background image

Questions?  Please Contact Your Local Manufacturer’s Representative

Hydronic-PURE-Control-UserManual-211214

 

TABLE OF CONTENTS

0-1

Introduction 1-1

Overview .............................................................................................................. 1-2
Warnings & Cautions ............................................................................................ 1-2
Disclaimers and Local Codes ................................................................................ 1-2

Installation 2-1

Overview .............................................................................................................. 2-2
Control Display Hardware..................................................................................... 2-2
Graphical Icon Reference Menu ........................................................................... 2-5

Control Menus 

3-1

Overview .............................................................................................................. 3-2
Boiler Control Menu ............................................................................................. 3-2

BOILER STATUS SCREEN ..............................................................................................................3-3

SAFETY DEVICE STATUS SCREEN .................................................................................................3-7

OPERATOR CONTROL ...................................................................................................................3-9

BOILER HISTORY ........................................................................................................................3-11

ALARM HISTORY ........................................................................................................................3-12

MAINTENANCE LOG ...................................................................................................................3-13

ISOLATION VALVES .....................................................................................................................3-14

PRIMARY (BOILER) PUMP CONTROL ........................................................................................3-16

SECONDARY (SYSTEM) PUMP CONTROL ..................................................................................3-18

Lead/Lag Menu .................................................................................................. 3-22

LEAD/LAG STATUS .....................................................................................................................3-24

LEAD/LAG CONFIGURATION ......................................................................................................3-26

HYDRONIC PARALLEL LEAD/LAG SEQUENCE ...........................................................................3-27

PID Control Menu and Boiler Modifiers .............................................................. 3-28

DELTA T PROTECTION (EDR+ BOILERS ONLY) ..........................................................................3-29

VENTING LIMITATION  ...............................................................................................................3-30 

LOCAL PID ..................................................................................................................................3-31

LOW FIRE HOLD..........................................................................................................................3-32

COLD START ................................................................................................................................3-33

FREEZE PROTECTION .................................................................................................................3-34

OUTLET MONITORING ................................................................................................................3-35

Setpoint Menu ................................................................................................... 3-36

SETPOINT CONFIGURATION.......................................................................................................3-36

OUTDOOR RESET ........................................................................................................................3-38

BMS ANALOG .............................................................................................................................3-39

Scheduling Menu ............................................................................................... 3-41 
Trending Screen.................................................................................................. 3-43
Admin Menu ...................................................................................................... 3-44

USER CONFIGURATION ..............................................................................................................3-44

SYSTEM CONFIGURATION .........................................................................................................3-45 

AUXILIARY  CONFIGURATION ....................................................................................................3-46

DOMESTIC HOT WATER CONFIGURATION .................................................................................3-47

UNIVERSAL DATA CONFIGURATION ..........................................................................................3-49 

LOCAL BOILER NETWORK STATUS ............................................................................................3-50 

BMS NETWORK STATUS .............................................................................................................3-51

SYSTEM DIAGNOSTICS MENU ...................................................................................................3-52

CONTROLS DIAGNOSTICS ..........................................................................................................3-52

CALL FOR HEAT DIAGNOSTICS ...................................................................................................3-53

SENSOR DIAGNOSTICS ...............................................................................................................3-53 

LEAD/LAG DIAGNOSTICS ...........................................................................................................3-54

Downloading a Program Update 

4-1

Overview .............................................................................................................. 4-2
Verifying which hardware is installed in the boiler ............................................. 4-2
Preparing the software on a flash drive ............................................................... 4-2
Performing the Update ........................................................................................ 4-6

Preparing for Lead/Lag Operation 

5-1

Overview .............................................................................................................. 5-2
Wiring the Boilers for Lead/Lag Operation .......................................................... 5-2
Configuring the PLC for Lead/Lag Operation ....................................................... 5-2

Exporting Data using the File Manager 

6-1

Overview .............................................................................................................. 6-2
Taking a Snapshot ................................................................................................ 6-5
Taking a Screenshot ............................................................................................. 6-7

BMS Integration 

7-1

Overview .............................................................................................................. 7-2
Wiring ................................................................................................................... 7-2
Hydronic PURE Control™ Settings ........................................................................ 7-2
Wiring/Setup for a Protonode with the Hydronic PURE Control™ ....................... 7-2

 WIRING ........................................................................................................................................7-2

Hydronic PURE Control™ BMS Points List ............................................................. 7-3
Hydronic PURE Control™ Alarm List ..................................................................... 7-7

Содержание HYDRONIC PURE CONTROL Endura

Страница 1: ...ial National Board Number Model Fulton Order Owner Site Name Date Hydronic PURE Control UserManual 211214 Endura EDR Condensing Hydronic Boilers 750 000 2 000 000 BTU HR Endura EDR Condensing Hydronic...

Страница 2: ......

Страница 3: ...SetpointMenu 3 36 SETPOINTCONFIGURATION 3 36 OUTDOORRESET 3 38 BMSANALOG 3 39 SchedulingMenu 3 41 TrendingScreen 3 43 AdminMenu 3 44 USERCONFIGURATION 3 44 SYSTEMCONFIGURATION 3 45 AUXILIARY CONFIGUR...

Страница 4: ...FultonGroupN A Inc 2020 TABLEOFCONTENTS Hydronic PURE Control UserManual 211214 0 2...

Страница 5: ...tYourLocalManufacturer sRepresentative 1 1 INTRODUCTION INTRODUCTION 1 HARDWAREANDNAVIGATION 2 CONTROLMENUS 3 DOWNLOADINGAPROGRAMUPDATE 4 PREPARINGFORLEAD LAGOPERATION 5 EXPORTINGDATAUSINGTHEFILEMANAG...

Страница 6: ...erved to prevent damage or destruction of equipment or loss of operating effectiveness AllWarnings and Cautions are for reference and guidance purposes and do not substitute for required professional...

Страница 7: ...rLocalManufacturer sRepresentative 2 1 HARDWAREANDNAVIGATION INTRODUCTION 1 HARDWAREANDNAVIGATION 2 CONTROLMENUS 3 DOWNLOADINGAPROGRAMUPDATE 4 PREPARINGFORLEAD LAGOPERATION 5 EXPORTINGDATAUSINGTHEFILE...

Страница 8: ...plier s instructions If you cannot reach your gas supplier call the fire department A qualified installer service agency or the gas supplier must perform installation and service Overview Hydronic PUR...

Страница 9: ...materials and other dangers In order to meet warranty conditions ensure all appropriate maintenance activities are performed The information contained in this manual is based on EDR version 1 3 7 9 a...

Страница 10: ...ing conduct and strict adherence to applicable jurisdictional professional codes or regulations WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch Donotus...

Страница 11: ...APHICAL ICON REFERENCE MENU Button Function Returns to the parent category Tap to display information based on the screen currently selected Green No alarm condition Tap to see Alarm History Yellow Wa...

Страница 12: ...FultonGroupN A Inc 2020 HARDWAREANDNAVIGATION Hydronic PURE Control UserManual 211214 SECTION2 2 6 PAGE LEFT INTENTIONALLY BLANK...

Страница 13: ...tYourLocalManufacturer sRepresentative 3 1 CONTROLMENUS INTRODUCTION 1 HARDWAREANDNAVIGATION 2 CONTROLMENUS 3 DOWNLOADINGAPROGRAMUPDATE 4 PREPARINGFORLEAD LAGOPERATION 5 EXPORTINGDATAUSINGTHEFILEMANAG...

Страница 14: ...res All information in this addendum is for reference and guidance purposes and does not substitute for required professional training conduct and strict adherence to applicable jurisdictional profess...

Страница 15: ...ing conduct and strict adherence to applicable jurisdictional professional codes or regulations Follow all proper lockout tagout procedures for service Before beginning any service ensure area is free...

Страница 16: ...he boiler will take a normal place in the Lead Lag sequence after the next call for heat Boilers must be connected and configured for the Lead Lag feature in order to be assigned a Lead Lag position I...

Страница 17: ...ded Temperature Field wiring for 0 10VDC TB4 A3 TB4 A4 Field wiring for 4 20mA at TB4 A1 TB4 A2 40024 INT16 Read Boiler Start 0 0 100 0 F How far below setpoint the boiler will receive a call for heat...

Страница 18: ...tpoint if this signal is lost RTD Field Wired to customer connec tions TB4 T5 TB4 T6 or Provided through BMS connection 40025 INT16 Read Write System Supply 50 00 250 00 F Optional RTD sensor for Syst...

Страница 19: ...limit is the first device in the safety circuit open and should be the first device addressed during troubleshooting as many of the safeties are wired in series The boiler specific electrical wiring...

Страница 20: ...ition Factory wired OTC between terminals 5 6 Part of the initial Burner Switch circuit that powers the LMV3 terminal X5 03 1 40034 INT16 Read On Off Switch Clear push button switch on the front of th...

Страница 21: ...activities are performed OperatorControl This screen is used for multiple functions Start Stop Deviations Anti CycleTimer and Manual Burner Control The start and stop deviations instruct the burner wh...

Страница 22: ...y or the gas supplier must perform installation and service Parameter Name Range Units Factory Default Description Wiring Modbus Register Boiler Status See Boiler Status Screen Control Modulation Modu...

Страница 23: ...vities are performed BoilerHistory Provides information on the operation of the boiler including run hours run cycles where the boiler has been modulating and efficiency calculations Thermal efficienc...

Страница 24: ...equirements and procedures All information in this addendum is for reference and guidance purposes and does not substitute for required professional training conduct and strict adherence to applicable...

Страница 25: ...e to applicable jurisdictional professional codes or regulations Follow all proper lockout tagout procedures for service Before beginning any service ensure area is free of combustible materials and o...

Страница 26: ...uirements and procedures All information in this addendum is for reference and guidance purposes and does not substitute for required professional training conduct and strict adherence to applicable j...

Страница 27: ...C3 40052 INT16 Read Manual Open Manual Close N A N A N A Only displayed in Manual Control Allows user input to open close the valve Field Wiring to TB4 C1 TB4 C2 and or TB4 C3 N A Close Delay Timer 0...

Страница 28: ...alified and fully understand all requirements and procedures All information in this addendum is for reference and guidance purposes and does not substitute for required professional training conduct...

Страница 29: ...on Field Wiring to TB4 C4 and TB4 C5 Pumps require a sepa rate power source Power provided to C4 will be seen on C5 Dry contact depend ing on the control mode and or boiler operation 40055 INT16 Read...

Страница 30: ...nd guidance purposes and does not substitute for required professional training conduct and strict adherence to applicable jurisdictional professional codes or regulations WHAT TO DO IF YOU SMELL GAS...

Страница 31: ...rent Value Delta T requires both system supply header and system return header temperature sensors to be field wired Delta P requires a 4 20mA signal from a field wired differential pressure sensor TB...

Страница 32: ...ny appliance Do not touch any electrical switch Donotuseanyphoneinyourbuilding Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach you...

Страница 33: ...are performed Delta P Scale Low 0 0 1000 0 Pres sure 0 0 Low 4mA scaling for Delta P input Delta P requires a 4 20mA signal from a field wired differential pressure sensor TB4 A5 and TB4 A6 not provi...

Страница 34: ...the gas supplier s instructions If you cannot reach your gas supplier call the fire department A qualified installer service agency or the gas supplier must perform installation and service Lead LagMe...

Страница 35: ...nce to applicable jurisdictional professional codes or regulations Follow all proper lockout tagout procedures for service Before beginning any service ensure area is free of combustible materials and...

Страница 36: ...e to applicable jurisdictional professional codes or regulations WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch Donotuseanyphoneinyourbuilding Immedia...

Страница 37: ...the Originator Ethernet Cable Connection be tween boilers for Lead Lag Field Wired N A Lead Lag Status 0 Offline 1 Alarm 2 Switch Off 3 Standby 4 Call for Heat 5 Modulating N A Status from each boiler...

Страница 38: ...MELL GAS Do not try to light any appliance Do not touch any electrical switch Donotuseanyphoneinyourbuilding Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instru...

Страница 39: ...riginator position is assigned to the boiler with the lowest IP address or the first boiler to be brought into the network The Network Originator is simply the boiler that is in charge of the Lead Lag...

Страница 40: ...ue to stage on additional Lag Boilers that are available based on the user defined PID and Lag Boiler DelayTime When a Lag Boiler comes online the Lead Boiler firing rate will be reduced so that the l...

Страница 41: ...ensure all appropriate maintenance activities are performed DeltaTProtection EDR BoilersOnly This modifier is mandatory and cannot be turned off or configured at the Fulton Control As the deltaT limit...

Страница 42: ...n this addendum is for reference and guidance purposes and does not substitute for required professional training conduct and strict adherence to applicable jurisdictional professional codes or regula...

Страница 43: ...s or regulations Follow all proper lockout tagout procedures for service Before beginning any service ensure area is free of combustible materials and other dangers In order to meet warranty condition...

Страница 44: ...s addendum is for reference and guidance purposes and does not substitute for required professional training conduct and strict adherence to applicable jurisdictional professional codes or regulations...

Страница 45: ...temperature based and will hold the boiler at low fire until those conditions are met For system startups i e when the loop is cold this will allow the boiler to warm up slowly and help prevent condit...

Страница 46: ...as supplier s instructions If you cannot reach your gas supplier call the fire department A qualified installer service agency or the gas supplier must perform installation and service FreezeProtectio...

Страница 47: ...priate maintenance activities are performed OutletMonitoring Useful in Lead Lag setups and unbalanced and or low flow conditions the Outlet monitoring will drive the boiler firing rate to low fire if...

Страница 48: ...for required professional training conduct and strict adherence to applicable jurisdictional professional codes or regulations WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touc...

Страница 49: ...he boiler if the OAT is above the selected value RTD Field Wired to customer connection on the back of the boiler TB4 T5 TB4 T6 N A Outdoor Air Cutoff 0 0 200 0 F 100 0 The boiler will no longer re ce...

Страница 50: ...liance Do not touch any electrical switch Donotuseanyphoneinyourbuilding Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas...

Страница 51: ...on what source is selected 40024 INT16 Read Minimum Setpoint 40 0 185 0 F 80 0 Absolute minimum setpoint that the unit will control to regard less of source or scaling Reference only Must be changed f...

Страница 52: ...s or regulations WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch Donotuseanyphoneinyourbuilding Immediately call your gas supplier from a neighbor s ph...

Страница 53: ...low all proper lockout tagout procedures for service Before beginning any service ensure area is free of combustible materials and other dangers In order to meet warranty conditions ensure all appropr...

Страница 54: ...ctional professional codes or regulations WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch Donotuseanyphoneinyourbuilding Immediately call your gas supp...

Страница 55: ...ndingScreen Allows users to view current and past trending data when available to the Fulton Controller TheTrending data is continuously recorded by the control and can be enabled or disabled by the o...

Страница 56: ...ualified and fully understand all requirements and procedures All information in this addendum is for reference and guidance purposes and does not substitute for required professional training conduct...

Страница 57: ...ime 00 00 23 59 HH MM Press on the Clock for a 24hr time selection for hours minutes Local Ethernet IP Address 192 168 1 100 192 168 1 109 N A 10 possible IP addresses for each boiler on the Lead Lag...

Страница 58: ...If you cannot reach your gas supplier call the fire department A qualified installer service agency or the gas supplier must perform installation and service Auxiliary Configuration Used for advanced...

Страница 59: ...is free of combustible materials and other dangers In order to meet warranty conditions ensure all appropriate maintenance activities are performed DomesticHotWaterConfiguration Accessible only when D...

Страница 60: ...tuseanyphoneinyourbuilding Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department A qualified...

Страница 61: ...ther Hardwire BMS or shared Determines where certain information is coming from Can be different for each boiler and must be set up individually Local Network Provider is selected for a hardwired conn...

Страница 62: ...ce Do not install operate service or repair any component of this equipment unless you are qualified and fully understand all requirements and procedures All information in this addendum is for refere...

Страница 63: ...MSEnableOverrideprovides a way to satisfy the BMS enable Network or Dry Contact without needing to send a signal This can be used if switching quickly to Local Standalone control orTroubleshooting pur...

Страница 64: ...equired professional training conduct and strict adherence to applicable jurisdictional professional codes or regulations WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any...

Страница 65: ...vice Before beginning any service ensure area is free of combustible materials and other dangers In order to meet warranty conditions ensure all appropriate maintenance activities are performed CallFo...

Страница 66: ...or repair any component of this equipment unless you are qualified and fully understand all requirements and procedures All information in this addendum is for reference and guidance purposes and doe...

Страница 67: ...ocalManufacturer sRepresentative 4 1 DOWNLOADINGAPROGRAMUPDATE INTRODUCTION 1 HARDWAREANDNAVIGATION 2 CONTROLMENUS 3 DOWNLOADINGAPROGRAMUPDATE 4 PREPARINGFORLEAD LAGOPERATION 5 EXPORTINGDATAUSINGTHEFI...

Страница 68: ...ce Overview The program update for the PURE Control is broken down into three sections Verifying what hardware is installed in the boiler Preparing the software on a flash drive and Performing the upd...

Страница 69: ...sdictional professional codes or regulations Follow all proper lockout tagout procedures for service Before beginning any service ensure area is free of combustible materials and other dangers In orde...

Страница 70: ...urposes and does not substitute for required professional training conduct and strict adherence to applicable jurisdictional professional codes or regulations WHAT TO DO IF YOU SMELL GAS Do not try to...

Страница 71: ...ce purposes and does not substitute for required professional training conduct and strict adherence to applicable jurisdictional professional codes or regulations Follow all proper lockout tagout proc...

Страница 72: ...to applicable jurisdictional professional codes or regulations WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch Donotuseanyphoneinyourbuilding Immediate...

Страница 73: ...o as a firmware upgrade Click on Upgrade PLC in the middle of the screen Verify that you would like to continue with the upgrade process by selecting Upgrade The upgrade process could take up to 20 mi...

Страница 74: ...stand all requirements and procedures All information in this addendum is for reference and guidance purposes and does not substitute for required professional training conduct and strict adherence to...

Страница 75: ...materials and other dangers In order to meet warranty conditions ensure all appropriate maintenance activities are performed 13 Press and hold the upper right corner of the screen for 3 seconds Select...

Страница 76: ...uidance purposes and does not substitute for required professional training conduct and strict adherence to applicable jurisdictional professional codes or regulations WHAT TO DO IF YOU SMELL GAS Do n...

Страница 77: ...alManufacturer sRepresentative 5 1 PREPARINGFORLEAD LAGOPERATION INTRODUCTION 1 HARDWAREANDNAVIGATION 2 CONTROLMENUS 3 DOWNLOADINGAPROGRAMUPDATE 4 PREPARINGFORLEAD LAGOPERATION 5 EXPORTINGDATAUSINGTHE...

Страница 78: ...reach your gas supplier call the fire department A qualified installer service agency or the gas supplier must perform installation and service Overview Setting up Lead Lag on the Endura requires the...

Страница 79: ...nsure area is free of combustible materials and other dangers In order to meet warranty conditions ensure all appropriate maintenance activities are performed 2 Check the box for Lead Lag on the right...

Страница 80: ...ional training conduct and strict adherence to applicable jurisdictional professional codes or regulations WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical swi...

Страница 81: ...service Before beginning any service ensure area is free of combustible materials and other dangers In order to meet warranty conditions ensure all appropriate maintenance activities are performed 9...

Страница 82: ...procedures All information in this addendum is for reference and guidance purposes and does not substitute for required professional training conduct and strict adherence to applicable jurisdictional...

Страница 83: ...Manufacturer sRepresentative 6 1 EXPORTINGDATAUSINGTHEFILEMANAGER INTRODUCTION 1 HARDWAREANDNAVIGATION 2 CONTROLMENUS 3 DOWNLOADINGAPROGRAMUPDATE 4 PREPARINGFORLEAD LAGOPERATION 5 EXPORTINGDATAUSINGTH...

Страница 84: ...rofessional training conduct and strict adherence to applicable jurisdictional professional codes or regulations WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electric...

Страница 85: ...regulations Follow all proper lockout tagout procedures for service Before beginning any service ensure area is free of combustible materials and other dangers In order to meet warranty conditions en...

Страница 86: ...for required professional training conduct and strict adherence to applicable jurisdictional professional codes or regulations WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not tou...

Страница 87: ...able jurisdictional professional codes or regulations Follow all proper lockout tagout procedures for service Before beginning any service ensure area is free of combustible materials and other danger...

Страница 88: ...in this addendum is for reference and guidance purposes and does not substitute for required professional training conduct and strict adherence to applicable jurisdictional professional codes or regu...

Страница 89: ...other dangers In order to meet warranty conditions ensure all appropriate maintenance activities are performed 5 Double tapping on a folder will navigate to the subfolders and files 6 To the right of...

Страница 90: ...ration manual without notice Do not install operate service or repair any component of this equipment unless you are qualified and fully understand all requirements and procedures All information in t...

Страница 91: ...YourLocalManufacturer sRepresentative 7 1 BMSINTEGRATION INTRODUCTION 1 HARDWAREANDNAVIGATION 2 CONTROLMENUS 3 DOWNLOADINGAPROGRAMUPDATE 4 PREPARINGFORLEAD LAGOPERATION 5 EXPORTINGDATAUSING THEFILEMAN...

Страница 92: ...electrical switch Donotuseanyphoneinyourbuilding Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire d...

Страница 93: ...81 Atmospheric Pressure Test 82 Filling Test Space 83 Gas Pressure Test 90 Gas Shortage Waiting Time 91 Limit String Open N A 40001 R Boiler Control Status INT16 0 Waiting 1 Disabled 2 Not Available 3...

Страница 94: ...ircuit Short 12 E12 Heater Circuit Short N A 40010 R VFD Command INT16 0 0 95 0 Note 1 Hz 40011 R VFD Feedback EDR Only INT16 0 0 95 0 Note 1 Hz 40012 R Fan Calculated RPM INT32 0 0 5500 0 Note 1 RPM...

Страница 95: ...R Customer Interlock 1 INT16 0 Fault 1 No Fault N A 40040 R Customer Interlock 2 INT16 0 Fault 1 No Fault N A 40041 R Secondary Low Water INT16 1 Fault 0 No Fault N A 40042 R Boiler Run Hours UINT32...

Страница 96: ...N A 40082 R Boiler 6 LL Status INT16 N A 40083 R Boiler 7 LL Status INT16 N A 40084 R Boiler 8 LL Status INT16 N A 40085 R Boiler 9 LL Status INT16 N A 40086 R Boiler 10 LL Status INT16 N A 40087 R Bo...

Страница 97: ...moved in order to use this network enable point Endura AlarmList Information on Alarm Info Screen Alarm Index Alarm Name Alarm Screen Description Alarm Screen Solution Error Code Error Diagnostic Code...

Страница 98: ...ous light dur ing startup air pres sure POC prevention of startup 4 70 LMV 18 Extraneous light Extraneous light dur ing startup combus tion pressure POC prevention of startup 4 82 LMV 19 Extraneous li...

Страница 99: ...ving test V2 leaking Check if the valve on the burner side is leaking Check if pressure switch for the leakage test is closed when there is gas pressure Check wiring and short circuit 12 83 LMV 31 POC...

Страница 100: ...POC closed sw ver sion V02 00 Check wiring Check if the valve s closing con tact opens when valve is controlled 21 1 LMV 45 Pmax POC POC open preven tion of startup SW version V02 00 Check wiring and...

Страница 101: ...ange Safety loop burner flange combustion pressure POC pre vention of startup 22 81 LMV 59 Safety loop burner flange Safety loop burner flange extraneous light combustion pressure POC prevention of st...

Страница 102: ...ion is acti vated ParNo 530 the default load for inter rupted communication to building automation ParNo 148 149 must not be set to invalid 60 2 LMV 73 Fuel Change Fuel 0 no error change to fuel 0 61...

Страница 103: ...26 LMV 91 Fuel air control Please contact your representative for information regarding this alarm be sure to provide the LMV alarm code and diag nostic code 75 0 LMV 95 Fuel air control Internal err...

Страница 104: ...lines check cable routing improve EMC 82 6 LMV 105 Error during stan dardization Invalid standardized speed The standardized speed measured does not lie in the permissible range 1 Motor turns too slow...

Страница 105: ...ot standardized Make standardized 82 255 LMV 115 Speed error VSD Please contact your representative for information regarding this alarm be sure to provide the LMV alarm code and diag nostic code 83 0...

Страница 106: ...t your representative for information regarding this alarm be sure to provide the LMV alarm code and diag nostic code 96 0 LMV 144 Error relay super vision Please contact your representative for infor...

Страница 107: ...se contact your representative for information regarding this alarm be sure to provide the LMV alarm code and diag nostic code 110 0 LMV 157 Power supply undervoltage Power supply under voltage Mains...

Страница 108: ...201 Flame failure test Please contact your representative for information regarding this alarm be sure to provide the LMV alarm code and diag nostic code 150 0 LMV 206 Trim function Error Start preven...

Страница 109: ...s may be an indication of an incorrect setting of the trim function or VSD PWM blower curve 156 11 LMV 216 Trim function Error Analog value Standby 1 Check whether a current setting of 12 mA is availa...

Страница 110: ...227 Internal error Please contact your representative for information regarding this alarm be sure to provide the LMV alarm code and diag nostic code 169 0 LMV 228 Internal error Please contact your r...

Страница 111: ...emperature limit has been reached This is a manual reset device 1001 0 PLC 242 O2 Out of Range The O2 was out of the allowable range Check O2 sensor opera tion 1002 0 PLC 243 PLC Limit Trip Secondary...

Страница 112: ...bounced off its low fire delta t limit more than 5 times in a 30 minute period 252 BMS Communica tion Failure Communication to the BMS failed 1012 0 PLC 253 LMV Communica tion Failure Communication t...

Страница 113: ...ck O2 sensor opera tion 1021 0 PLC Just a warn ing The O2 board failed to register a minimum of 20 00 O2 while in pre purge This warning is just letting the customer know there may be an issue with th...

Страница 114: ...PAGE INTENTIONALLY LEFT BLANK...

Страница 115: ...nsfer innovators No part of this Addendum manual may be reproduced in any form or by any means without permission in writing from Fulton Group N A Inc Fulton BoilerWorks Inc Fulton Heating Solutions I...

Отзывы: