8-3. Current release control
The rotation number of compressor is controlled so that the outdoor unit input current does not ex-
ceeds current limit value set according to the outdoor temperature.
The rotation number of compressor returns according to the operation mode, when the current be-
comes lower than the release value.
¢
Models: AOHG07KPCA, AOHG09KPCA, and AOHG12KPCA
Operation mode
Outdoor temp. (Ta)
Trigger condition
Release condition
Cooling
50°C ≤ Ta
4.0 A
3.5 A
46°C ≤ Ta < 50°C
4.0 A
3.5 A
40°C ≤ Ta < 46°C
5.0 A
4.5 A
12°C ≤ Ta < 40°C
6.0 A
5.5 A
2°C ≤ Ta < 12°C
6.0 A
5.5 A
Ta < 2°C
6.0 A
5.5 A
Heating
17°C ≤ Ta
5.5 A
5.0 A
12°C ≤ Ta < 17°C
7.0 A
6.5 A
5°C ≤ Ta < 12°C
7.5 A
7.0 A
Ta < 5°C
8.5 A
8.0 A
8-4. Cooling pressure over-rise protection
When the outdoor unit heat exchanger temperature reaches trigger condition below, the compressor
is stopped and trouble display is performed.
Trigger condition
65°C
8-5. Compressor temperature protection
When the compressor temperature sensor detects higher than the trigger condition below, the com-
pressor is stopped. When the compressor temperature sensor detects the release condition, the pro-
tection is released.
Trigger condition
108°C
Release condition
80°C
(3 minutes after compressor stop)
8-6. High pressure protection
Trigger condition
Pressure switch: Off (Open: Higher than 4.2 MPa)
Compressor stop
Release condition
Pressure switch: On (Close: Lower than 3.2 MPa)
(3 minutes after compressor stop)
Compressor restart
8-3. Current release control
- (04-28) -
8. Various protections
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Содержание General ASHG07KPCE
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2021 12 16 SR_CH01_AS059EG_01 ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2022 07 07 SR_CH02_AS059EG_02 ...
Страница 31: ...3 TROUBLESHOOTING 2022 07 07 SR_CH03_AS059EG_02 ...
Страница 34: ......
Страница 92: ...6 2 Outdoor unit 03 58 6 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Страница 93: ...4 CONTROL AND FUNCTIONS 2022 07 07 SR_CH04_AS059EG_02 ...
Страница 125: ...5 FILED WORKING 2022 07 07 SR_CH05_AS059EG_02 ...