Line
Function
Setting range or display
Setting
increment
Basic setting
Domestic Hot Water (Only with the DHW kit option)
1610
Nominal setpoint
Reduced setting (line 1612)…
to 65 °C
1
50 °C
The backup electrical system is required to reach this level.
1612
Reduced setpoint
8 °C...
to Nominal setpoint (line 1610)
1
25 °C
Swimming pool (Only with swimming pool kit option)
2056
Setpoint source heating
8... 35 °C
22 °C
Fault
6711
Reset HP
No, Yes
No
Service / Special operation
7141
Emergency operation
Off, On
Off
Off : The heat pump does not use the boiler connection when a fault occurs (error 370).
On : The heat pump uses the boiler connection when a fault occurs (error 370).
In the "On" position, the energy costs can be onerous if the error is not eliminated.
Diagnostics heat generation
8410
Return temp HP
0... 140 °C
Setpoint (return) HP
0... 140 °C
8412
Flow temp HP
0... 140 °C
Setpoint (flow) HP
0... 140 °C
8413
Compressor modulation
0... 100%
Diagnostics consumers
8700
Outdside temperature
-50... 50 °C
8701
Outside temp min
Reset ? (No, Yes)
-50... 50 °C
8702
Outside temp max
Reset ? (No, Yes)
-50... 50 °C
8740
Room temperature 1
0... 50 °C
20 °C
Room setpoint 1
4... 35 °C
20 °C
8743
Flow temperature 1
0... 140 °C
50 °C
Flow temperature setpoint 1
0... 140 °C
50 °C
8756
Flow temp cooling 1
0... 140 °C
0
Flow temp setpoint cooling 1
0... 140 °C
0
8830
DHW (domestic hot water) temperature
0... 140 °C
DHW temperature setpoint
5... 80 °C
50 °C
Operation manual "1408 - EN"
- 11 -
Control Box