CONTROLLER FOR REFRIGERATION

  AND DEFROSTING

Ver.01

TC-960Ri LOG

1. DESCRIPTION

TC-960Ri

 

LOG 

is  a  temperature  controller  for  frozen  goods  that  automates  the  defrosting 

processes in accordance with the needs of the facility, thus providing large power savings.
It has two sensors: one for ambient temperature and the other fixed to the evaporator that controls the 
defrosting ending and the fan restarting. It is also fitted with an alarm output and buzzer that can be 
activated by different events. It is fitted with two digital inputs, being able to read the supply voltage 
(protecting the loads from under- and over-voltage), and an hour-meter function that indicates when the 
time for compressor maintenance has come. Beyond these resources the instrument has an internal 
data-logger with 70 hours of autonomy, or almost 3 days ( in a 30 seconds sample time). It also has a 
digital filter for the temperature reading that decrement the response time of the ambient sensor to 
prevent the compressor action by fast changes of this measurement.

2. APPLICATION

• Refrigerated Trucks
• Refrigeration chambers
• Counters

3 - TECHNICAL SPECIFICATIONS

- Power Supply:

12 or 24 Vdc ± 10%

- Control temperature:

 -50 or 75°C / -58 or 167°F

- Operating temperature:

 0 or 40°C / 32 or 104°F

- Operation humidity: 

10 or 90% RH (without condensation)

- Resolution: 

0.1ºC from -10 to 75ºC and 1ºC outside this range / 1°F in all range

4 - CONFIGURATIONS

4.1 - Control temperature adjust (SETPOINT):

- Press          for 2 seconds until            appears, and release it after that. The adjusted temperature will 
appear.  Use         and         to change the value and then press           to record it. The display will show
            meaning that the setpoint value of the economy setpoint must be adjusted. Use the same 
procedure to adjust the economy setpoint value and when ready, press        to save and return to the 
preferred view.
The economy setpoint will be activated in accordance with the hourly setup adjusted through functions 
F57 to F62.

   

SET

SET

- Load current (outputs):

 COMP: 12(8)A / 240 Vac 1HP

                                          FANS: 5(3)A / 240Vac 1/8HP (evaporator fans) 
                                          DEFR: 1(3)A / 240Vac (defrost resistance or hot gas)
                                          ALARM: 5(3)A / 240Vac 1/8HP  

- Dimensions: 

71 x 28 x 71mm  

SET

- Sensors:

S1: ambient temperature sensor (black cable, comes with the product)
S2: evaporator sensor (gray cable, comes with the product)

Description

Fun

4.4 -  Parameters table

Min

Max

Unit

0.1

-50

F03

0

-20

-20

0 - disabled

0 - disabled

-50

0

0

0

0 - off

0 - no

-50

0.1

20.0

F04

75.0

30

20.0

20.0

6

6

75.0

30

999

999

1 - on

1 - yes

75.0

20.0

2

-50

75.0

0

0.0

0.0

0

0

0.0

1

0

0

1

1

50.0

2.0

°C

°C

°C

min.

°C

°C

-

-

°C

min.

sec.

sec.

-

-

°C

°C

 

 

Control differential (hysteresis)

Minimum setpoint allowed to the end user

Maximum setpoint allowed to the end user

Delay when the instrument is powered on

Offset indication for ambient temperature sensor

Offset indication for evaporator sensor

Operation mode of digital input 1 (*)

Operation mode of digital input 2 (*)

Evaporator temperature (S2) for fan return after draining

Maximum time of fan return after draining (fan-delay)

Minimum time of compressor turned on

Minimum time of compressor turned off 

Compressor status with inoperative ambient temperature sensor (S1)

Fan on with compressor off (refrigeration)

Fan stopped for high temperature in the evaporator (S2)

Fan return hysteresis (after stopping due to high evaporator temperature)

Maximum refrigeration time (for security, if F22 = 1)

Evaporator temperature to start defrosting (if F22=1)

Time to confirm a low S2 temperature to start defrosting (if F22=1)

Maximum time with compressor turned on without reaching the set point (to warn)

Defrosting type

Condition to start defrosting (**)

Interval between defrosts

 (

if

 F22=0)

Time for collecting the gas before the start of the defrost cycle

Delay before performing the 1st defrost (if F22=0)

Defrost when the instrument is powered on 

Evaporator temperature (S2) determine the end of defrost

Maximum defrost duration (for security)

Fan turned on during defrost 

Temperature indication (S1) locked during defrosting

Draining time (dripping of defrost water)

Low ambient temperature alarm (S1)

Low temperature alarm hysteresis

High ambient temperature alarm (S1)

1

-50

0

0

0 - resist.

0

1

0

0

0 - no

-50

0

0 - no

0 - no

0

-50

0.1

-50

240

75.0

90

999

1 - hot gas

2

999

90

999

1 - yes

75.0

90

1 - yes

1 - yes

30

75.0

20.0

75.0

24

-5.0

10

300

0

0

240

0

0

0

40.0

45

0

0

10

-50

1.0

75.0

hours

°C

min.

min.

-

-

min.

min.

min.

-

°C

min.

-

-

min.

°C

°C

°C

High ambient temperature alarm hysteresis

Alarm inhibition time after powering the instrument on

Alarm inhibition time after draining

Inhibition time for the open door alarm (only buzzer)

Buzzer enabling 

Minimum supply voltage (protection)

Maximum supply voltage (protection)

Offset voltage indication

Time to validate the voltage reading

Datalogger operation mode (***)

Alarm time (on cycle)

Alarm time (off cycle)

0.1

0

0

0

0

0

0 - disabled

10

10

-5.0

0

0

20.0

999

999

99

999

999

1 - enabled

30

30

5.0

30

2

1.0

0

0

0

1

1

1

10

30

0.0

5

2

°C

min.

min.

min.

sec.

sec.

-

Vdc

Vdc

Vdc

sec.

-

CELSIUS

FAHRENHEIT

Min

Max

Unit

1

-58

F03

0

-36

-36

0 - disabled

0 - disabled

-58

0

0

0

0 - off

0 - no

-58

1

36

F04

167

30

36

36

6

6

167

30

999

999

1 - on

1 - yes

167

36

4

-58

167

0

0

0

0

0

32

1

0

0

1

1

122

4

°F

°F

°F

min.

°F

°F

-

-

°F

min.

sec.

sec.

-

-

°F

°F

1

-58

0

0

0 - resist

0

1

0

0

0 - no

-58

0

0 - no

0 - no

0

-58

1

-58

240

167

90

999

1 - hot gas

2

999

90

999

1 - yes

167

90

1 - yes

1 - yes

30

167

36

167

24

23

10

300

0

0

240

0

0

0

104

45

0

0

10

-58

2

167

hours

°F

min.

min.

-

-

min.

min.

min.

-

°F

min.

-

-

min.

°F

°F

°F

1

0

0

0

0

0

0 - disabled

10

10

-5.0

0

0

36

999

999

99

999

999

1 - enabled

30

30

5.0

30

2

2

0

0

0

1

1

1

10

30

0.0

5

2

°F

min.

min.

min.

sec.

sec.

-

Vdc

Vdc

Vdc

sec.

-

Standard

Standard

4.2 - To enter the function menu

Press        and,        at the same time for 2 seconds until           appears, letting off on it instantly. When
          appears, press        (short touch) and enter the code (123) through the keys        and       to 
confirm press the key         . Through the keys        and        access the other functions and do the same 
to adjust them. To leave the menu and return to normal operation, press            (Long touch) until
appears.

4.3 - Functions

Entry of access code
Advanced configuration functions
Adjustment of clock and date 

SET

SET

SET

COMPONENT

TC960RiLOG01-04T

-12256

Содержание TC-960Ri LOG

Страница 1: ...g fan delay Minimum time of compressor turned on Minimum time of compressor turned off Compressor status with inoperative ambient temperature sensor S1 Fan on with compressor off refrigeration Fan stopped for high temperature in the evaporator S2 Fan return hysteresis after stopping due to high evaporator temperature Maximum refrigeration time for security if F22 1 Evaporator temperature to start ...

Страница 2: ... that the compressor will keep turned off it means the time period between the last stopped and the next started It serves to alliviate the pressure and to increase the useful life of the compressor F13 Compressorstatuswithdetachedambientsensor S1 If the ambient sensor S1 is detached or out specified range the compressor assumes the configured statusinthisfunction Exemple For counters that storage...

Страница 3: ...emoryisfulltheinstrumentandSitradwillsignalfullmemory F51 Numberofdefrostsperday MondaytoFriday The defrost cycles are evenly distributed in accordance with the number of defrosts set per day always considering the preferred time The value can be adjusted to 1 2 3 4 6 8 or 12 This function works to scheduletheoperationfromMondaytoFriday Indicateswhetherthechangeinanyoutputwillforcetherecordingofda...

Страница 4: ...hat maintenance should be done To reset this counter It can be done only afterthewarningoccurs press for10seconds 6 9 Turn off the control functions Pressing for 5 seconds the controller will go to a state where only temperatures and voltages are read where no control are performed and where all outputs kept off Communication with SITRAD softwareandtheDataloggerwillstillwork Tomakethedevicefullyop...

Страница 5: ...or PROTECTIVE VINYL This adhesive vinyl included inside the packing protects the instruments against water drippings as in commercial refrigerators for example Do the application after finishingtheelectricalconnections Remove the protective paper and apply the vinyl on the entire superior part of the device folding the flaps as indicated by thearrows 72 mm Dimension of the clipping for setting of ...

Отзывы: