sis
tance v
alue should be docume
nted prefer
ably in a log book
to facilitate iden
�
f
ying a
deteriora
�on of the
e
xplosion p
rot
ec�on.
If the re
sis
t
ance is no�c
e
ably highe
r
, the
rea
son
f
or this must be
f
ound by m
ea
suring the
re
sis
tance
b
etween the c
onnec�on
t
o the equipme
n
t's g
r
ound and
at di
ff
erent point
s along the arm, s
t
ar�ng with
the suc�on h
ead and
s
tep
by s
tep in towar
ds the
a
�
achment. The f
ault sou
rce wi
ll be lo
cated a
s a
re
sult.
Replace def
ec�
ve component
s with n
ew
, original s
pare part
s. Whe
re ther
e is the slig
hte
st doubt,
contact
your n
eare
s
t dealer or head o
ffice.
In the event of re
duc
e
d suc�on
cap
acity: check th
a
t damper is not clos
e
d, th
at all c
onnec�ons a
r
e �g
ht
and that the f
an is in a s
a
�s
factor
y
c
ondi�on.
Log book
for mea
suring
resistance
Re
sis
t
ans (
Ω
)
Date
Date
Date
Re
sis
t
ans (
Ω
)
Re
sis
t
ans (
Ω
)