6.3.8 Control functions shutdown

The shutdown of the control functions allows the controller to operate only as a temperature indicator, 
keeping  the  control  outputs  and  alarms  off.  The  use  of  this  feature  is  enabled  or  disabled  by  the 
shutdown function of the control functions (F56). When enabled, the control functions and alarms are 
switched  off  (

[CTRL][OFF,]

)  or  on  (

[Ctrl][ON,,]

)  in  the  quick  access  menu  through  the

 

[Ctrl]

 option. When the control functions are off, the message 

[OFF,]

is displayed alternating with 

the temperature and other messages.

6.3.9  Stage  of  the  process,  elapsed  time  and  temperature  in 

sensors S2 and S3

The  operating  status  of  the  controller  can  be  displayed  by  pressing  the 

>

  key  (short  press). A 

sequence of messages will be shown, indicating the current process, time (hh:mm) already elapsed in 
this stage, temperature in the evaporator (S2) and temperature in S3. If the sensors are disabled, their 
measurements will not be displayed.
Stages of the process:

[dEL,]

 Initial delay (delay at start of the instrument)

[Fan,]

 Fan-delay (delay for return of the fan)

[rEFr]

 Cooling

[Pre,]

 Pre-Defrost

[dEFr]

 Defrost

[dRAi]

 Drainage

[OFF,]

 Control functions off

6.3.10 Minimum and Maximum Temperature Record

The display of the minimum and maximum temperature record can be requested through the quick 
access menu or by pressing the 

<

 key while displaying the temperature. The minimum and maximum 

temperatures recorded for each sensor are displayed in sequence preceded by identification messages 

[rEg,]

[,t-1]

 for ambient sensor (S1), 

[,t-2]

 for S2 (when active) and 

[,t-3]

 for S3 (when 

active).  To  delete  the  minimum  and  maximum  recorded  values,  hold  the 

<

  button  for  2s  when 

displaying records or use the 

[CrEg]

option in the quick access menu.   The

 [rSET]

 message 

indicates that the records have been deleted.

6.3.11 Unit Selection

To select the unit in which the instrument will operate enter the 

[,F01]

 function with access code 

[,231]

  and  press  the 

/

  key.  Then,  select  the  desired  unit 

[,=C,]

  or 

[,=F,]

  using  the 

<>

keys. To confirm, press 

/

. Whenever the unit is changed, the function settings assume the 

default value, therefore needing to be reconfigured.

6.3.7 Functions Lockdown

The use of the functions lockdown provides greater safety for the instrument's operation. With it active, 
the setpoint and other parameters are visible to the user, but protected against unauthorized changes. 
To  activate  the  functions  lockdown,  access  the

[LOC,]

function  in  the  quick  access  menu.  The 

message 

[no,,]

(lockdown must be enabled and deactivated), with it on display hold down the

>

 

key for the time set for functions lockdown (F55), the activation is indicated by the message 

[LOC,] 

[On,,]

. To enable the use of this function it is necessary that the time for functions lockdown (F55) is 

set to a value greater than or equal to 15 seconds. The 

[LOC,]

 message when trying to change the 

parameters indicates that the functions lockdown is active. To deactivate it, turn the controller off and on 
again with the 

>

 key pressed. Keep the key pressed until the message 

[LOC,][OFF,]

 indicates 

unlocking 

(10 seconds)

.

6.4 ADVANCED OPERATIONS

The  functions  menu  can  be  accessed  through  the  quick  access  menu,  option 

[Func]

  or 

simultaneously  pressing 

<

  and 

>

  while  displaying  the  temperature.  To  allow  changing  the 

parameters, enter 

[,F01]

 by pressing 

/

 (short press), and using the 

<

 or 

>

 keys enter code 123 

(one hundred and twenty three). Confirm with 

/

. To modify the other functions, navigate the menu 

using the 

<

 or 

>

 keys and follow the same procedure to set them. To exit the menu and return to 

normal operation, press and hold

/

 until 

[----]

 appears. 

NOTE:

 If the functions lockdown is active when pressing the 

<

 or 

>

 keys, the controller will show the 

[LOC,]

 message on the display and will not allow the setting of parameters.

6.3.2 - Fast Freezing 

In  the  fast  freezing  mode  the  cooling  output  remains  permanently  activated,  thus  accelerating  the 
cooling or freezing process. This operating mode can be activated or deactivated in the quick access 
menu through the 

[FASt]

 option or through an external switch connected to the digital input (F49 or 

F50).  It  can  also  be  deactivated  automatically  by  time  (F15)  or  by  low  temperature  (F14).  During 
operation in the fast freezing mode, the compressor on indication flashes quickly and defrost keeps 
happening. If, when activating the fast freezing mode, the controller identifies that there is a defrost 
scheduled to start by time in this period, the defrost will be performed immediately before entering the 
fast freezing mode.

6.3.3 - Economic setpoint (SPE) 

The 

[SP-E]

  provides  the  system  with  greater  economy  by  using  more  flexible  parameters  for 

temperature  control  (F06  -  Economic  Setpoint  and  F07  -  Control  Differential).  When  active,  the 

[ECO,] 

message is displayed alternating with the temperature and other messages. The operation in 

economy mode can be activated or deactivated through the commands: 

Function

Command

Action

6.3.4 Manual defrost

The defrost process can be activated/deactivated manually in the quick access menu through the 

[defr]

option  or  the  external  switch  connected  to  the  digital  input  (F49  or  F50).  Activation  or 

deactivation will be indicated by the messages 

[defr][On,,]

 or 

[defr][OFF,]

 respectively.

6.3.5 How to determine the end of defrost by temperature

a)

 Reconfigure the listed functions at the end of the defrost to the maximum value:

- Cooling time (Interval between defrosts)

 F3=999min

- Evaporator temperature to end defrost 

F28=105°C / 221°F

- Maximum defrost time

 F23=0 (OFF)

b) 

Wait for a while until a layer of ice forms in the evaporator.

c)

 Perform a manual defrost (using the 

;

scroll key up to 

[dEFr]

 and press 

/

).

d)

 Follow the melting process.

e)

 Wait until all of the ice in the evaporator has melted to consider the process completed.

f)

 With the defrost finished, check the evaporator temperature (S2) using the 

>

 key (see section 

6.3.9).

g)

 Using the value read in S2, set the temperature for end of defrost

- Evaporator temperature for end of defrost 

F28 =Temp. S2

h)

 For safety, reset the (maximum defrost time), according to the type of defrost set. 

Eg:
- Electrical defrost (by resistance) 

F23=45min

- Hot gas defrost 

F23=20min

i)

Finally, set the cooling time (F3) at the desired value.

6.3.6 Defrost with two evaporators

With S3 configured for the 2nd evaporator (F49), the Fan output allows control of the second resistance. 
Defrost always starts with the two outputs triggered. The resistors are shut down individually as their 
evaporators reach the temperature to end defrost. With the two outputs off or having the maximum 
defrost time elapsed, the draining process is started. With these settings, all the features of the Fan are 
disregarded, including the Fan Delay process.

FAN-DELAY

COOLING

PRE-DEFROST

MAX. F33

IF F25=0

F03

F22

F31

F34

Unlock 
the indication

IF F25=1

F27

Lock the display
if enabled on F31

DEFROST

DRAINAGE

MAX. F23

F32

F28

Connection 12 Vac/dc

1

5 6 7 8

2 3 4

9

10 11 12 13 14 15 16 17

Sensor S1

D1/S3

D2

Sensor S2

CO

MP

DE

FR

FA

NS / 

DE

FR 2

24 Vac/dc

1

5 6 7 8

2 3 4

9

10

Sensor S1

D1/S3

D2

Sensor S2

Connection 24 Vac/dc

11 12 13 14 15 16 17

CO

MP

DE

FR

FA

NS / 

DE

FR 2

12 Vac/dc

6.5 TABLE OF PARAMETERS

CELSIUS

FAHRENHEIT

Min

Max

Unit

Fun

[,F01]

[,F02]

[,F03]

[,F04]

[,F05]

[,F06]

Min

Max

Unit

Access code: 123 (one hundred and twenty-three)

Delay at start (energization)

Cooling time (interval between defrosts)

Normal setpoint

Normal setpoint control differential (hysteresis)

Economic setpoint  

 

 

Loads supply

Initial delay
Cooling

*The 

sensor S1 (black) 

must be in the ambient.
*The 

sensor S2 (gray)

 must 

be placed in the evaporator 
through metallic cramp.

Description

Standard

Standard

Loads supply

-

F49 / F50

F10

F11

F12

F49 / F50

F13

F13

-

-

Activates / Deactivates

Activates / Deactivates

Activates

Deactivates

Stays activated

Stays deactivated

Deactivates

Stays deactivated

Stays deactivated

Deactivates

Action through quick access menu (

[ECO,]

)

External key (digital input)

Closed door time to activate

S3-S1 temperature difference to deactivate

S3-S1 temperature difference to activate

Open door indication (digital input)

Maximum time in economy mode

Maximum time in economy mode =0(no)

Error in ambient temperature reading (S1)

When switching on the instrument

0

0 (no)

1

-50

0.1

-50

 

 

999

30

999

105

20

105

 

 

-

min.

min.

°C

º C

º C

 

 

0

0 (no)

240

-15

2.0

-10

 

 

-

min.

min.

°F

°F

°F

 

 

0

0

1

-58

-58

-58

 

 

999

30

999

221

36

221

 

 

0

0 (no)

240

5

3

14

 

 

Отзывы: