6.3.2 Forced Defrost

6.3.3 Functions Lockdown

To unlock, turn off the controller and reconnect it with the

>

 key pressed. Keep the key pressed until the 

message

 [LOC,]

 appears. When realizing it, the message 

[OFF,]

 will appear on the display.

6.3.4 Control Functions Shutdown

Forced defrost is carried out through the quick access menu. Press the 

;

 key (quick touch) until the 

message 

[defr] 

appears (flashing 

@

LED), then press key 

/

(quick touch) to select. Then, the 

message 

[defr][On,,]

 appears ( access 

@

LED).

To turn off defrost manually, press key 

;

(quick touch) until the message 

[defr]

 appears (flashing 

@

LED). Press the

/

 key (quick touch) to select. Then, the message 

[defr] [OFF,]

 appears 

(LED 

@

 off).

For safety reasons, this controller provides the ability to lock functions. With this setting enabled, the 
setpoint and the other parameters are protected against unauthorized changes. However, they can be 
visualized. In this condition, when trying to change these values, the message 

[LOC,]

 appears on 

display. To perform the functions lockdown it is necessary, first, that parameter “

[,F20]

 - 

Time for 

functions lockdown

 ” parameter is set to a value higher than 14 ( if lower than 15, the message 

[no,,] 

is shown, which means not allowing the lockdown of functions). With key 

;

(quick touch), 

select    , then press 

/

(quick touch), then keep the 

>

 key pressed until 

[LOC,]

 appears. When 

releasing the key, the message 

[On,,]

 will appear.

With the shutdown of the control functions the controller will operate only as a temperature indicator and 
output relay stays off.
The  way  to  operate  the  control  functions  shutdown  depends  on  the  parameter  setting  “

[,F21]

Control functions shutdown

”:

[,,,0]

Does not allow the shutdown of the control functions.

[,,,1]

Allows to turn on and off the control functions only if the functions are unlocked.

[,,,2]

Allows  to  turn  on  and  off  the  control  functions  even  when  the  functions  are  locked

With key 

;

(quick touch), select      , then press 

/

(quick touch) to confirm.

Then, the message 

[ctrl][Off,]

 will appear. At this time the temperature display will switch to the

 

[OFF,]

message. 

To turn the control functions on again, just follow the same procedure as that for shutdown, selecting 
with the 

;

 key (quick touch),     .Once the user presses the 

/

 key the message 

[ctrl][On,,]

will 

appear.

NOTE:  When  turning  the  control  functions  back  on,  the 

  will  continue 

respecting functions “

[,f09]

- output off minimum time” and “

[,f12]

 - Initial status when 

energizing the instrument.

MT-512 

e

 

2HP

6.3.5 

 

Visualization of Processes

6.3.6 Minimum and Maximum Temperature Record

To view the status and the elapsed time, press

>

(short press). Thus, the controller will display the 

status of the current process. the following messages may appear on the display:

[----]

control off

[del,]

initial delay 

[refr]

cooling 

[HoT,]

heating

[defr]

defrost

By pressing key 

<

 or also through the quick access menu (see chapter 6), the message 

[rEg,]

 will 

appear, followed by the minimum and maximum recorded temperatures.
To turn the current minimum and maximum values off, press key 

;

(short press), until the message

 

[CrEg]

is displayed. Press key

/

to confirm.

6.3.7  Unit Selection

To determine the unit in which the instrument will operate, enter function “

[,F01]

” with access code

 

[,231] 

press key 

/

now the user can select the unit by pressing keys 

<>

where the messages 

[,=C,]

or

[,=F,]

 will alternate. Press key 

/

to confirm the desired unit. Then, the indication that 

corresponds to the unit 

{

or

}

 will come on.

Every time the unit is changed, the parameters must be reconfigured, since they are assumed the 
"standard" values.

6.4  ADVANCED OPERATIONS

6.4.1 Changing the parameters of the controller

Access function 

[,F01]

pressing keys 

<

and

>

 simultaneously or through the quick access menu. 

After that, 

[,F01]

 will appear, then, press the

/

 key (short press). Use keys 

<

or 

>

to enter with 

access code 

[,123]

 and, when ready, press 

/

. Use keys 

<

or

>

 to access the desired function.

After selecting the function, press the key

/

 (short press), to visualize the set value for that function. 

Use keys 

<

or

>

 to change the value, and when ready, press

/

 to memorize the set value and return 

to  the  functions  menu.  To  exit  the  menu  and  return  to  normal  operation  (temperature  indication) 
press

/

(long press) until 

[----]

.

NOTE:

 In case temper proof function is active, when pressing keys 

<

or

>

, the controller will show 

message 

[LOC]

 in the display and will not allow the setting of parameters.

Access code: 123 (one hundred and twenty-three)

Desired temperature (Setpoint)

Indication displacement (Offset)

Minimum set point allowed to the end user

Maximum set point allowed to the end user

Control differential (hysteresis)

Operating mode

Minimum output time on

Minimum output time off

Cooling time (interval between defrosts)

Defrost time

Initial status when energizing the instrument

Temperature indication locked during defrost

Instrument energization delay

Additional time at the end of the first cycle

Compressor status with the sensor inoperative

Compressor time on in case of error

Compressor time off in case of error

Digital filter intensity

Time for functions lockdown

Control functions shutdown

[,F01]

[,F02]

[,F03]

[,F04]

[,F05]

[,F06]

[,F07]

[,F08]

[,F09]

[,F10]

[,F11]

[,F12]

[,F13]

[,F14]

[,F15]

[,F16]

[,f17]

[,f18]

[,F19]

[,F20]

[,F21]

Description

Fun

Min

Max Unit

-

-

5.0

200

200

20.0

1-heat.

999

999

999

999

1-defr.

yes.

240

240

2

999

999

9

60

2

-

°C

°C

°C

°C

ºC

-

sec

sec

min

min

-

-

min

min

-

min

min

-

sec

-

CELSIUS

-

-

-9

-58

-58

1

no

no

1

no

no

no

no

0

1

1

no

no

no

0-cool.

0-cool.

-

-

9

392

392

36

1-heat.

999

999

999

999

1-defr

yes

240

240

2

999

999

9

60

2

-

°F

°F

°F

°F

°F

-

sec

sec

min

min

-

-

min

min

-

min

min

-

sec

-

FAHRENHEIT

Min

Max Unit

Standard

-

-

-5.0

-50

-50

0.1

0-cool.

no

no

1

no

0-cool.

no

no

no

0

1

1

no

no

no

-

39

0

-58

167

1

20

20

240

30

no

no

no

0

15

15

no

no

no

0-cool.

0-cool.

-

4

0

-50

75

1.0

0-cool.

20

20

240

30

0-cool.

no

no

no

0

15

15

no

no

no

6.5 PARAMETERS TABLE

F01 - Access code:

The 

 has 2 different access codes:

[,123]

 It allows to modify the advanced parameters

[,231]

 It allows to choose the temperature unit, Celsius or Fahrenheit

F02 - Desired temperature (Setpoint):

It is the reference value for temperature control, that is, the temperature to be maintained in a controlled 
environment.

F03 - Indication displacement (Offset):

It allows to compensate any deviations in temperature caused by a sensor change or alteration of the 
cable's length.

F04 - Minimum setpoint allowed to the end user: 

It prevents that, by mistake, the setpoint temperature is set unreasonably low.

F05 - Maximum setpoint allowed to the end user: 

It

 

prevents that, by mistake, the setpoint temperature is set unreasonably high.

F06 - Control differential (hysteresis):

It is the difference in temperature (hysteresis) between turning ON and OFF the cooling (or heating) 
Example: If it is desired to control the temperature at 4.0 °C with a differential of 1.0 °C. Therefore, the 
cooling is switched off at 4.0 °C and switched back on at 5.0 °C (4.0 + 1.0).

MT-512 

e

 

2HP

F07 - Operating mode:

It allows to set the operating mode of the controller. 

[,,,0]

Cooling

[,,,1]

Heating

F08 - Minimum output time on:

It is the minimum time the compressor will stay on, that is, the time interval between the last start and the 
next stop.

F09 - Minimum output time off:

It is the minimum time the compressor will stay off, that is, the time interval between the last stop and the 
next start. It serves to relieve discharge pressure and increase the service life of the compressor.

Temperature [°C]

Setpoint

Cooling

Se Hysteresis

Time [S]

Relay OFF

Relay ON

4°C

5°C

Temperature [°C]

Setpoint

Heating

Setpoint - Hysteresis

Time [S]

4°C

5°C

Standard

Relay OFF

Relay ON

F10-Cooling time (interval between defrosts):

It corresponds to the time the controller will act on cooling. At the end of this time, the controller enters 
the defrost process.

F11 - Defrost time:

It is the defrost time. During this period, the relay will remain off. At its end, the controller will return to the 
cooling state.

F12 - Initial status when energizing the instrument:

It allows to carry out a defrost at the time the controller is energized.

MT-512 

e

 

2HP

MT-512 

e

 

2HP

MT-512 

e

 

2HP

Legend: 

[yes,]

= yes

              

[no,,]

= no

6.5.1 Parameters description

Содержание MT-512 E 2HP

Страница 1: ...n that deactivates the controlling outputs turning the instrument into a digital temperatureindicator APPLICATIONS Coldstorages Reachincoolers Stadupcoolers Industrialheating Coolingequipment Anyothertypeofequipmentrequiring precisetemperaturecontrol Powersupply MT 512E2HP 115or230Vac 10 50 60Hz MT 512EL2HP 12or24Vac dc 10 Controltemperature 50to105ºC 58to221 F Operatingtemperature 0to50ºC 32to122...

Страница 2: ... visualize the set value for that function Usekeys or tochangethevalue andwhenready press tomemorizethesetvalueandreturn to the functions menu To exit the menu and return to normal operation temperature indication press longpress until NOTE In case temper proof function is active when pressing keys or the controller will show message LOC inthedisplayandwillnotallowthesettingofparameters Access cod...

Страница 3: ...theUSBandSerialTTLareused together ENVIRONMENTALINFORMATION Packaging The materials used in the packaging of Full Gauge products are 100 recyclable Try to performdisposalthroughspecializedrecyclers Product The components used in Full Gauge controllers can be recycled and reused if disassembledbyspecializedcompanies Disposal Do not incinerate or dispose the controllers that have reached the end of ...

Страница 4: ...ormation as possible in relation to the issue detected must be sent to facilitate analysis testing and execution of the service These procedures and any maintenance of the product may only be provided by Full Gauge Controls Technical Support services in the company s headquarters at Rua Júlio de Castilhos 250 CEP 92120 030 Canoas Rio Grande do Sul Brasil Copyright 2013 All rights reserved Rev 03 ...

Отзывы: