THREE-PHASE CONTROLLER FOR 

DEMAND AND POWER FACTOR

PWR3K201-04T

-1

1853

®

1 - DESCRIPTION

The 

PWR-3200 plus

 plus is a controller equipped with 32 outputs, configurable between demand control, power factor control, outputs for 

programming "schedule of events" and two alarms. The equipment is able to measure, display to the user and store in an internal data logger 
several electrical parameters, such as single-phase voltages and line currents, the currents of each phase, the power, demands and single-phase 
and  three-phase  power  factor,  the  grid  frequency,  as  well  as  single-phase  and  three-phase  active,  reactive  and  apparent  energy.
From the measured demands and power factors, the equipment operates with capacitor banks to correct the power factor, and with the consumer's 
energy loads, to control the demand of the electrical system.

2 - APPLICATION

This equipment may be used in any business, which is a consumer of electricity, and wants to manage demand or the power factor, or simply 
acquire knowledge about electrical parameters, for monitoring and decision-making.

3 - TECHNICAL SPECIFICATIONS

- Supply:

 90 ~ 264 Vac ± 10% (50/60Hz)

- Voltage Range: 

50  to 500Vac (50/60Hz)

- Current Range: 

5A (expandable with an external CT)

- Command: 

Alarms: Two relays N.C. (3A Max)

                     Control Outputs: 30 x N.O. solid state relays (20~250Vac / max 125mA)**

- Dimensions (WxHxD): 

220x134x54mm

- Operating temperature: 

0 to 40° C

- Operating humidity: 

10 to 90% RH (no condensation)

**Solid state relays can only drive AC voltages (VAC) loads 

4 - KEYBOARD

Five keys are available for operating the menu.
In general, these keys have the following functions:

If the variable shown is editable, pressing this key will cause it to blink and values can then be increased or decreased. If a variable being 

edited (is blinking), pressing this key will validate it with the value chosen. If no editable value is shown, and the menu shows another level 
(represented by the symbol   

>>>

, or  by a numeric index), by pressing this key, you will go to the next menu level. Ex.:

If any variable is being edited (blinking) and this key be pressed, the editing will be canceled, and the value of the variable will remain as before 

the editing. If there is a previous level and this key is pressed, the menu will go back one level

If a variable is being edited, this key will increase the displayed value (the value that is blinking). If no variable is blinking, this key allows one to 

advance in the items on the same menu level. If you are in the "quick view of the electrical parameters" menu, pressing this key for 1 second will 
display the menu "record of maximums and minimums." Whilst in the menu "record of maximums and minimums," holding this key for 2 seconds, 
will reset the recorded maximum and minimum values.

Note: 

The increment in the speed of the variable being edited increases with the time the key is pressed.

SIf any variable is being edited, this key decreases the value shown (value that is blinking). If no variable is blinking, this key allows one to 

return the items on the same menu level (e.g. Quit menu 2.2 and go to 2.1). If you are in the "quick view of the electrical parameters" menu, pressing 
the key for more than 1 second will display the menu "view electrical parameters," where the key        does not go to the "record maximums and 
minimums" menu, but goes forward in the menu items.

Note: 

The increment in the speed of the variable being edited increases with the time the key is pressed.

         If you are in "quick view of the electrical parameters" menu, clicking on the "menu" key will show the "quick access menu." If the menu is in the 
"Setting the priority of load shutdown" or "Set the timing for the reconnection of the loads" position, when you press this key for 2 seconds, you can 
edit the name of the outputs. After editing, to confirm the allocated name, you must press the key again for 2 seconds.

MENU

5 - MENUS
   5.1 - Quick View of measured electrical parameters

It is used to display the selected electrical parameters.
To access: go to the main menu, which will be shown when you leave another menu (e.g. from item 3 of the parameters configuration menu, and 

pressing the         key).

 Note: The values showed on next screens are merely illustrative

or

Energies     >>>    

Activ En A ( Wh)  

02-Power Fact >

  N Outputs PF Ctr

  P01 @ 12  

Activ En A (kWh)

    2.941      
Activ En

    2.925

       

 B (kWh)

Activ En

    2.935      

 C (kWh)

Rt En A (kVArh)

    1.216      
Rt En B (kVArh)

    1.245       

Rt En C (kVArh)

    1.198     

Activ En 3 (kWh)

    8.801      

Rt En 3 (kVArh)

    3.659       

Ap En A (kVAh)

    3.138       
Ap En B (kVAh)

    3.245      
Ap En C (kVAh)

    3.148      
Ap En 3 (kVAh)

    9.531       

  VAB  VBC  VCA

  311  309  312  
Frequency (Hz)

     60.0      
 PF(3 )  Dem(3 )

 0.92(i) 44.411 
PF iii  A0.91   

B0.92   C0.92   
Dem(kW) A14.312

B15.265 C14.834  
Pow 3   P49.226 

Q20.970 S53.507
S(kVA)  A17.659  

B17.874 C17.974
Q(kVAr) A6.921  

B7.005  C7.044
P(kW)   A16.246  

B16.444 C16.536
Cur( A) A81.233  

B81.546 C81.224
Vol(V)  A220.1   

B219.2  C221.3   

  

  5.2 - Visualize Electrical Parameters 

The same as "Quick View of Electrical Parameters” (the screen menus are the same), but differs from the             key, this does not go to the 
maximum and minimum menu, but advances in the menu items.
To access: From within the "Quick View of Electrical Quantities" menu, press the          key for 2 seconds.

      Note: After 2 minutes without touching any key, the menu automatically returns to quick view of the measured electrical parameters.

5.3 - Record of Maximums and Minimums

This menu shows the maximum and minimum values of some parameters.

      To access: From within the "Quick View of Electrical Parameters" menu, press the          key for 2 seconds.

Note: From within this menu, pressing the         key for more than 2 seconds to reset all the recorded values.

Energies     >>>

Maximum single-phase demand 

Maximum voltage of phase 

Minimum voltage of phase

Maximum current

Minimum recorded inductive Power Factor (PF) 

Minimum recorded capacitive Power Factor (PF) 

Single-phase active power

Three-phase active power

Single-phase reactive power

Three-phase reactive power

Single-phase apparent power

Three-phase apparent power 

Line voltages

Grid Frequency

Power factor and three-phase demand

Single-phase power factor

Single-phase demand

Active, reactive and apparent three-phase power

Single-phase apparent power

Single-phase reactive power

Single-phase active power

Currents in each phase

Phase voltages

  MM1- Max dem reg

  Phase A  00.0 

kW

MM2- Max Vrms

Phase

 A  00.0 V

 MM3- Min Vrms

 Phase A  00.0 V        

MM4- Max Irms

Phase

 A  00.0 A

MM5- Min ind PF 

 3    1.00
MM6- Min cap PF

 3    1.00

Power

The “

iii

” or “ 

i

” means that the power factor 

is  inductive.  If  it  would  be  capacitive,    the 
letter shown would be “

c

”.

Note:

   iii

Phase   A  B  C

Содержание PWR-3200 plus

Страница 1: ...the key for more than 1 second will display the menu view electrical parameters where the key does not go to the record maximums and minimums menu butgoesforwardinthemenuitems Note Theincrementinthespeedofthevariablebeingeditedincreaseswiththetimethekeyispressed Ifyouarein quickviewoftheelectrical parameters menu clicking onthe menu keywillshowthe quickaccess menu Ifthemenuisinthe Setting the prio...

Страница 2: ...he power factor control this can be between 0 and 32 none or all outputs This parameter can beeditedinmenu N The outputs for the control of the power factor always start at the first output i e OUT 01 will always be the first output for this control The otheroutputsarenext inascendingorder Note To change the number of outputs for the Power Factor or Demand control the controls must be disabled If ...

Страница 3: ...e timing between the sampling of the information in the data logger may be edited Theconfiguredvalueisinseconds DataloggerConfiguration 04 Data Logger Sample time L01 20 sec Volt variation L02 10 V Rewrite mem L03 YES Operation Mode L04 Manual Activate DL L05 YES Timebetweensamples VoltageVariation Overwritememory OperatingMode Enabledatalogger 8 2 Voltage Variation If there is a need to enforce t...

Страница 4: ...oed 12 2 Clear Names Theuseofthisfeaturecausesallthenamesassignedtodemandcontroloutputstobeerased 12 3 Clear Memory Thisfunctioncausesallthedataloggermemorytobeerased 12 4 Display Outputs DThis may become a little confused in relation to which outputs control the power factor which ones are for the demand control which are to schedule events and which ones are for the alarms this feature helps to ...

Страница 5: ...s not work The control may be disabled the references to the control may be unadjusted the information on the prioritiesmaynothavebeeninputcorrectly PWR 3200 Plus DIN RAIL WALL WINRING PANEL Full Gauge Controls 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 43 44 45 46 47 48 49 50 51 52 53 54 55 56 29 30 31 32 33 34 35 36 37 38 39 40 41 42 1 2 3 4 5 6 7 8 9 10 11 12 13 ...

Страница 6: ...IRONMENTALINFORMATION Package The packages material are 100 recyclable Just dispose it through specialized recyclers Products The electro components of Full Gauge controllers can be recycled or reused if it is disassembledforspecializedcompanies Disposal Do not burn or throw in domestic garbage the controllers which have reached the end of life Observe the respectively law in your region concernin...

Страница 7: ...5 VAr kW kW hh mm hh mm Sec Sec Volts hh mm hh mm hh mm hh mm hh mm hh mm hh mm hh mm hh mm dd mm yy Parameter Configurable Parameters Description Minimum Standard Unit Maximum 0 0 0 6 0 62 0 NO 0 0 0 00 00 00 00 1 0 NO 2 2 NO Always OFF NO Next output after the demand control Daily Sunday 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 01 02 07 Sunday Portuguese 1 5 NO NO Line Voltage Minim...

Страница 8: ...ctive power Phase A accumulated apparent power Phase B accumulated apparent power Phase C accumulated apparent power Three phase accumulated apparent power Parameter 0 0 0 0 0 0 0 0 0 0 00 0 00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Volts Amperes Kilo Watts Reactive Kilo Volt Ampere Kilo Volt Ampere Kilo Watts Reactive Kilo Volt Ampere Kilo Volt Ampere Kilo Watts Kilo Watts Hertz Volts Kilo Watt hours Kilo...

Отзывы: