1.5
Cooling Air and Exhaust Flows
This section explains the cooling air and exhaust flows of each cabinet.
z
Cooling air and exhaust flows of the PRIMEQUEST 520A/520/420 main unit
(
z
Cooling air and exhaust flows of the PCI_Box
)
When planning the installation of the equipment, it is important to consider the
flows of cooling air and exhaust. If the equipment is installed without giving
proper consideration to these flows, a cabinet or rack may draw in the exhaust
from another cabinet or rack and be adversely affected as a result. Particularly,
a device that monitors the temperature of intake air may continue to output the
alarm indicating abnormal intake temperature.
Figure 1.5 Cooling air and exhaust flows of the PRIMEQUEST 520A*/520/
420 main unit
*: not supported by Fujitsu Technology Solutions