Full Gauge Controls EVOLUTION Multi-FG Скачать руководство пользователя страница 2

2)

In the same menu, power up the second controller, select a new address, and then press

/

. Repeat this operation until all controllers in the network have addresses configured.

NOTE: 

The menu 

[Add,]

 has a 15-second time limit if no key is pressed. The message 

[----]

is displayed after this time and returns to the temperature display.

3)

 After all addresses are configured, update the readings by pressing 

;

 ,select the menu 

[Chng]

 and press 

/

.

NOTE 1:

 If more than one address is added at each change, either manual or automatic (see item 11.1), the message 

[Addr]

 + number of the address to be viewed will be displayed.

NOTE 2: 

 If you want to erase all records in the scan list, enter the 

code 717

 in the menu 

[Code]

(see item 6.2).

7. ADVANCED CONFIGURATION

7.1 Searching instruments in the network

If a controller has an address other than 247, i.e. previously changed by 

 itself or by Sitrad, 

use this procedure to add to the list. This way the address will not be changed in the controller. Follow the 
steps below:

Step 1: 

With the security code previously entered (according to item 6.2), hold down keys

>

and

<

 

until the menu 

[sCan]

is displayed.

Step 2: 

Power up the controller to be inserted on the list.

Step 3: 

Press

/

 and then 

 will automatically search the network for addresses displaying 

the numbers from 

[,001]

 to 

[,246]

.

Signaling:

NOTE: 

To clear the whole scan list, go to the main menu (according to item 6.2), select the menu 

[code]

and  enter  the 

code  717.

 

  will  reboot  with  the  scan  list  without  registered 

addresses.

7.2 Removing an instrument from the scan list

With the security code previously entered (according to item 6.2), hold down the keys 

>

and

<

 until 

the menu 

[Del,]

is displayed. Select the value of the address to be removed from the list and then 

press  

/

. The message 

[Done]

will be displayed if the operation is successful.

The message 

[no,,]

will be displayed if the address is not on the list.

Multi-FG

Multi-FG

Multi-FG

8.2 Quick Access Keys Map

When controller is on temperature display mode, the following keys can be used as shortcuts for the 
following functions:

9. ACCESS MENU

10. ADJUSTING THE DESIRED TEMPERATURE

Access  the  main  menu  by  pressing  the  keys 

>

and

<

,  simultaneously.  The  menus  will  be 

displayed upon releasing the keys. It is also possible to access the main menu through the quick access 
menu (see item 8.1).

[Code]

 Enter the access code

[func]

 Functions of the controller's parameter table (related to the current instrument)

[Cnfg]

 

[Add,]

 Program the instrument in the controller and add it to the list (sending a new address)

[sCan]

 Search an instrument

[Del,]

 Remove an instrument from the list

Hold down the key 

/

 for 2 seconds to enter the setpoint adjustment menu. The message

 [SP,,]

 

will be shown in the display and then the value to adjust the normal setpoint. Use the keys 

>

or

<

 to 

change the value and press

/

to confirm. Then the message 

[SP-e]

 will be displayed to indicate the 

economy  setpoint  adjustment.  Use  the  keys 

>

or

<

again  to  change  the  value  and  press

/

.  to 

confirm. Finally the indication 

[----]

 is signaled concluding the configuration. The setpoints may also 

be adjusted individually in the quick access menu.

Multi-FG 

configurations

11. SETTINGS TABLE OF MULTI-FG

Instrument scan mode

Maximum update time

Time for functions lockdown

[,C01]

[,C02]

[,C03]

Description

Fun

Min

Max

Unit

Auto

20

60

-

sec.

sec.

Manual

5

No = 14

11.1 Description of the functions

C01- Instrument scan mode:

If more than one instrument is registered on the scan list, 

 allows changing the instrument 

view automatically at each interval defined in C02.
The views are displayed according to the instrument's address in ascending order.

NOTE: 

Even in the automatic mode the instrument may be changed manually by pressing 

;

to access 

the menu 

[Chng]

, and then pressing

/

.

C02 - Maximum update time:

This function defined the reading update time according to the following configurations:

Only one instrument registered: 

The elapsed time updates the data reading.

More than one instrument registered and C01 in manual mode: 

The elapsed time updates only the 

data reading of the instrument being viewed.

More than one instrument registered and C01 in automatic mode: 

The elapsed time changes the 

instrument to the next on the list in ascending order with the data reading updated.

C03 - Time for functions lockdown:

For safety reasons the controller has a feature to allow locking functions. When this configuration is 
active, the setpoint and other parameters are protected from undue changes. However, these can be 
viewed. In this condition the message

[LOC,]

no display. will be displayed when trying to change those 

values. 
To lock functions you need first to adjust the parameter 

Multi-FG

[,C03]

- Time for functions lockdown” with a 

value greater than 14 (below 15, 

[no,,]

is displayed and it means that function lockdown is not 

allowed).  Using  the  key 

;

(quick  touch)  select  the  function  lock  function  and  then  press

/

(quick 

touch). After that, hold down the key

>

until 

[LOC,][On,,]

is displayed.

EM DESENVOL

VIMENT

O

To unlock, turn the controller off and then turn it on again with the key 

>

pressed. Hold down the key 

until the message 

[LOC,][OFF,]

 indicates the unlocking

 (10 seconds)

.

Multi-FG

ADDRESS 1

ADDRESS 2

CONFIGURING

A

A

B

B

A B

B A

Multi-FG

Sitrad

VEE

Power

MULTI-FG

  2 |

multi-FG (B)

1 |

multi-FG (A)

SITRAD 

  11 |

SITRAD (A)

12 |

SITRAD (B)

RELAYS

13-14 | 

fans

15-16 |

compressor

17-18 | 

defrost

Line

SENS. PRESS.

3 |

4~20mA (green)

4 |

12Vdc (brown)

|

Power Supply

 

12Vdc - 1.3A

vx-

950 

plus

SENS. TEMP. / DIG. IN

9-10 |

sens. ambient temp.

8-9 |

sens. evap. temp.

6-7 | 

sens. suction temp.

5-6 |

digital input (door)

 

 

 

 

 

A B

A

A

B

B

A B

A B

Multi-FG

Sitrad

VEE

Power

MULTI-FG

  2 |

multi-FG (B)

1 |

multi-FG (A)

SITRAD 

  11 |

SITRAD (A)

12 |

SITRAD (B)

RELAYS

13-14 | 

fans

15-16 |

compressor

17-18 | 

defrost

Line

SENS. PRESS.

3 |

4~20mA (green)

4 |

12Vdc (brown)

|

Power Supply

 

12Vdc - 1.3A

vx-

950 

plus

SENS. TEMP. / DIG. IN

9-10 |

sens. ambient temp.

8-9 |

sens. evap. temp.

6-7 | 

sens. suction temp.

5-6 |

digital input (door)

Multi-FG

Sitrad

VEE

Power

MULTI-FG

  2 |

multi-FG (B)

1 |

multi-FG (A)

SITRAD 

  11 |

SITRAD (A)

12 |

SITRAD (B)

RELAYS

13-14 | 

fans

15-16 |

compressor

17-18 | 

defrost

Line

SENS. PRESS.

3 |

4~20mA (green)

4 |

12Vdc (brown)

|

Power Supply

 

12Vdc - 1.3A

vx-

950 

plus

SENS. TEMP. / DIG. IN

9-10 |

sens. ambient temp.

8-9 |

sens. evap. temp.

6-7 | 

sens. suction temp.

5-6 |

digital input (door)

A

A

B

B

A B

A B

12Vdc

1.3A

 

 

12Vdc

1.3A

 

 

12Vdc

1.3A

Multi-FG

115/230 Vac MAINS

8. OPERATIONS

8.1 Quick Access Menu Map

To access or browse in the quick access menu use the key 

;

(quick touch) while the temperature is 

being displayed by the controller. Each touch displays the next function of the list; for confirming, use the 
key

/

(quick touch).

FUNCTIONS LOCKDOWN

CONTROL FUNCTIONS

(ON/OFF)

;

SWITCH THE VIEW TO THE NEXT

REGISTERED INSTRUMENT

;

;

MULTI-FG 

CONFIGURATION

EXIT FUNCTION

;

FUNCTION SELECTION

;

CURRENT PROCESS 

VIEWER

;

ERASE MIN. AND MAX. 

RECORD VALUES

;

MIN. AND MAX. TEMPERATURE 

RECORD

;

Multi-FG

Multi-FG

Multi-FG

Multi-FG

Multi-FG

Multi-FG

Multi-FG

Multi-FG

;

Multi-FG

DEFROST (ON/OFF)

ECONOMY SETPOINT (ON/OFF)

;

Multi-FG

;

Multi-FG

/

<

<

Hold down for 2 seconds: Setpoint adjustment.
Quick touch: Displays the current process, process time, and sensor data.

Quick touch: Maximum and minimum records display.

<

Hold down for 2 seconds: Erases the maximum and minimum records.

<

Hold down for 2 seconds: When the buzzer is active, disables the audible 

alarm.

<

Hold down for 4 seconds: Carries out manual defrost.

<

<

Quick touch: Enters function selection.

and

Default

Auto

8

No

The address is already being used by another instrument.

The address searched found a new instrument in the network.

[uSed]

[done]