Enters function selection.

6.3. Basic operations

6.3.3. Functions lockdown

 

The use of the functions lockdown brings greater security to the operation of the instrument. When it is 
active, the setpoint and other parameters can be visible to the user, but are protected against undue 
changes (F35=2) or you can block changes of control functions and leave the adjustment of the setpoint 
enabled (F35=1). 
Using the key 

;

 (short touch), access the function 

[LOC,]

 in the easy menu, confirm by pressing 

(short touch), then the message 

[no,,]

 will be displayed. After that keep the key 

>

 pressed for the 

time configured for the functions lockdown (F36), until 

[LOC,]

 is displayed. The message 

[On,,]

 

will be displayed indicating the lockdown function is activated upon releasing the key.

To unlock, turn the controller off and then turn it on again with the key 

>

 pressed. Keep the key pressed 

until 

[LOC,]

 is displayed. Keep the key pressed for ten seconds and the message 

[OFF,]

 will be 

shown on the display indicating the deactivation of the lockdown

 

function when the key is released.

6.3.1. Adjusting desired temperature (setpoint)

If configured not to use recipes (F03= 

[no,,]

): 

- Hold down the 

/

key for 2 seconds until the message 

[Set,]

is displayed; 

- Then the message 

[SP,,]

will be displayed and the setpoint may be adjusted; 

- Use the 

>

 or 

<

 keys for changing the value, then press

/

 to confirm.

If configured to use presets (F03=

[Yes,]

):

Each preset may be set up to use different values for the Setpoint, Control differential (hysteresis) and 
Cooling time (interval between defrosts). 

To select the preset:

- Hold down the 

/

 key for 2 seconds until the message 

[Set,]

is displayed;

- Then the  currently selected preset will appear 

[Rc1,]

or 

[Rc2,]

.

- Use the

>

 or 

<

 keys to select which of the 2 presets will be used.

- To confirm the selection, press

/

 .

Note: 

The  values  of  functions  Setpoint,  Control  differential  (hysteresis)  and  Cooling  time  (interval 

between defrosts) for each preset are set up in the parameters menu.

6.3.2. Manual defrost

The manual defrost is carried out through the quick access menu. Hold down the 

;

 key (quick touch) 

until the message 

[dEFr]

appears (flashing 

@

LED), and then press the

/

key (quick touch) to make 

a selection. Then the message 

[defr][On,,]

will appear ( 

@

LED on). 

To turn off defrost manually press the 

;

 key (quick touch) until the message 

[defr]

appears (flashing 

@

LED). Press the 

/

key (quick touch) to select. Then the message

[defr][OFF,]

 appears (

@

 

LED off). 

The manual defrost may also be activated/deactivated by holding down the key 

<

for 4 seconds.

<

<

<

Enters quick access menu.

;

Hold down for 4 seconds: Carries out manual defrost.

MT-514

e

MT-514

e

6.3.4. Control functions shutdown

Turning the control functions off allows for the controller to operate just as an indicator of temperature, 
keeping the control outputs and the alarms disconnected. Use of this feature is enabled or not by the 
control functions shutdown (F35) function. When enabled, the control and alarms functions are turned 
off  (

[CtrL][OFF,]

)  or  on  (

[CtrL][0n,,]

)  through  the  quick  access  menu  in  the  option 

[CtrL]

. When the control functions are off the message 

[OFF,]

 will then be displayed alternately 

with the temperature and the other messages. 

NOTE: 

When  switching  the  control  functions  back  on, 

  will  continue  to  respect  the 

functions “

[,F16]

 - Minimum OUT1 output time off” and “

[,f17]

 - Initial status when energizing the 

instrument”.

MT-514

e

MT-514

e

Note 1: 

The minimum and maximum temperature records shall only be performed after the elapsing of 

the alarm inhibition time when energizing the controller and after the delay in the instrument energizing 

[,F27]

 + 

[,F19]

.

Note 2:

 The minimum and maximum temperature records shall only be performed after the compressor 

reaches the active preset setpoint ; before that, the 

[____]

 messages will be displayed for the records 

of minimum and 

[++++]

 for the records of maximum temperature.

6.3.7. Unit Selection 

To select the temperature unit in which the instrument will operate enter the function 

[,F01]

 using the 

access code

 [,231]

 then press the 

/

. key. Then, select the unit desired

[,=C,]

or

[,=F,]

 using 

the

<>

 keys; to confirm press 

/

. Every time the unit is changed, the functions settings return to the 

default value, thus, they must be set up again.

6.3.8. Buzzer inhibition

When activated, the buzzer can be inhibited by pressing the 

>

key for two seconds. The Buzzer will 

remain inhibited until a new alarm event takes place.

6.4. Advanced operations

The functions menu can be accessed through the quick access menu (according to chapter 6), option

 

[Func]

 or by pressing simultaneously

during the temperature display. To allow change of 

parameters, enter 

[,F01]

by pressing 

/

 (quick touch) and using the 

 keys enter code 123 

(one hundred and twenty-three), and then confirm with

/

. For changing the other functions, browse the 

menu through the 

 keys and proceed the same way in order to adjust them. To exit the menu 

and return to the normal operation, press 

/

 (long touch) until

 [----]

 is displayed.

OBS: 

If the functions lockdown is enabled, when pressing the

keys, the controller will display 

the message 

[LOC,]

 and will not allow parameter adjustment.

>

and

<

>

or

<

>

or

<

>

or

<

6.5. Parameters table

Legend:

[yes,]

= yes

             

[no,,]

= no

             

[Off,]

= off

6.3.5. Visualization of Processes 

To view the process and the time elapsed, press 

>

(quick touch) or by the

[dEL,]

- Initial delay (delay in the instrument start-up)

[rEFr]

- Cooling

[Hot,]

- Heating

[dEFr]

- Defrost

[drAi]

- Drainage

[----]

- Control functions off

 

;

(Flatec) key pressing it 

until the message 

[Proc]

 appears. This way, the controller will display the current process status, and 

the following messages may appear on the display:

6.3.6. Minimum and Maximum Temperature Record

Pressing down the

<

key or also via the quick access menu (see chapter 6), will cause the message 

[rE9,]

 to be displayed, then the minimum and maximum temperatures recorded.

 

For erasing the current minimum and maximum values, hold down the 

;

key (quick touch) until the 

message 

[CrE9] 

is displayed, then the message 

[CodE]

 will appear; enter the value 

[,123]

then confirm with the

/

key. If the code is correctly entered, the message 

[rSt,]

 will be displayed. 

[rSt,]

.  This  procedure  keeps  unauthorized  users  from  erasing  the  minimum  and  maximum 

temperature records.

F01- Access code 123 (one hundred and twenty-three):

This is required when intending to change the configuration parameters. Entering of this code is not 
required if the intention is just visualizing the parameters adjusted. 
It allows entering of the expected access codes:

[,123]

- Allows access for changing the table parameters.

[,231]

- Allows configuring of the unit of measurement 

[,=f,]

 or 

[,=C,]

[,231]

- To select the unit in which the instrument will operate enter the function

[,F01]

 using the 

access code

[,231]

then press the

/

key. Then, select the unit desired 

[,=C,]

 or

[,=F,]

using 

the

< >

keys; to confirm press 

/

NOTE:

  Every  time  the  unit  is  changed,  the  parameters  should  be  reset,  since  they  assume  the 

‘standard’ values of the parameter’s table.

F02 - Sensor indication displacement (offset):

Allows compensation for any temperature deviations from sensor replacement or change in the cable 
length.

or

6.5.1. Description of parameters

Access code 123

Sensor indication displacement (offset)

Using Presets

Output operating mode OUT1

Operation setpoint (

)

Control differential (Hysteresis) (

)

Cooling time (interval between defrosts) (

)

Defrost time (

)

Operation setpoint (

)

Control differential (Hysteresis) (

)

Cooling time (interval between defrosts) (

)

Defrost time (

)

Minimum setpoint allowed to the end user

Maximum setpoint allowed to the end user

Minimum OUT1 output time on

Minimum OUT1 output time off

Initial status when energizing the instrument

Temperature indication locked during defrost

Instrument energization delay

Compressor status with the sensor damaged

Compressor time on in case of error

Compressor time off in case of error

Maximum Compressor on without reaching setpoint

Low temperature alarm

High temperature alarm

OUT2 output operating mode

Alarm inhibition time when energizing the controller

Enable buzzer 

Digital input operating mode

Output on time in OUT2 alarm status

Output off time in OUT2 alarm status

Open door time for alarm

Operating mode of the digital filter

Digital filter intensity applied to the sensor

Functions lockdown

Time for functions lockdown

Control functions shutdown

rc1

rc1

rc1

rc1

rc2

rc2

rc2

rc2

[,F01]

[,F02]

[,F03]

[,F04]

[,F05]

[,F06]

[,F07]

[,F08]

[,F09]

[,F10]

[,F11]

[,F12]

[,F13]

[,F14]

[,F15]

[,F16]

[,f17]

[,f18]

[,F19]

[,F20]

[,F21]

[,F22]

[,F23]

[,F24]

[,F25]

[,F26]

[,F27]

[,F28]

[,F29]

[,F30]

[,f31]

[,f32]

[,F33]

[,F34]

[,f35]

[,f36]

[,f37]

Fun

Min Max Unit

CELSIUS

FAHRENHEIT

Min Max Unit

Standard

-

-5.0

no

0-cool.

-50

0.1

1

0(no)

-50

0.1

1

0(no)

-50

-50

0(no)

0(no)

0-cool.

no

0(no)

0

1

1

0(no)

-50

-50

1

0(no)

0(off)

0(no)

0

0

0(no)

0

0(no)

0

15

0(no)

-

-9

no

0-cool.

-58

1

1

0(no)

-58

1

1

0(no)

-58

-58

0(no)

0(no)

0-cool.

no

0(no)

0

1

1

0(no)

-58

-58

1

0(no)

0(off)

0(no)

0

0

0(no)

0

0(no)

0

15

0(no)

-

5.0

yes

1-

200

20

999

999

200

20

999

999

200

200

999

999

1-defr.

yes

240

2

999

999

240

200

200

5

999

1

6

999

999

999

1

20

2

60

2

heat.

-

9

yes

1-

392

36

999

999

392

36

999

999

392

392

999

999

1-defr.

yes

240

2

999

999

240

392

392

5

999

1

6

999

999

999

1

20

2

60

2

heat.

-

°C

-

-

°C

°C

min.

min.

°C

°C

min.

min.

°C

°C

sec.

sec.

-

-

min.

-

min.

min.

min.

°C

°C

-

min.

-

-

sec.

sec.

min.

-

sec.

-

sec.

-

-

°F

-

-

°F

°F

min.

min.

°F

°F

min.

min.

°F

°F

sec.

sec.

-

-

min.

-

min.

min.

min.

°F

°F

-

min.

-

-

sec.

sec.

min.

-

sec.

-

sec.

-

-

0

no

0-cool.

4

1

240

30

0

1

240

30

-50

75

20

20

0-cool.

no

0(no)

0

15

15

0(no)

-50

200

1

0(no)

0(off)

0(no)

1

1

0(no)

0

0(no)

0

15

0(no)

-

0

no

0-cool.

39

1

240

30

32

1

240

30

-58

167

20

20

0-cool.

no

0(no)

0

15

15

0(no)

-58

392

1

0(no)

0(off)

0(no)

1

1

0(no)

0

0(no)

0

15

0(no)

Standard

Description

Содержание MT-514e

Страница 1: ...arm ALRM DEFR COMMON NO NC REFR HEAT NO NC COMMON COMMON 6 OPERATIONS 6 1 Quick Access Menu Map To access or browse in the quick access menu use the key quick touch while the temperature is being displayed by the controller Each touch displays the next function of the list for confirming use the key quicktouch Forfurtherdetails refertochapter6 3 REFR HEAT NO NC REFR HEAT NO NC COMMON COMMON Loads ...

Страница 2: ...nfirmwith Forchangingtheotherfunctions browsethe menu through the keys and proceed the same way in order to adjust them To exit the menu andreturntothenormaloperation press longtouch until isdisplayed OBS If the functions lockdown is enabled when pressing the keys the controller will display themessage LOC andwillnotallowparameteradjustment and or or or 6 5 Parameters table Legend yes yes no no Of...

Страница 3: ...tatuswiththesensordamaged Ifthesensorisinshort circuited offoroutofthemeasurerange thecompressorassumesthesetstatus inthisfunction 0 Compressoroff 1 Compressoron 2 Cyclingaccordingtotimesdefinedin F21 and F22 Note Ifintheheatingmode andinerror theoutputwillbeswitchedoff F21 Compressortimeonincaseoferror F22 Compressortimeoffincaseoferror These determine the minimum time the compressor will remain ...

Страница 4: ... the clipping for fixing in the extension frame is 71x29mm in varied situations sinceiteliminatesprecisioncuttoembedtheinstrument Allowscustomizationviaastickerwith the brand and the company contact and accompany two 10A 250 Vac switches that can trigger internal light aircurtain on offsystemorfan OFF eCAL pppp 7 SIGNALS Error in sensor Sensor disconnected or damaged Manual activation of defrost p...

Страница 5: ...t covered either natural wear and tear of parts external damage caused by falls or inadequate packaging of products LOSS OF WARRANTY Products will automatically lose its warranty in the following cases The instructions for assembly and use found in the technical description and installation procedures in Standard IEC60364 are not obeyed The product is submitted to conditions beyond the limits spec...