6.3.8 Control functions shutdown

The shutdown of the control functions allows the controller to operate only as a temperature indicator, 
keeping the control outputs and alarms off. The use of this feature is enabled or disabled by the shutdown 
function of the control functions (F56). When enabled, the control functions and alarms are switched off 
(

[CTRL][OFF,]

) or on (

[Ctrl][ON,,]

) in the quick access menu through the

 [Ctrl]

 option. 

When the control functions are off, the message 

[OFF,]

is displayed alternating with the temperature 

and other messages. Also is possible turn on/ turn off  the control functions by pressing the key 

;

 for 5 

seconds. 

Note: 

The time defined in the startup delay function begins counting once the control functions are 

switched on again.

6.3.9 Stage of the process, elapsed time and temperature in sensors 

S2 and S3

The operating status of the controller can be displayed by pressing the 

>

 key (short press). A sequence 

of messages will be shown, indicating the current process, time (hh:mm) already elapsed in this stage, 
temperature  in  the  evaporator  (S2)  and  temperature  in  S3.  If  the  sensors  are  disabled,  their 
measurements will not be displayed.
Stages of the process:

[dEL,]

 Initial delay (delay at start of the instrument)

[Fan,]

 Fan-delay (delay for return of the fan)

[rEFr]

 Cooling

[Pre,]

 Pre-Defrost

[dEFr]

 Defrost

[dRAi]

 Drainage

[----]

 Control functions off

6.3.10 Minimum and Maximum Temperature Record

The display of the minimum and maximum temperature record can be checked through the quick access 
menu  or  by  pressing  the 

<

  key  while  displaying  the  temperature.  The  minimum  and  maximum 

temperatures recorded for each sensor are displayed in sequence preceded by identification messages 

[rEg,]

[,t-1]

 for ambient sensor (S1), 

[,t-2]

 for S2 (when active) and 

[,t-3]

 for S3 (when 

active).  To  delete  the  minimum  and  maximum  recorded  values,  hold  the 

<

  button  for  2s  when 

displaying  records  or  use  the 

[CrEg]

option  in  the  quick  access  menu.   The

 [rSET]

  message 

indicates that the records have been deleted.

6.3.11 Unit Selection

To select the temperature unit in which the instrument will operate enter the 

[,F01]

 function with 

access code 

[,231]

 and press the 

/

 key. Then, select the desired unit 

[,=C,]

 or 

[,=F,]

 using 

the 

<

or

>

keys. To confirm, press 

/

. Whenever the unit is changed, the function settings assume the 

default value, therefore needing to be reconfigured.

6.3.7 Functions Lockdown

The use of the functions lockdown adds greater security to the operation of the controller. When it is 
active, the setpoint and other parameters are visible to the user, but are protected against undue 
changes (F57=2) or you can block changes of control functions and leave the adjustment of the setpoint
enabled (F57=1). To activate the functions lock, access the 

[LOC,]

 option in the quick access menu.

Then 

[no,,]

 message will be displayed (lock must be enabled and inactive). With that on the display, 

press the

>

key for the time configured for the functions lock (F58), the activation is indicated by the 

 

[LOC,][On,,]

message. To enable the use of this function, F57 must be configured with 1 or 2. 

When trying to change the parameters, the

[LOC,]

message indicates that the functions lock is active, 

to deactivate it, turn the controller off and then turn it on again with the

>

key pressed. Keep the key 

pressed until the

 [LOC,][OFF,]

message indicates the unlocking 

(10 seconds)

.

6.4 Advanced operations

The  functions  menu  can  be  accessed  through  the  quick  access  menu,  option 

[Func]

  or 

simultaneously pressing 

<

and

>

while displaying the temperature. To allow changing the parameters, 

enter 

[,F01]

 by pressing 

/

 (short press), and using the 

<

 or 

>

keys enter code 123 (one hundred 

and twenty three). Confirm with 

/

. To modify the other functions, navigate the menu using the 

<

 or 

>

 keys and follow the same procedure to set them. To exit the menu and return to normal operation, 

press and hold

/

 until 

[----]

 appears. 

NOTE:

 If the functions lockdown is active when pressing the 

<

 or 

>

 keys, the controller will show the 

[LOC,]

 message on the display and will not allow the setting of parameters.

6.3.2 Fast Freezing

 

In  the  fast  freezing  mode  the  cooling  output  remains  permanently  activated,  thus  accelerating  the 
cooling or freezing process. This operating mode can be activated or deactivated in the quick access 
menu through the 

[FASt]

 option or through an external switch connected to the digital input (F52 or 

F53).  It  can  also  be  deactivated  automatically  by  low  temperature  (F33)  or  by  time  (F34).  During 
operation in the fast freezing mode, the compressor on indication flashes quickly and defrost keeps 
happening. If, when activating the fast freezing mode, the controller identifies that there is a defrost 
scheduled to start by time in this period, the defrost will be performed immediately before entering the 
fast freezing mode.

6.3.3 Economic setpoint (SPE) 

The 

[SP-E]

  provides  the  system  with  greater  economy  by  using  more  flexible  parameters  for 

temperature control (F27- Economic Setpoint and F28 - Control Differential). When active, the 

[ECO,] 

message is displayed alternating with the temperature and other messages. The operation in economy 
mode can be activated or deactivated through the commands: 

Function

Command

Action

6.3.4 Manual defrost

The defrost process can be activated/deactivated manually in the quick access menu through the 

[defr]

 (F52 or 

F53).  Activation  or  deactivation  will  be  indicated  by  the  messages 

[defr][On,,]

  or 

[defr][OFF,]

 respectively.

or pressing the 

<

 for 4 seconds or using external switch connected to digital input

6.3.5 How to determine the end of defrost by temperature

a)

 Reconfigure the listed functions at the end of the defrost to the maximum value:

- Cooling time (Interval between defrosts)

 F8 = 999min.

- Evaporator temperature to end defrost 

F13 = 105°C / 221°F

- Maximum defrost time

 F14 = 90min.

b) 

Wait for a while until a layer of ice forms in the evaporator.

c)

 Perform a manual defrost (using the 

;

scroll key up to 

[dEFr]

 and press 

/

).

d)

 Follow the melting process.

e)

 Wait until all of the ice in the evaporator has melted to consider the process completed.

f)

 With the defrost finished, check the evaporator temperature (S2) using the 

>

 key (see section 

6.3.9).

g)

 Using the value read in S2, set the temperature for end of defrost

- Evaporator temperature for end of defrost 

F13 =Temp. S2

h)

 For safety, reset the maximum defrost time, according to the type of defrost set. 

Eg:

- Electrical defrost (by resistance) 

F14 = 45min.

- Hot gas defrost 

F14 = 20min.

i)

Finally, set the cooling time 

(F8)

 at the desired value.

6.3.6 Defrost with two evaporators

With S3 configured for the 2nd evaporator (F52), the Fan output allows control of the second resistance. 
Defrost always starts with the two outputs triggered. The resistors are shut down individually as their 
evaporators reach the temperature to end defrost. With the two outputs off or having the maximum 
defrost time elapsed, the draining process is started. 

With these settings, all the features of the Fan 

are disregarded, including the Fan Delay process.

FAN-DELAY

COOLING

PRE-DEFROST

MAX. F20

IF F39=0

F08

F23

F17

F19

Unlock 
the indication

IF F39=1

F41

Lock the display
if enabled on F17

DEFROST

DRAINAGE

MAX. F14

F18

F13

Connection 12 Vac/dc

1

5 6 7 8

2 3 4

9

10 11 12 13 14 15 16 17

Sensor S1

D1/S3

D2

Sensor S2

CO

MP

DE

FR

FA

NS / 

DE

FR 2

24 Vac/dc

1

5 6 7 8

2 3 4

9

10

Sensor S1

D1/S3

D2

Sensor S2

Connection 24 Vac/dc

11 12 13 14 15 16 17

CO

MP

DE

FR

FA

NS / 

DE

FR 2

12 Vac/dc

6.5 Table of parameters

Loads supply

The 

sensor S1 (black) 

must be in the ambient.
The 

sensor S2 (gray)

 must 

be placed in the evaporator 
through metallic cramp.

Loads supply

F29

F30

F31

F32

F32

F52 / F53

F52 / F53

-

-

-

Activates

Deactivates

Stays activated

Deactivates

Stays deactivated

Activates / Deactivates

Stays deactivated

Activates / Deactivates

Stays deactivated

Deactivates

Closed door time to activate

S3-S1 temperature difference to deactivate

S3-S1 temperature difference to activate

Maximum time in economy mode

Maximum time in economy mode =0(no)

External key (digital input)

Open door indication (digital input)

Action through quick access menu (

[ECO,]

)

Error in ambient temperature reading (S1)

When switching on the instrument

CELSIUS

FAHRENHEIT

Min

Max

Standard

Unit

Description

Fun

[,F01]

[,F02]

[,F03]

[,F04]

[,F05]

[,F06]

Min

Max

Unit

0

0.1

-20

-50

-50

0 (NO)

 

 

999

20

20

105

105

30

 

 

-

°C

° C

° C

°C

min.

 

 

0

2

0

-50

105

0 (NO)

 

 

-

°F

°F

°F

°F

min.

 

 

0

1

-36

-58

-58

0 (NO)

 

 

999

36

36

221

221

30

 

 

0

3

0

-58

221

0 (NO)

 

 

Access code

Control differential (normal hysteresis)

Ambient temperature S1 indication offset

Minimum setpoint allowed to the end user

Maximum setpoint allowed to the end user

Delay at start (energization)

 

 

Standard