4.1 Mounting Requirements
(6) Environmental
temperature
Temperature condition at installed in a cabinet is indicated with ambient temperature measured
30 mm from the HDD. At designing the system cabinet, consider following points.
•
Make a suitable air flow so that the DE surface temperature never exceed 60°C.
•
Cool the PCBA side especially with air circulation inside the cabinet. Confirm the cooling effect
by measuring the surface temperature of specific ICs and the DE. These measurement results
must satisfy the temperature condition listed in Table 4.1.
•
Keep the DE surface temperature at 50°C or below to meet the condition for assuring an MTBF
of 1,400,000 hours. An air flow of 0.5m/s or more is required at ambient temperature 30°C.
Table 4.1
Surface temperature check point and maximum temperature
No.
Measurement point
Maximum temperature
1 DE
Surface
60°C
2
Read channel LSI
82°C
3 VCM/SPM
Driver
93°C
4 HDC
97°C
5 MPU
94°C
2
4
5
3
1
Figure 4.5 Surface temperature measurement points
(7)
Environmental magnetic field
Do not install the HDDs in the vicinity of equipment giving off strong magnetic fields, such as
monitors, televisions, or loudspeakers.
(8)
Leakage magnetic flux
Do not mount the HDDs near the devices that the leakage magnetic flux influence easily.
C141-E266
45
Содержание MBC2036RC SERIES
Страница 1: ...C141 E266 01EN MBC2073RC MBC2036RC HARD DISK DRIVES PRODUCT MANUAL ...
Страница 10: ...This page is intentionally left blank ...
Страница 16: ...This page is intentionally left blank ...
Страница 24: ...This page is intentionally left blank ...
Страница 56: ...This page is intentionally left blank ...
Страница 82: ...Diagnostics and Maintenance 78 C141 E266 Figure 6 4 Fraction packaging ...
Страница 88: ...This page is intentionally left blank ...
Страница 94: ...This page is intentionally left blank ...
Страница 96: ...This page is intentionally left blank ...
Страница 97: ......
Страница 98: ......