11. GLOSSARY OF ACRONYMS

- °C: 

Temperature in Celsius degrees.

- °F:

 Temperature in Fahrenheit degrees.

-

 

Heat.: 

Heating.

- LOC:

 Blocked.

- OFF:

 Turned off/disabled.

- ON: 

Turned on, enabled.

- Refr: 

Refrigeration.

- SET (as in "Setting")

 (setting or configuration).

- Vac:

 Electrical voltage (volts) of alternating current.

- Vdc:

 Electrical voltage (volts) of direct current.

9. SIGNALS

Error in sensor: Sensor disconnected or damaged.

[Err1]

[LOC,][On,,]

[LOC,][OFF,]

[OFF,]

[ClO,]

[EClO]

[ALrM]

[eCAL]

[pppp]

Functions lock.

Unlocking of functions.

Control functions off.

Contact Full Gauge Controls.

Reconfigure the values of the functions.

F09- Time for manual activation of the event output:

Time for which the event output remains on when manually activated. After this time has elapsed the 
event output returns to the automatic operation. This function can be switched off by setting it at the 
minimum value 0 

[No,,]

.

F10 - Preferred measurement view:
It allows choosing which measurement will be displayed:

[Temp]

- Temperature (if sensor is enabled).

[Hour]

- Hour

[All,]

- Switches between temperatures (if sensor is enabled) and time.

F11 - Recirculation - Scan time (if F05 = 1- heating):

Time during which the controller keeps the water circulation activated to equalize the water temperature 
in the keg.

F12 - Interval between scans (if F05 = 1- heating):

It is the interval between the last and the next temperature scan.

NOTE:

 If the temperature to switch on the thermostat is reached the scan cycle is restarted.

F13 - Maximum time the thermostat output remains on without reaching the setpoint (if F05 = 1- 
heating):

It is the maximum time the thermostat output will remain on without reaching the setpoint during the 
heating process. When this time is exceeded the visual alarm 

[alrm] 

is activated and the thermostat 

output remains off according to the time defined in F13. Functions F12 and F13 serves as protections for 
the gas-fired heater so that in case of fault (flame out for instance), the water circulation is interrupted 
and the heater is switched off to protect it.
This function can be switched off by setting it at the minimum value 0 

[no,,]

.

F14 - Thermostat output off time in state of alarm for not reaching the setpoint (if F05 = 1- 
heating):

It allows adjusting the time for which the controller will keep the thermostat output off while in state of 
alarm for not reaching the setpoint. If the setpoint is reached during this time the alarm is switched off. If 
the setpoint is not reached after this time has elapsed, new checks are performed during the time 
defined in F12.

F15 - Digital input operating mode:

Allows the output associated with the event calendar to be associated outside of the schedule of events, 
respecting the functions options and F07- Toggle thermostat to the event schedule and F09- Time of 
manual activation of the event output.

[Off,]

 Off

[,,,1]

 Activate / deactivate manual override (NO button)

[,,,2]

 Activate / deactivate manual activation (NF button)

F16 - Digital filter intensity applied to the sensor:

This filter has the purpose of simulating an increase in thermal mass at the sensor thereby increasing its 
response time (thermal inertia). The higher the value set in this function, the more time the sensor takes 
to respond. This function can be switched off by setting it at the minimum value 0 

[no,,]

.

F17 - Function lock mode:

It allows and configures the function lock.

[,,,0]

Do not allow the function lock.

[,,,1]

It allows a partial lock where the control functions will be locked but the adjustment of the 

setpoint, date views, and maximum and minimum record views are allowed.

[,,,2]

It allows the full lock, enabling only the date views and maximum and minimum record views.

F18 - Time for functions lock:

Allows lockdown of control functions (see item 8.3.2).

[,,15]

 - 

[,,60]

 - Defines the time in seconds for the controller to activate.

F19 - Control functions shutdown:

Allows the turning off the control functions (see item 8.3.3).

[,,,0]

Disables the control functions shutdown.

[,,,1]

Enables activation/deactivation of the control functions only if the functions are unlocked.

[,,,2]

Enables activation/deactivation of the control functions even if the functions are locked.

[,,,3]

It enables the activation/deactivation of the control functions only if the functions are unlocked, 

switching off the display.

[,,,4]

Enables  activation/deactivation  of  the  control  functions  even  if  the  functions  are  locked, 

switching off the display.

NOTE:

 In options 3 and 4 the display is switched off if no keys are pressed and switched on when any 

key is pressed, remaining on for five seconds.

F20 - Address of the instrument in the RS-485 network:

Equipment's network address for communicating with Sitrad® software.

Note: 

One network must not have different equipment with the same address.

Adjustment or visualization of the date and time.

Invalid date and/or time (adjust the clock).

12. OPTIONAL ITEMS - Sold Separately

Ecase protective cover

It is recommended for the Evolution line, keeps water from entering the back part of the instrument. It 
also protects the product when the installation site is washed.

ECASE PROTECTIVE COVER

Extended frame

It allows the installation of Evolution line controllers with sizes 76 x 34 x 77 mm in various situations, 
since it does not require precision in the notch of the instrument fitting panel. The frame integrates two 
switches of 10 Amperes that may be used to actuate interior light, air curtain, fan, and others. 

CONTROLLER

EXTENDED 
FRAME

SWITCHES

Alarm for failure to reach the setpoint.

10. 

INTEGRATING CONTROLLERS, RS-485 SERIAL INTERFACE 

AND COMPUTER

A

B

MT-530

super

A

B

MT-530

super

A

A

B

B

A B

A

B

A

A

B

B

A B

A

A

B

B

A B

A

A

B

B

A B

*Connecting Block for Serial Communication

Used to connect more than one instrument to the Interface. The wire's connections must 
be made in agreement with the following rules: terminal 

A

 of the instrument connects to 

the terminal 

A

 of the connecting block, that must be connected with the terminal 

A

 of the 

Interface. Repeat the action for terminals 

B

 and  

 

  

, being  

 

 

 the cable shield.  

the terminal  

 

  of connecting block must be connected to the respective terminals  

 

  of 

each instrument.

*Sold Separately

CONV. 32 

or

CONV. 256

 Keep Sitrad updated in website:

 http://www.sitrad.com

®

 

 - version 2 or higher

EasyProg

It is an accessory that has as its main function to store the parameters of the controllers. At any time, you 
can  load  new  parameters  of  a  controller  and  download  them  on  a  production  line  (of  the  same 
controller), for example. It has three types of connections to load or unload the parameters:

- Serial RS-485:

 It connects via RS-485 network to the controller (only 

for controllers that have RS-485). 

- USB:

 it can be connected to the computer via the USB port, using 

Sitrad's Recipe Editor.

- Serial TTL: 

The controller can be connected directly to 

EasyProg 

by the TTL Serial connection.

EASYPROG

IMPORTANT

TO  PERFORM  THE  COMMUNICATION 
WITH EASYPROG THIS EQUIPMENT MUST 
NOT  BE  COMMUNICATING  WITH  SITRAD 
SOFTWARE.

Watch Sitrad installation video in: 

http://www.fullgauge.com/

videos/sitrad