14.4.4
Replacing the TPM
Field Replaceable Unit
(FRU)
Hardware: 40 minutes
Tools:
Removing the system board:
– Phillips PH2 / (+) No. 2 screw driver
Replacing the TPM:
– Bit screw driver
– TPM bit insert
(*)
– Thin slotted screw driver (2 x 0.4 mm)
(*)
– Flat nose pliers
(*)
For Japan:
– Dedicated TPM screw driver (CWZ8291A)
– TPM module fixing tool (S26361-F3552-L909)
CAUTION
▶
Advise your contact persons that they must provide you with all
recovery keys which belong to the system to restore them in the
TPM later.
Preliminary steps
▶
"Locating the defective server" on page 47
▶
"Suspending BitLocker functionality" on page 107
.
▶
"Shutting down the server" on page 49
.
▶
"Disconnecting the power cord" on page 50
.
▶
"Getting access to the component" on page 51
▶
"Removing the system air duct" on page 67
.
▶
"Removing the PCI air duct" on page 88
System board and components
TX2550 M5
Upgrade and Maintenance Manual
485
Содержание PRIMERGY TX2550 M5
Страница 20: ...Content Upgrade and Maintenance Manual TX2550 M5 ...
Страница 106: ...Basic hardware procedures 106 Upgrade and Maintenance Manual TX2550 M5 ...
Страница 322: ...Fans 322 Upgrade and Maintenance Manual TX2550 M5 ...
Страница 392: ...Expansion cards and backup units 392 Upgrade and Maintenance Manual TX2550 M5 ...
Страница 408: ...Main memory 408 Upgrade and Maintenance Manual TX2550 M5 ...
Страница 428: ...Processor CPU 428 Upgrade and Maintenance Manual TX2550 M5 ...
Страница 522: ...System board and components 522 Upgrade and Maintenance Manual TX2550 M5 ...
Страница 590: ...FUJITSU Server PRIMERGY TX2550 M5 System Cabling Overview System Cabling Overview English Cable plan for May 2019 ...
Страница 631: ...List of all used screws for PRIMERGY Servers Assembled in Germany and Japan February 2019 ...