2.5
AC Cable Connection under a Free-Access Floor
(Only for Use inside Japan and General Use
outside Japan)
If AC cables are connected to the power distribution box (or main unit, PCI_Box)
under a free-access floor, it is recommended the underfloor height be 300 mm (11.8
in.) or more in consideration of the shape of the AC cable connector, cable bending
(1)).
However, if the underfloor height is less than 300 mm (11.8 in.), place outlets
(2)).
Prepare an outlet near the unit.
Remark 1: This drawing shows the Fujitsu 19-inch global rack with the main unit as
an example.
Remark 2: Values in ( ) are in inches.
Figure 2.17 AC cable connection under a free-access floor
(only for use inside Japan and general use outside Japan)
(1) When the underfloor height is 300 mm
(11.8 in.) or more
(2) When the underfloor height is less
than 300 mm (11.8 in.)
Unit: mm (in.)
Free-access
floor
Outlet
More than
300 (11.8)
Less than 300 (11.8)
Outlet
Free-access
floor
250 (9.8)