Fujitsu UTY-TWRX Скачать руководство пользователя страница 1

En-1

AIR CONDITIONER

OPTIONAL PARTS

Terminal block kit for 2-wire remote controller

INSTALLATION MANUAL

 For authorized service personnel only.

PART No. 9380828068

 

1. SAFETY PRECAUTIONS

• Hand this manual to the customer to keep for future use, such as for relocating or repairing the product.

 

WARNING

Indicates a potentially or imminently hazardous situation which, if not avoided, could result in death or 
serious injury.

For the air conditioner to operate satisfactorily, install it as outlined in this installation manual.
Installation work must be performed in accordance with national wiring standards by authorized personnel only.
Do not turn on the power until all installation work is complete.
Discharge static electricity before the installation.

 

CAUTION

Indicates a potentially hazardous situation that may result in minor or moderate injury or damage to 
property.

Do not wire the terminal block kit wire together with or parallel to the connection cables, transmission cables, remote controller 
cables, bus wire, and power supply cables of the indoor and outdoor units. It may cause erroneous operation.
Do not touch the aluminum 

fi

 n in the indoor unit.

When installing, do not cut or pinch the wires with the front panel or control box cover. An electric shock may occur if wires are damaged.

 

2.  ABOUT THE UNIT

 

  2.1.  Parts and accessories

• The following installation parts are supplied. Use them as required.

Name and shape

Q'ty

Description

Installation 
manual

 

1

This manual

Terminal block 
(with wire)

 
 

1

For connecting the 
wired remote control 
unit to the indoor unit 
main PCB.

Screw (M4x25)

 

1

For installing the terminal 
block to the indoor unit.

Name and shape

Q'ty

Description

Screw (M4x14)

1

For installing the cable 
to the indoor unit.

Cable clamper

1

For installing the cable 
to the indoor unit.

Communication PCB

1

For connecting the 
remote controller to the 
indoor unit.

Holder

 

2

For attaching the 
communication PCB to 
the main PCB.

Contents

1. SAFETY 

PRECAUTIONS 

............................................................................................................................................................ 1

2. ABOUT 

THE 

UNIT

2.1. Parts and accessories ........................................................................................................................................................... 1

3. INSTALLATION 

WORK

3.1. Front panel, control box cover removal ................................................................................................................................. 2
3.2. Installing the terminal block ................................................................................................................................................... 2
3.3. Connecting the remote controller cable ................................................................................................................................ 3
3.4. Installing the communication PCB to the indoor unit main PCB ........................................................................................... 4
3.5. Front panel, control box cover replacement .......................................................................................................................... 4

9380828068_IM_EN.indd   1

9380828068_IM_EN.indd   1

11/11/2015   1:30:34 PM

11/11/2015   1:30:34 PM

Содержание UTY-TWRX

Страница 1: ...cables of the indoor and outdoor units It may cause erroneous operation Do not touch the aluminum fin in the indoor unit When installing do not cut or pinch the wires with the front panel or control box cover An electric shock may occur if wires are damaged 2 ABOUT THE UNIT 2 1 Parts and accessories The following installation parts are supplied Use them as required Name and shape Q ty Description ...

Страница 2: ...remove the intake grille in direction of the arrow b Intake grill removal b a 2 Remove 4 caps 3 Remove wire cover screw then remove the wire cover 4 Remove 10 screws Wire cover screw Screws 10 places Caps 4 places Wire cover 3 2 Installing the terminal block 1 Attach the terminal block to the indoor unit firmly with 1 screw M4x25 accessory 2 Place the wiring as per the figure Place the wires from ...

Страница 3: ... match For details refer to the installation manual of the remote controller 2 Install the cable as shown in the following photographs Be sure to place the wiring under the tabs 3 Fix the cable with the cable clamper and screw M4x14 accessory Tab Cable clamper and screw M4x14 accessory Remote controller cable Red White Front view Right view CAUTION Do not connect the wired remote controller to the...

Страница 4: ...place the intake grille Front panel Top hooks 3 places Top holes 3 places Indoor unit Middle hooks 5 places Middle hooks 5 places c Press down on 4 places Intake grill installation Cut Knockout holes Knockout holes Front panel 3 5 Front panel control box cover replacement Reinstall by reversing the procedure in 3 1 Front panel control box cover removal 3 4 Installing the communication PCB to the i...

Отзывы: