En-5

Remove 4 screws and remove the cover of main unit.

Screws

7.1.  Connecting the power supply cable

for U.S.A. and Canada

(1)  Remove the 4 screws (M4 × 6 mm), and then remove the cover.
(2)  Remove the dust proof bushing and open the knockout hole.
(3)  Install the conduit.
(4)  Fix the conduit with lock nut.
(5)  Pass the power supply cable through the conduit.
(6)  Connect the power supply cable to their respective terminal block.
(7)  Then confirm that the cable will not come out.

Conduit 

(Power supply cable)

[Trade size: 1/2 in.]

Knockout hole

Power supply cable

Lock nut

for Others

(1)  Remove the 4 screws (M4 × 6 mm), and then remove the cover.
(2)  Make a hole in the center of the dust proof bushing with the Phillips 

head screwdriver.

(3)  Pass the power supply cable through the hole of dust proof bushing 

and pull it into the MODBUS convertor.

(4)  Connect the power supply cable to their respective terminal block.
(5)  Securely tighten the cable tie and then confirm that the cable will not 

come out.

Dust proof bushing

Power supply cable

Cable tie

(Accessories)

Cable tie *

(Accessories)

The screw hole

* When wiring the cable to the opposite side, fix the cable as shown below:
(1)  Remove the cable tie holder attached to the sheet metal.
(2)  Attach the cable tie holder to the screw hole in the direction where the 

cable is wired. 

(3)  Fix the cable with the cable tie.

7.2.  Connecting the transmission cables

(1)  Turn the power off.
(2)  Make a hole in the center of the dust proof bushing using a driver.
(3)  Pass the transmission cables through the hole of dust proof bushing 

and pull it into the MODBUS convertor.

(4)  Connect the transmission cable to terminal block to connect to VRF 

network.

(5)  Connect the transmission cable to accessory MODBUS Connector to 

connect to MODBUS network.

(6)  Connect the MODBUS cables to  (D+), RS485_B- (D-), and 

Common (COM) according to the polarity of the master unit.

(7)  Attach the MODBUS connector to the board terminal.
(8)  When using MODBUS cable with shield, earth (ground) at one end of 

cable. If this unit is earthed (grounded), connect to the Earth (Ground) 

terminal. Do not connect the shield to the Common (COM).

(9)  Securely tighten the cable ties and then confirm that the cable will not 

come out.

(10) Once the wiring of the cables has been completed, mount the cover 

to the MODBUS convertor. Use the screws (M4 × 6 mm) to mount the 

cover.

(11) Use the 4 screws (M4 × 16 mm) provided to mount the MODBUS 

convertor to the behind ceiling, wall, floor or other suitable location. 

 

Содержание UTY-VMGX

Страница 1: ...English INSTALLATION MANUAL MODBUS CONVERTOR FOR VRF For authorized service personnel only PART NO 9374707133 03 UTY VMGX Original instructions ...

Страница 2: ...purposes such as storing food raising animals growing plants or preserving precision devices or art objects It can degrade the quality of the preserved or stored objects Install the unit in a well ventilated place avoiding rains and direct sun light Do not operate this unit when your hands are wet Touching the unit with wet hands will cause an electric shock If children may approach the unit take ...

Страница 3: ...n away from television and ra dio to avoid distorted images and noise Otherwise a malfunction could result Perform wiring so that water does not enter this unit along the external wiring Always install a trap to the wiring or take other countermeasures Otherwise it will cause trouble or electric shock or fire Confirm the name of each unit and name of each terminal block of the unit and connect the...

Страница 4: ...bles using an appropriate tool so that the cables do not come loose 3 Use the specified cables connect them securely and fasten them so that there is no stress placed on the terminals 4 Use an appropriate screwdriver to tighten the terminal screws Do not use a screwdriver that is too small otherwise the screw heads may be damaged and prevent the screws from being properly tight ened 5 Do not tight...

Страница 5: ...6 in Tightening torque for installing cables to MODBUS connector 0 22 to 0 25 N m 1 9 to 2 2 lbf in 2 2 to 2 5 kgf cm 7 INSTALLING THE MODBUS CONVERTOR WARNING Always use the accessories and specified installation work parts Check the state of the installation parts Not using the specified parts will cause units to fall off electric shock fire etc Install at a place that can withstand the weight o...

Страница 6: ...e cable as shown below 1 Remove the cable tie holder attached to the sheet metal 2 Attach the cable tie holder to the screw hole in the direction where the cable is wired 3 Fix the cable with the cable tie 7 2 Connecting the transmission cables 1 Turn the power off 2 Make a hole in the center of the dust proof bushing using a driver 3 Pass the transmission cables through the hole of dust proof bus...

Страница 7: ... Factory setting When setting address please be sure that the address of MODBUS Convertor is not overlap the address of other controller like Touch Panel Controller Network Convertor for Group Remote Controller When the rotary switch is set to 16 or more MODBUS convertor Remote Controller Address setting is 15 2 Terminal resistance setting SW SET2 1 When there is no other terminal resistance in th...

Страница 8: ...3 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 17...

Страница 9: ...erminal resistances Set the terminal resistances at the both ends to be valid and set the terminal resistances other than at the both ends to be invalid ON Terminal resistance valid OFF Terminal resistance invalid Default The switches from 5 to 8 are read at the time of power on Even if these switches are changed after power on the setting is not reflected 10 Unused SW SET2 2 SET6 1 SET7 1 to 3 No...

Страница 10: ...itch SET2 3 to ON 2 The indoor unit registered to the convertor starts the test run 3 Check that the indoor unit registered to the convertor performs the test run 4 Turn the test run switch SET2 3 to OFF 5 The indoor unit which performs the test run stops it When 60 minutes passes after the start of test run test run of indoor unit ends automatically Always turn the test run switch SET2 3 to OFF 1...

Страница 11: ...ach manual Error indications Error contents LED1 green LED2 orange LED3 red 1 5 Scan error 1 6 Peripheral unit communication error Error indications Error contents LED5 green LED6 orange LED7 red 11 1 Peripheral unit main PCB error Display mode 0 5s ON 0 5s OFF 0 1s ON 0 1s OFF Number of flashing ...

Отзывы: