Fujitsu UTY-RNRUZ2 Скачать руководство пользователя страница 1

En-1

1. SAFETY PRECAUTIONS

• The “SAFETY PRECAUTIONS” indicated in the manual contain impor-

tant information pertaining to your safety. Be sure to observe them.

• For details of the operation method, refer to the operating manual.
• Request the user to keep the manual on hand for future use, such as for

relocating or repairing the unit.

 WARNING

Indicates a potentially or imminently hazardous situ-

ation which, if not avoided, could result in death or 

serious injury.

Installation of this product must be done by experienced service techni-

cians or professional installers only in accordance with this manual. 

Installation by nonprofessional or improper installation of the product 

may cause serious accidents such as injury, water leakage, electric 

shock, or fire. If the product is installed in disregard of the instructions in 

this manual, it will void the manufacturer’s warranty.
Installation must be performed in accordance with regulations, codes, 

or standards for electrical wiring and equipment in each country, region, 

or the installing place.
Do not operate this unit when your hands are wet. Touching the unit with 

wet hands will cause an electric shock.
When children can approach the unit or touch the unit, take preventive 

measures.
Dispose of the packing materials safely. Tear and dispose of the plastic 

packing bags so that children cannot play with them. There is the dan-

ger of suffocation if children play with the original plastic bags.

 CAUTION

Indicates a potentially hazardous situation that may 

result in minor or moderate injury or damage to 

property.

When detecting the room temperature using the remote controller, 

please set up the remote controller according to the following conditions. 

If the remote controller is not well set, the correct room temperature will 

not be detected, and thus the abnormal conditions like “not cool” or “not 

heat” will occur even if the air-conditioner is running normally. :
• A location with an average temperature for the room being air condi-

tioned.

• Locate where is not be affected by inflow of outside air such as caused

by opening and closing a door.

• Not directly exposed to the outlet air from the air conditioner.
• Out of direct sunlight.
• Away from the influence of other heat sources.

REMOTE CONTROLLER 

(WIRED TYPE)

INSTALLATION MANUAL

PART No. 9373328407

For authorized service personnel only.

Installation by endusers or not qualified persons can cause harm to 

personal safety, can cause severe damage to building and product, can 

lead to improper function or reduced lifetime of the equipment.

Do not install the unit in the following areas:
• Do not install the unit near a source of heat, steam, or flammable gas. 

Otherwise, fire could result.

• Area filled with mineral oil or containing a large amount of splashed oil 

or steam, such as a kitchen. It will deteriorate plastic parts, causing the 

parts to fall.

• Area containing equipment that generates electromagnetic interfer-

ence. It will cause the control system to malfunction, and cause er-

roneous operation.

• Install the unit in a well-ventilated place avoiding rains and direct sun-

light.

Do not touch the switches with sharp objects. Doing so will cause injury, 

trouble, or electric shock.
Do not expose this unit directly to water. Doing so will cause trouble, 

electric shock, or heating.
Do not set vessels containing a liquid on this unit. Doing so will cause 

heating, fire, or electric shock.

2. MAIN UNIT AND ACCESSORIES

The following installation parts are supplied. Use them as required.

Name and shape

Q’ty

Name and shape

Q’ty

Wired remote controller

1

CD-ROM

1

Installation manual

(This manual)

1

Screw (M4 × 16mm)

For installing the remote 

controller

2

Operating manual

1

Cable tie

For remote controller and 

remote controller cable 

binding

1

3. ELECTRICAL REQUIREMENT

When connecting the remote controller use the following wiring.

Cable size

Wire type

Remarks

22 to 16 AWG

(0.33 to 1.25 mm²)

Non polar 

2 core

Use sheathed 

twisted pair cable

18AWG

Thermostat cable 

2 core

Use sheathed non 

twisted pair cable

Select a flexible cable that can be bound using cable ties from over the 

cable sheath inside this unit.

Maximum connectable number of remote controllers by cable size and the 

length.

Cable size

Max. connectable number of  

remote controllers

AWG

mm²

L* ≤ 328 ft

(L* ≤ 100 m)

328 ft < L*  

≤ 820 ft

(101 m < L*  

≤ 250 m)

820 ft < L*  

≤ 1,640 ft

(251 m < L*  

≤ 500 m)

VRF RAC VRF RAC VRF RAC

16

1.25

4

2

4

2

4

2

18

0.75 (1.25 > S* ≥ 0.75)

4

2

4

2

2

2

20

0.5 (0.75 > S* ≥ 0.5)

4

2

2

2

2

2

22

0.3 (0.5 > S* ≥ 0.3)

4

2

1

1

1

1

*L: Total cable length, *S: Cable size

Français

Español

English

CONTENTS

1.  SAFETY PRECAUTIONS .........................................................................1

2.  MAIN UNIT AND ACCESSORIES ............................................................1

3.  ELECTRICAL REQUIREMENT ................................................................1

4.   SELECTING AN INSTALLATION LOCATION ..........................................2

5.   INSTALLING THE REMOTE CONTROLLER ...........................................3

6.  SETTING THE REMOTE CONTROLLER ................................................5

7.  TEST RUN ..............................................................................................10

8.  ERROR CODES .....................................................................................10

9373328407-01_IM.indb   1

2/22/2017   11:06:13 AM

Содержание UTY-RNRUZ2

Страница 1: ...For authorized service personnel only Installation by endusers or not qualified persons can cause harm to personal safety can cause severe damage to building and product can lead to improper function or reduced lifetime of the equipment Do not install the unit in the following areas Do not install the unit near a source of heat steam or flammable gas Otherwise fire could result Area filled with mi...

Страница 2: ...witch to Occupied even if the indoor unit starts operation Anti freeze operation Away operation Optimum start operation j Menu Set the various settings k Status Check the status of indoor unit and error l Vacation When this is touched the schedule is disabled and the indoor unit remains unoccupied Vacation is displayed only when a schedule is set Refer to operating manual m Custom Auto Mode or Awa...

Страница 3: ...nt case screws are removed Otherwise injury could result Install the remote controller cables 1 m away from television and radio to avoid distorted images and noise Confirm the name of each terminal block of the unit and connect the wiring in accordance with the directions given in the manual Improper wiring work will damage the electric parts and cause smoke and fire Connect the connectors secure...

Страница 4: ...ot propagate to the terminal connection even if force of 30 N is applied to the cable Select a flexible cable that can be bound using cable ties from over the cable sheath inside this unit Cable tie GOOD PROHIBITED 5 3 3 Attach the front case Connect the remote controller cable connector to the connector of the front case PC board Insert after adjusting upper part of front case Otherwise there is ...

Страница 5: ...age Setting screen has two pages You can switch be tween the pages by touching Next Page or Previous Page Touch the language to be used Touch OK to display the R C Master Slave Setting screen Deutsch Español Ё Français Język polski Language Setting Page 1 2 Cancel OK Next Page English Language Setting Page 2 2 Cancel OK Русский Previous Page Português Türkçe Italiano Ελληνικά Dutch 6 2 3 R C Maste...

Страница 6: ...ch Next Page or Previous Page to switch between screens Touch the items you wish to configure Items that indoor unit does not support are not displayed Back Next Page Page 1 3 Initial Setting Language Setting Date Setting R C Group Name Setting Temp Unit Setting Back Previous Page Page 2 3 Initial Setting R C Sensor Setting Password Setting Display Item Setting Master Indoor Unit Setting Next Page...

Страница 7: ...or Unit another indoor unit cannot be made the master indoor unit unless the settings of the current master indoor unit are cancelled beforehand Reset cannot be performed while the indoor unit is operating 6 3 7 Password Setting administrator password Set or change the administrator password 1 Touch the Password Setting on the Initial Setting screen The Password Setting screen is displayed Then to...

Страница 8: ...nit X whose address you want to interchange 3 The address selection screen is displayed Select the address of the indoor unit you want to match to the display number selected at step 2 with or When OK is touched the display returns to the screen of 2 and the address is interchanged with the selected display number Unit X Repeat steps 2 and 3 up to the desired order When Back of the screen of 2 is ...

Страница 9: ... indoor unit 1 Touch the I U Address Verification on the Maintenance screen The I U Address Verification screen is displayed If there are multiple pages you can switch between them by touch ing Next Page or Previous Page Touch Check to display the indoor unit address checking start screen 2 Touch Yes to display the confirmation screen 3 Select the indoor unit to be checked If there are multiple pa...

Страница 10: ...ance Other Settings 6 4 5 Test Run 8 ERROR CODES Check the error 1 If an error occurs an error icon appears on the Monitor mode screen Touch the Status on the Monitor mode screen The Status screen is displayed 2 Touch the Error Information on the Status screen The Error Information screen is displayed If there are no errors the Error Information will not be displayed 3 2 digit numbers correspond t...

Отзывы: