You can expect our batteries meet with the standards JIS, DIN, IEC & BS6290-4.We have obtained ISO9001 certification. We have obtained UL and CE approval for all types of batteries. All 

these render our batteries to be compatible with requirements of world-level equipments. 

M

M

A

A

I

I

N

N

T

T

E

E

N

N

A

A

N

N

C

C

E

E

 

 

- Check the tightening of connections. 

- Every month, it is recommended that the total voltage at the battery terminals be measured. It should be 2.27-2.30Vpc at a temperature of 20

. Once each year, it is recommended that 

the voltage of each cell in the battery should be read off. 

- A difference of plus or minus 2.0% between these individual voltages and the average voltage may be observed. This is due to the gas- recombination process. 

- A check on capacity (independent operation on load) can be performed once or twice per year. 

Safety: When carrying out any work on the battery, the applicable safety standards should be followed. 

Note: it is recommended that a battery log be maintained, and that records should be kept of the total voltage measurements, any mains failures, major battery discharges (current and time) 

etc. 

The main factors causing reduction in the life expectancy of 

FULI DC 

Series cells: 

- Deep discharges      - Poor regulation on the float voltage      - Cycling or micro- cycling    - Poor quality (smoothing) of the charging current    - High ambient temperature. 

I

I

N

N

S

S

T

T

A

A

L

L

L

L

A

A

T

T

I

I

O

O

N

N

 

 

O

O

F

F

 

 

T

T

H

H

E

E

 

 

B

B

A

A

T

T

T

T

E

E

R

R

Y

Y

 

 

General recommendations 

- Do not wear clothing of synthetic material, to avoid the generation of static potentials. 

- Use insulated tools. 

- Consult the drawing for the correct position of the cell poles (positive=red colour, negative = black colour). 

- Before attaching the inter-cell flexible cables, check that all terminals are in the correct position.   

- The battery cells are connected in series, which is with a positive pole connected to a negative pole. 

Содержание Deep Cycle series

Страница 1: ...te leakage can occur from the terminals or case of any FULI battery This feature insures safe and efficient operation of FULI batteries in any position FULI batteries are classified as Non Spillable and will meet all requirements of the International Air Transport Association I A T A Dangerous Goods Regulation Long Service Life Float or Cyclic The FULI VRLA battery has a long life in float or cycl...

Страница 2: ...RLA batteries It is necessary to closely control the actual voltage to ensure that it is within the limits advised Float Service 2 25 2 30 Vpc at 25 Cycle Service 2 4 2 45 Vpc at 25 FULI suggests that the initial current be set within 0 2 C Amps Figure 1 shows one example of a constant voltage charging Constant Current Charging This method of charging is generally not recommended for VRLA batterie...

Страница 3: ...p between temperatures and charging voltages in both cyclic and standby applications Effect of Voltage on Battery Gassing Although the batteries are of the recombination type and the amount of gassing at normal operating voltages and temperature are negligible if the charging voltage is increased gassing will occur despite the recombination design of the product Gassing does not normally occur whi...

Страница 4: ...oximately 3 per month when stored at an ambient temperature of 25 The self discharge rate will vary as a function of ambient storage temperature Figure 4 shows the relationship between storage times at various temperatures and the remaining capacity Shelf life In general when lead acid batteries of any type are stored for extended periods of time lead sulphate is formed on the negative plates of t...

Страница 5: ... current of 0 1C Amps or 15 to 20 hours at constant voltage of 2 45Vpc Within 12 months after manufacture 8 10 hours at constant current of 0 1C Amps or 20 24 hours at constant voltage of 2 45Vpc In order to successfully top charge a battery stored for more than 12 months the open circuit voltage must be checked to ensure that it is higher than 2 0 volts per cell Therefore ALWAYS check the open ci...

Страница 6: ...an be performed once or twice per year Safety When carrying out any work on the battery the applicable safety standards should be followed Note it is recommended that a battery log be maintained and that records should be kept of the total voltage measurements any mains failures major battery discharges current and time etc The main factors causing reduction in the life expectancy of FULI DC Serie...

Страница 7: ...ts into contact with your skin or eyes generously wash the affected area with clean water and consult a physician immediately 4 Batteries explode if put into the fire Never dispose of batteries in the fire 5 Mixed usage of batteries differing in capacity type manufacturer or history of use charge discharge operation must be AVOIDED for this may damage the batteries and the equipment due to the dif...

Отзывы: