En-7

C: Inlet air thermistor/D: Outlet air thermistor

Install in a location where the effects of heat sources such as heat exchangers and heat-
ers, etc., are minimized as far as possible.

C

D

Inlet air thermistor 
(Accessories)

Outlet air thermistor 
(Accessories)

Air outlet

Air inlet

General indoor unit

7. ELECTRICAL WIRING

 

WARNING

Electrical work must be performed in accordance with this Manual by a person 
certi

fi

 ed under the national or regional regulations. Be sure to use a dedicated circuit 

for the unit. An insuf

fi

 cient power supply circuit or improperly performed electrical work 

can cause serious accidents such as electric shock or 

fi

 re.

Before starting work, check that power is not being supplied to the all units.

Use the included connection cables and power cables or ones specified by the 
manufacturer. Improper connections, insuf

fi

 cient insulation, or exceeding the allowable 

current can cause electric shock or 

fi

 re.

For wiring, use the prescribed type of cables, connect them securely, making sure 
that there are no external forces of the cables applied to the terminal connections. 
Improperly connected or secured cables can cause serious accidents such as 
overheating the terminals, electric shock, or 

fi

 re.

Do not modify the power cables, use extension cables, or use any branches in the 
wiring. Improper connections, insufficient insulation, or exceeding the allowable 
current can cause electric shock or 

fi

 re.

Match the terminal board numbers and connection cable colors with those of the 
outdoor unit (or RB unit). Erroneous wiring may cause burning of the electric parts.

Securely connect the connection cables to the terminal board. In addition, secure the 
cables with wiring holders. Improper connections, either in the wiring or at the ends of 
the wiring, can cause a malfunction, electric shock, or 

fi

 re.

Always fasten the outside covering of the connection cable with the cable clamp. (If 
the insulator is chafed, electric discharge may occur.)

Securely install the electrical box cover on the unit. An improperly installed electrical 
box cover can cause serious accidents such as electric shock or 

fi

 re through exposure 

to dust or water.

Install sleeves into any holes made in the walls for wiring. Otherwise, a short circuit 
could result.

Install an earth leakage breaker. In addition, install the earth leakage breaker so that 
the entire AC main power supply is cut off at the same time. Otherwise, electric shock 
or 

fi

 re could result.

Always connect the earth (ground) cable.
Improper earthing (grounding) work can cause electric shocks.

Install the remote controller cables so as not to be direct touched with your hand.

Perform wiring work in accordance with standards so that the DX-kit can be operated 
safely and positively.

Connect the connection cable 

fi

 rmly to the terminal board. Imperfect installation may 

cause a 

fi

 re.

If the supply cable is damaged, it must be replaced by the manufacturer, its service 
agent or similarly quali

fi

 ed persons in order to avoid a hazard.

Take special precaution for connection to the external controller (DDC, 

fi

 eld supply).

Make sure the wiring for the external input and output signals is correct.
Miswiring of these cables could damage the entire system.

5.5. Installing heat insulation

 

CAUTION

After checking for gas leaks (refer to the Installation Manual of the outdoor unit), 
perform this section. Failure to do so may cause water leaks.

Implement heat insulation as shown in the diagram below.
(1)  Mount the rubber sheets (accessories).
(2)  Mount the heat insulations (accessories). There should be no gaps between the 

insulation and the product.

(3)  Secure to a pipe using 2 cable ties.

(1)  Butyl rubber sheets 

(Accessories)

(2)  Heat insulations 

(Accessories)

(3)  Cable ties 

(Large, accessories)

No gap

•  Perform the work in (1), (2) and (3) for the 2 pipes.
•  For the heat insulation on the separation tube (Optional parts) used to connect 2 EEV 

units ,refer to the installation manual of the separation tube.

6. MOUNTING THERMISTORS

•  To prevent water from accumulating on top of the thermistor, orient the thermistor wires 

downwards when mounting the thermistor.

•  Make good contact between thermistor and air handling unit. Put the top of the thermis-

tors on the air handling unit, this is the most sensitive point of the thermistor.

Mounting thermistors to general indoor units

A

C

D

B

EEV 

kit

Refrigerant 

fl

 ow 

during cooling

Air inlet

Air outlet

Heat 

Exchanger

General indoor unit

A: Heat exchanger inlet pipe

Braze a thermistor holder pipe (Ø 6.35, accessory) in front of the distributor branch.
Use a thermistor spring (accessory) to tightly seal and secure the thermistor (

Φ

4, acces-

sory) pipes.

(1) (2)

(3)

(1)

(2)

(3)

(1)  Thermistor holder pipe 

(Ø 6.35 mm)

(2)  Thermistor (Ø 4 mm)
(3) Thermistor spring

Distributor

Heat 
Exchanger

* Attach this thermistor in a location where the evaporating temperature can be detected 

during cooling operation.

B: Heat exchanger outlet pipe

Braze a thermistor holder pipe (Ø 9.53, accessory) to the heat exchanger outlet pipe.
Use a thermistor spring (accessory) to tightly seal and secure the thermistor (Ø6, acces-
sory) pipes.

(1)

(1)

(2)

(3)

(2)

(3)

(1)  Thermistor holder pipe 

(Ø 9.53 mm)

(2)  Thermistor (Ø 6 mm)
(3) Thermistor spring

Heat Ex-
changer

9381279005_IM.indb   7

9381279005_IM.indb   7

6/30/2014   11:31:18 AM

6/30/2014   11:31:18 AM

Содержание UTP-VX30A

Страница 1: ...PART NO 9381279005 Original instructions INSTALLATION MANUAL DX kit For authorized service personnel only UTY VDGX UTP VX30A UTP VX60A UTP VX90A TM ...

Страница 2: ...his unit contains no user serviceable parts Always consult authorized service personnel to repairs When moving consult authorized service personnel for disconnection and installation of the unit 2 ABOUT THIS PRODUCT 2 1 Precautions for using R410A refrigerant WARNING Do not introduce any substance other than the prescribed refrigerant into the refrigeration cycle If air enters the refrigeration cy...

Страница 3: ...or Inlet air and Outlet air 2 For measuring the room temperature Thermistor Label GAS 1 For measuring the gas pipe temperature For gas pipes Thermistor Label LIQ 1 For measuring the liquid pipe temperature For liquid pipes Thermistor holder pipe Small 1 For mounting the thermistor Thermistor holder pipe Large 1 For mounting the thermistor Name and Shape Q ty Application Thermistor spring For small...

Страница 4: ... temperature Refer to the Design Technical manual Condensation temperature Refer to the Design Technical manual Capacity Class kW 14 0 20 0 25 0 40 0 50 0 EEV unit model No 60 90 90 90 90 90 90 Cooling capacity kW 14 22 4 25 40 50 4 Heating capacity kW 16 25 28 45 56 5 Heat exchanger capacity Refer to the Design Technical manual Airflow rate Reference m3 h 2 240 3 560 4 000 6 400 8 000 Capacity ra...

Страница 5: ...n below System Configuration Diagram Fujitsu general approved devices Outdoor unit Indoor unit Control unit Liquid pipe Gas pipe Control line Thermistor 4 Wired remote controller Piping Wiring EEV unit 3 2 3 Pipe Conditions EEV unit Heat Exchanger R Straight pipe 200 mm or more Liquid pipe Gas pipe 4 INSTALLATION WORK Correct initial installation location is important because it is difficult to mo...

Страница 6: ...nly Cannot be installed outdoors EEV unit inclination limits 10 or less 10 or less 4 3 1 Installing the Control unit If installing outdoors make sure to orient A upwards Using a template accessory is recommended when positioning the holes for mounting the control unit 5 or less Inclination limits Sealing washers 3 Accessories M8 Nuts 3 Accessories A A Contorl unit 200 mm or more Service space 200 ...

Страница 7: ...tion location of the refrigerant piping is expected to exceed 70 install heat insulation around the refrigerant piping If the expected humidity level is 70 to 80 use heat insulation that is 15 mm or thicker and if the expected humidity exceeds 80 use heat insulation that is 20 mm or thicker If heat insulation is used that is not as thick as specified condensation may form on the surface of the ins...

Страница 8: ...round cable Improper earthing grounding work can cause electric shocks Install the remote controller cables so as not to be direct touched with your hand Perform wiring work in accordance with standards so that the DX kit can be operated safely and positively Connect the connection cable firmly to the terminal board Imperfect installation may cause a fire If the supply cable is damaged it must be ...

Страница 9: ...ent breaker requirements Model MCA MFA UTY VDGX 0 096 A 20 A MCA Minimum Circuit Ampacity MFA Main Fuse Ampacity When the power crossover wiring is done make it so that the total of the MCA of the connected DX kits RB units and indoor units does not exceed the 15 A For indoor unit MCA and RB unit MCA refer to the indoor unit and RB unit installation manual If the capacity of connected DX kits RB u...

Страница 10: ...therwise the screw heads may be damaged and prevent the screws from being properly tightened 5 Do not tighten the terminal screws too much otherwise the screws may break 6 See the table for the terminal screw tightening torques 7 Please do not fix 2 power supply cables with 1 screw Sleeve Strip 10 mm Screw with special washer Screw with special washer Ring terminal Cable Terminal block Cable Ring ...

Страница 11: ...G20 Type245 IEC57 or equivalent T1 THERMISTOR GAS H5 Thermistor mounted to the gas pipe 0 33 AWG22 Sheathed PVC cable Relay the multi conductor cable and pass it through the designated hole T2 THERMISTOR LIQUID Thermistor mounted to the liquid pipe T3 THERMISTOR INLET AIR Thermistor mounted to the inlet T4 THERMISTOR OUTLET AIR Thermistor mounted to the outlet EV1 EEV1 1 Red 2 Brown 3 Black 4 Gree...

Страница 12: ...le gland recommended value A B For M10 0 5 N m 0 5 N m For M16 1 0 N m 1 5 N m For M20 1 0 N m 2 0 N m Outdoor cable connections 1 Thermistor cable connections Connect the thermistor cables to the relay multi conductor cables as shown in the diagram before passing through the hole Make sure to use only weatherproof relay cables Terminal block Thermistor Relay cable Cable connector 2 Electronic exp...

Страница 13: ...R SIGNAL INPUT CNA06 CNA07 COOL HEAT SIGNAL CNA03 CNA04 FLOAT SW SIGNAL Incompatible CNA05 External input terminal Dry contact terminal External input terminal Apply voltage terminal External output terminal CNA01 CNA04 CNA02 CNA07 CNB01 Controller PCB CNA03 CNA06 Use an external input and output cable with appropriate external dimension depending on the number of cables to be installed The wire c...

Страница 14: ...e Pulse input method Terminal block Input signal Command ON OFF SIGNAL INPUT Pin1 to Pin2 OFF ON Operation Pin1 to Pin3 OFF ON Stop The last command has priority The indoor units within the same remote controller group operates in the same mode 2 ERROR SIGNAL INPUT If an error signal is input perform protection operation Thermostat OFF mode Make sure to install so that the input signals during nor...

Страница 15: ...her than the DX kit Connected unit etc 1 2 3 4 5 6 Power supply Terminal Relay PC board Control unit DX kit Connected unit Connected device 1 Connected device 2 Connected device 3 Connected device 4 Connected device 5 Drain pump PC board Power supply for drain pump AC 220 to 240 V 1A max DC 30 V max 1A max When using a drain pump connect relay that is compatible with AC power supply field supply P...

Страница 16: ...t where the wireless remote controller can be used the addresses can also be set using the remote controller If setting the addresses using the wireless remote controller set the indoor unit address and refrigerant circuit address to 00 For information on setting using the wireless remote controller Table A Address Rotary Address Rotary Switch Setting Switch Setting Refrigerant circuit REF AD SW I...

Страница 17: ...FF ON ON Precautions if using the DX kit as the administrative indoor unit If the Administrative indoor unit setting is ON for another indoor unit connected to the same refrigerant system or RB unit make sure to turn OFF that setting For details see the wired remote controller installation manual When connecting the wired remote controller to the DX kit set this switch to OFF Set the Administrativ...

Страница 18: ...R CODES When an error occurs the LED on the PC board LED name LED1 flashes Error code can be viewed by connecting the optional wired remote controller group remote controller and IR receiver unit etc If you use a wired type remote controller Optional parts error codes will appear on the remote controller display If you use a wireless remote controller IR receiver unit of optional parts the lamp on...

Страница 19: ...he operation temperature using analog external inputs Connected unit Connected device Control unit DX kit Analog signal The operation temperature is set by changing the voltage of the input signals If using this function set the DIP switch SET3 2 to OFF Formula Operation temperature T C 2 5 Ain 7 5 Ain Input voltage 1 0 to 9 0V See the following diagram for the advanced input conditions a Using th...

Отзывы: