Full Gauge PWR-3200 plus Скачать руководство пользователя страница 4

07

08

11 - OTHER SETTINGS

Other configurations for the device, relating to other tasks, are located in the sub-item of menu 7.

06-Clock 

Clock

R01 @ 12:00:00
Date

R02 @ 01/01/2010
Week day

R03 @ SUNDAY

07-Configs

Language

C01 @ PORTUGUESE
485 Address

C02 @ 01
Ext CT Rel

C03 @ 500:05
Activ Alarm 1 ?

C04 @ YES
Activ Alarm

C05 @ YES

 2 ?

Init screen

C06 @ VOLTAGE
Backlight

C07 @ MAXIMUM
Contrast

C08 @ 03

Language 

Serial communication address

Ratio of external current transformer

Setting the time

Setting the date

Setting the day of the week

Enabling alarms

Setup screen

Backlight and Contrast

Setting the clock

Configurations

11.3 - Ratio of external current transformer

In the 

C03 

parameter you can change the ratio of external current transformer (CT). The minimum value is 5:5 (without an external CT), and 

the maximum is 3000:5 (i.e., when 3000 Amps pass through the cabling, there will be 5 amps at the output of the CT).

Care  should  be  taken  when  setting  this  value,  since  all  the  calculations  and  electrical  information  that  the  device  offers  are 
dependent on this.

 
11.4 - Activating the alarm

The 

C04

 and 

C05 

parameters allow the outputs 31 and 32 to be configured for alarms of Power Factor and Demand, respectively.  The choice 

between them is independent, and if you configure "NO", the output can be used to control power factor, demand control, or if nothing is 
allocated to any of these controls it will be an "events scheduler”.
The Alarms take precedence over the scheduled event outputs, i.e., if outputs 31 and 32 are allocated to the schedule, and alarm 1 and/or 2 
become activated, the output no longer functions as a schedule, it becomes an alarm function.
Operation: When an alarm occurs, the output 31 will be triggered intermittently (on and off every second), if it is a PF, or the output 32, if the 
event is to control demand. The alarms are deactivated by pressing the          button, returning again when an error occurs again.

11.5

 - 

Setting up the initial screen

When setting up the 

C06

, you will be informing the device which screen to show after being idle for 15 seconds, if you are in the menus 

"configuration parameters," , "visualization of maximums and minimums" or "quick access" or for 2 minutes, if you are in the " visualization of 
electrical parameters." For example, if the configuration of the "initial screen" is set at "current" (CORR) and the unit has been idle for 15 
seconds in somewhere in the "configuration parameters" menu,  the display screen will automatically return to where you are for the "quick 
view of electrical parameters," showing the currents.

11.6 - Backlight e Contrast

In the 

C07

 parameter the device display backlight can be adjusted. The backlight is the brightness of the screen, and can choose between 

Maximum, High, Medium, Low and MINIMUM.
In the 

C08

 parameter it is possible to configure the display contrast, which will adjust the brightness of the letters that are shown.

MENU

10 - SETTING THE CLOCK AND DATE

On the  

R01

,

 R02

 e 

R03

 parameters of the menu, you can set the time, date and day of week, respectively.

The time setting is done by increasing, or decreasing minutes, which consequently will also set the time.
Seconds are not adjusted, but when the time setting is confirmed, they are zeroed.
The date is adjusted by the increasing or decreasing the days, which will consequently change the month (the months change after the 31st day) 
and year (the year changes after the 12th month). The internal clock has a calendar set for leap years, and the number of days in any month, and it 
will progressively show the date correctly. However, when editing the date, it is possible to insert an invalid value, such as February 31. 

The User 

should take all precautions to avoid this. 

The day of the week is chosen by selecting from Sunday to Saturday.

11.1 - Language

In the 

 

C01

 parameter, you can select the device menu language. The options are - Portuguese, English and Spanish.

11.2 - Serial Communication Address

In the  

C02

 parameter it is possible to change the address of the RS485 serial communication. The number must be unique in the network, and   

at most 247.

12.1 - Reset Power

The active, reactive and apparent single-phase and three-phase power are tabulated over time and are periodically stored in an E2PROM 
memory so that this information is not lost in the case of having to reboot the machine for some reason, or if there is a power outage and the 
device is powered down. When performing this function, all power is zeroed.

12.2 - Clear Names

The use of this feature causes all the names assigned to demand control outputs to be erased.

12.3 - Clear Memory

This function causes all the data logger memory to be erased.

12.4 - Display Outputs

DThis may become a little confused in relation to which outputs control the power factor, which ones are for the demand control, which are to 
schedule events, and which ones are for the alarms, this feature helps to make this a little clearer, since it indicates, through a display screen 
and LEDs, that shows which outputs belong to each function.

12.5 - Check order of the phases

This function must be performed after the installation of the device to make sure that it is correctly installed. If it is correct, an "OK" will be 
displayed, however, if not, there will be an error warning, and the unit will indicate the phases with these errors.
Because many electrical installations do not have all phases shown, this function becomes necessary.
If the unit shows an error, check the following, in this order:

- Is the current in each phase greater than the "external CT ratio," divided by 20? For example, if the external CT ratio is 500:5, then the  
current must be greater than 5 Amps (500/5 = 100, 100/20 = 5).
- Try to invert the polarity of the current measurement of the phases that are showing errors. If only one phase is showing an error, it is 
quite possible that the current polarity is inverted (the effect of the inverted polarity is an indication of capacitive power factor, when it is 
inductive, and vice versa).
If the error continues, and for more than one phase, the voltages and currents may not be connected correctly (voltage 1 with current 1, 
and this applies for phases 2 and 3). One may observe the active, reactive and apparent power, so that the consistency of readings may 
be observed. If the reading of two of the phases is inconsistent, you should try to change their current signals, namely, the current in-CT2-
IN and CT2-OUT, should go to CT3-IN and CT3-OUT, and the current in 3 goes to 2.
- If the function is showing an error but no phase is shown (all phases are zero, in the display, in the result of the function), then the error is 
in the voltage phase sequence. Therefore the order of phases should be reversed, B with C, A with B or C with A, for the controller to 
sample some of the sequences: ABC, BCA or CAB.

 

Note: This function works perfectly for inductive circuits. If they are capacitive, it may show unjustified errors, or not display the errors 
correctly.

13 - OTHER IMPORTANT INFORMATION

*  The voltages as well as the current have a minimum value to be measured, so that the controller shows the information correctly. If any of the 
three voltages is below 50 volts (but greater than 10), the controller will show the value of 0.1 volts, and indicate "voltage limit error" in the 
corresponding phase. If any current is less than 10mA times the CT ratio, then the current and the powers of this phase will be shown as a zero 
value. For example, for a CT of 500:5, the minimum current would be 1 Amp (500/ 5*10mA).
*  The accuracy of the instantaneous measurement of the electrical parameters is 2%. However, for power, this is 3%. These errors do not take into 
account the accuracy of the external current transformer, which is the responsibility of the equipment user. It is advisable to use   Class 0.3 
transformers.
*  When a measured value exceeds one million, the unit changes from Kilo (k) to Mega (M) and when this passes one billion, it will be shown in Giga 
(G).
* The equipment considers, for measurements and calculations, up to the 5th harmonic for voltage and the 233rd for current.
* If the equipment loses it calibration because of some external noise, it will automatically reload the values stored in the E2PROM, and a warning 
will show: "

Recar. Calib.

14 - TROUBLE SHOOTING

- Capacitive power factor, should be inductive - Polarity of the current sensor (CT) reversed.
Action: exchange TCx IN with TCx OUT.
- Currents and power factors show very abrupt changes - This effect is common in industrial installations, where there are machines that 
have large motors or are controlled by semi-conductor power devices.
- Currents and power are zeroed - The current is probably below the minimum threshold for reading.
- Voltages are zeroed, or at 0.1 volt - Voltage at zero is indicative that the voltage is below 10 volts. If at 0.1, this is indicative that it is 
between 50 and 10 volts.

12 - FUNCTIONS

Reset energy

Clear Names

Clear Memory

 Display outputs

Check order of phases

Functions

08-Functions

Reset Energies ?

F01 @ NO
Clear Names ?

F02 @ NO
Clear Memory ?

F03 @ NO
Show Outputs ?

F04 @ NO
Verify Install ?

F05 @ NO

Содержание PWR-3200 plus

Страница 1: ...the key for more than 1 second will display the menu view electrical parameters where the key does not go to the record maximums and minimums menu butgoesforwardinthemenuitems Note Theincrementinthespeedofthevariablebeingeditedincreaseswiththetimethekeyispressed Ifyouarein quickviewoftheelectrical parameters menu clicking onthe menu keywillshowthe quickaccess menu Ifthemenuisinthe Setting the prio...

Страница 2: ...he power factor control this can be between 0 and 32 none or all outputs This parameter can beeditedinmenu N The outputs for the control of the power factor always start at the first output i e OUT 01 will always be the first output for this control The otheroutputsarenext inascendingorder Note To change the number of outputs for the Power Factor or Demand control the controls must be disabled If ...

Страница 3: ...e timing between the sampling of the information in the data logger may be edited Theconfiguredvalueisinseconds DataloggerConfiguration 04 Data Logger Sample time L01 20 sec Volt variation L02 10 V Rewrite mem L03 YES Operation Mode L04 Manual Activate DL L05 YES Timebetweensamples VoltageVariation Overwritememory OperatingMode Enabledatalogger 8 2 Voltage Variation If there is a need to enforce t...

Страница 4: ...oed 12 2 Clear Names Theuseofthisfeaturecausesallthenamesassignedtodemandcontroloutputstobeerased 12 3 Clear Memory Thisfunctioncausesallthedataloggermemorytobeerased 12 4 Display Outputs DThis may become a little confused in relation to which outputs control the power factor which ones are for the demand control which are to schedule events and which ones are for the alarms this feature helps to ...

Страница 5: ...s not work The control may be disabled the references to the control may be unadjusted the information on the prioritiesmaynothavebeeninputcorrectly PWR 3200 Plus DIN RAIL WALL WINRING PANEL Full Gauge Controls 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 43 44 45 46 47 48 49 50 51 52 53 54 55 56 29 30 31 32 33 34 35 36 37 38 39 40 41 42 1 2 3 4 5 6 7 8 9 10 11 12 13 ...

Страница 6: ...IRONMENTALINFORMATION Package The packages material are 100 recyclable Just dispose it through specialized recyclers Products The electro components of Full Gauge controllers can be recycled or reused if it is disassembledforspecializedcompanies Disposal Do not burn or throw in domestic garbage the controllers which have reached the end of life Observe the respectively law in your region concernin...

Страница 7: ...5 VAr kW kW hh mm hh mm Sec Sec Volts hh mm hh mm hh mm hh mm hh mm hh mm hh mm hh mm hh mm dd mm yy Parameter Configurable Parameters Description Minimum Standard Unit Maximum 0 0 0 6 0 62 0 NO 0 0 0 00 00 00 00 1 0 NO 2 2 NO Always OFF NO Next output after the demand control Daily Sunday 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 01 02 07 Sunday Portuguese 1 5 NO NO Line Voltage Minim...

Страница 8: ...ctive power Phase A accumulated apparent power Phase B accumulated apparent power Phase C accumulated apparent power Three phase accumulated apparent power Parameter 0 0 0 0 0 0 0 0 0 0 00 0 00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Volts Amperes Kilo Watts Reactive Kilo Volt Ampere Kilo Volt Ampere Kilo Watts Reactive Kilo Volt Ampere Kilo Volt Ampere Kilo Watts Kilo Watts Hertz Volts Kilo Watt hours Kilo...

Отзывы: