6. INSTALLATION PROCEDURE

a)

Cut the sheet where the thermostat will be fixed, with a dimension of 72 x 29 mm - Figure VII;

b)

Remove the side latches (J - Figure V): for this, press the central elliptical part (with the Full Gauge 

Controls logo) and slide the latch backward;

c)

Insert the thermostat in the 72 x 29 mm housing socket, from the outside in;

d)

Reinstall the latches (J) to fix the thermostat in the housing;

e)

Do the electrical wiring as described in item 5.3;

f)

Set the parameters as described in Chapter 7.

Protective vinyl (K) - Figure VI: 

Protects instruments installed in locations subject to splashing water, as in 

commercial refrigerators.
This adhesive vinyl is with the instrument, inside the packing. 
Do the application after finishing the electrical connections.

a)

 Remove the side latches (J);

b)

 Remove the protective paper;

c) 

Apply the vinyl (K) over the entire top, folding the flaps, as indicated by the arrows - Figure VI.

d) 

Reinstall the latches (J).

NOTE: The protective vinyl is transparent and does not cover the wiring diagram of the controller.

7. SET POINT AND PARAMETER SETTING

A - 

Led Relay

B - 

SET key

C - 

Display

D - 

Lower limit of operating scale

E - 

Upper limit of operating scale

Signs

- Led "Relay": when lit, it indicates that the NA contact (terminal "11" of the thermostat) is energized.
-  When  the                  indication  appears  on  display,  it  indicates  that  the  sensor  is  disconnected  or  the 
temperature is out of the specified range. 

AHI

 means high temperature alarm. 

ALO

 means low temperature alarm. 

SOF

 means software, and the number that appears next to it represents the version of the controller. 

7.1 Set point setting (control temperature)

Set point          , or control temperature, is the right temperature to keep for a controlled environment, ie the 
temperature at which the output will be disconnected.

a)

 Press key         for 2 sec. and           will appear on display. Release the key;

b)

 After 2 seconds, the currently set control temperature will appear;

c)

 Press          to modify the value. 

NOTE 1: For each stroke of the       , key, the value increases 0.1°C until the end of the scale (105°C) or to 
the maximum limit specified in the parameter setting           (see item 7.2.2).

Then, the value returns to the beginning of the scale (- 50°C) or to the minimum limit specified in the 
parameter setting           

(see item 7.2.2) .

 

NOTE 2: Keeping the         key pressed, the value increment on display is accelerated.

d)

 After setting the control temperature, wait 4 sec. and the value will be recorded.

SET

SET

SET

7.2 Parameter setting

7.2.1 

NOTE: Access to all parameters is protected by the           access code.

For detailed information, see item 7.2.4. ‘‘Entering the access code’’. 

Table of parameters

7.2.2 Parameter description

           

 Mode of operation 

Determines the mode of operation according to the purpose of the installation: 
0 = cooling     1 = heating
            

Temperature differential (hysteresis)

It is the value of the difference in temperature to reactivate the "Relay" control output. 
In other words, the difference between the Set point temperature         and the temperature at which the 
thermostat relay will be reactivated. The difference            will be:

*Refrigeration (Operation mode           ="0"): 

For a temperature higher than that of the Set point         :  

the relay on when the temperature is higher than            +            and off when less than            .

*Heating (Operation mode          ="1"): 

For a temperature lower than that of the set point           : the relay 

on when the temperature is lower than            -            and off when higher than            .

Example (Heating):

 If you want to turn on the output with 30°C and turn off at 35°C. Adjust the          with 

"1", the Set Point            with 35.0 and hysteresis            with 05.0.

NOTE: The setting of a very small hysteresis results in high frequency in the thermostat relay on/off cycles 
and consequently of the driven load, which may shorten the service life of these components. 

            

Minimum delay to turn on the output

This determines the minimum time during which the output will be off. The counting of the time begins when 
the output is turned off. If the output is off and you need to turn it back on right away, the relay will be triggered 
only after the end of the timing adjusted to the           delay. The goal is to avoid consecutive restarts of 
output control.
            

Offset

It allows to compensate deviations in the temperature reading. Example: when changing or altering the 
length of the sensor cables, it is suggested to take a detour to obtain a better response for the control in 
question.

NOTE: In order to correct the deviation of the sensor reading, it is necessary to use a standard thermometer, 
preferably calibrated by an approved laboratory. The driver sensor is placed alongside the standard sensor 
for a few minutes for the reading to stabilize. Then, based on the reading difference between the sensors, 
set the offset value in the Off Set function.

          

  Lower limit of the set point*

Determines minimum adjustment temperature for the set point.

            Upper limit of the Set point*

Determines maximum adjustment temperature for the set point.

NOTE 1*: Together, parameters           and           limit the thermostat control range. This scale restriction is 
intended  to  protect  the  system  and  also  safety  of  the  application,  avoiding  for  example,  be  adjusted 
temperatures outside the tolerated range.
NOTE 2: The scale capacity limits of the thermostat are represented by the items in Figure IX (X - minimum) 
and (Y - maximum). Respectively: -50°C and 105°C.

7.2.4 Entering the access code

The parameters setting (except set point) is protected by an access code          . 
To access with the code and release the setting of parameters:

a)

Keep the          key pressed for 10 seconds. The display will show the message            ; release the key     

.       ;

b)

After 2 seconds           will show on display;

c)

Press the        key until           appears on display.

NOTE: This  operation  must  be  performed  within  4  seconds,  otherwise  the  display  will  show  the  room 
temperature. In this case, restart the procedure.

7.2.5 Setting the parameters

After entering the access           code, in a maximum of 15 seconds:

a)

Press the         key as many times as necessary to select the desired parameter: OP, dF, dL, OF, Lo or Hi: 

see the parameter description in the previous item 7.2.2;

b)

After 2 seconds, the currently set value for the selected parameter will appear;

c)

Press the         key as many times as necessary to obtain the desired value for the parameter;

d)

Wait 4 sec. and the value will be recorded: the display will return to normal operation, showing the room 

temperature;

e)

Do the same for the setting of all parameters.

NOTE: After entering the access code, be careful not to leave the         key idle (not pressed) for more than 
15 seconds between the alteration of one parameter and another. If this happens,               will appear and 
access  to  settings  will  be  automatically  blocked,  requiring  you  to  enter  the  023  code  again  to  make 
alterations.

8. CONFIGURATION EXAMPLES

Case 1:

 Configuring the 

 for initial fermentation or maturation of an artisanal brewer, where 

the temperature should be between 17 º C (off) and 20 º C (on).

Case 2:

 Configuring the 

, used in a cold chamber to maintain the temperature between 6 and 

8°C.
For these cases, make the adjustments suggested in columns "Case 1" and "Case 2" of the following table.

TIC17RGTi

TIC17RGTi

PARAMETER

CASE 2

17.0

0 - COOLING

03.0

000

00.0

-50

105

06.0

0 - COOLING

02.0

000

00.0
05.0
10.0

CASE 1

SET

SET

SET

SET

SET

SET

SET

SET

SET

SET

SET

SET

FIGURE. IX

=1

=0

-50ºc

105ºc

X

ENVIRONMENTAL INFORMATION

Package:

The packages material are 100% recyclable. Just dispose it through specialized recyclers.

Products:

The  electro  components  of  Full  Gauge  controllers  can  be  recycled  or  reused  if  it  is 
disassembled for specialized companies.

Disposal:

Do not burn or throw in domestic garbage the controllers which have reached the end-of-life. 
Observe  the  respectively  law  in  your  region  concerning  the  environmental  responsible 
manner  of  dispose  its  devices.  In  case  of  any  doubts,  contact  Full  Gauge  controls  for 
assistance.

2013

Operation mode

Differential (hysteresis)

Minimum delay to turn on the output

Offset (local calibration)

Minimum set allowed to the final user 

Maximum set allowed to the final user 

0-refrig.

0.1

0

-5.0

-50

-50

1-heat.

20.0

999

5.0

105

105

-

°C

sec.

°C

°C

°C

0

2.0

0

0.0

-50

105

Description

Min

Max

Unit

Default

Fun

7.2.3 Graphical interpretation of the parameters (Figure IX )

The graph illustrates the meaning of the various parameters on the line of temperatures. 