2-17. E: 62. Outdoor unit main PCB error (Outdoor unit)
Indicator
Indoor unit
Operation indicator
6 time flash
Timer indicator
2 time flash
Economy indicator
Continuous flash
Error code
E: 62
Detective actuator Outdoor unit
Main PCB
Access to EEPROM failed due to some cause after
outdoor unit started.
Forecast of cause
External cause (Noise, temporary open, voltage drop)
Main PCB failure
Check point 1. Reset power supply and operate
Does error indication show again?
Check point 2. Replace main PCB
Change main PCB.
End
Check point 1-2. Check external cause
•
Check if temporary voltage drop was not
generated.
•
Check if momentary open was not generat-
ed.
•
Check if ground is connection correctly or
there are no related cables near the power
line.
End
2-17. E: 62. Outdoor unit main PCB error (Outdoor unit)
- (03-22) -
2. Troubleshooting with error code
TR
O
U
B
LESH
O
O
TI
N
G
TR
O
U
B
LESH
O
O
TI
N
G
Содержание GENERAL AOHG18KMTA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2022 03 11 SR_CH01_AS070EG_01 ...
Страница 15: ...2 TECHNICAL DATA AND PARTS LIST 2022 03 11 SR_CH02_AS070EG_02 ...
Страница 40: ...7 3 Model AOHG24KMTA 02 24 7 PC board diagrams TECHNICAL DATA AND PARTS LIST TECHNICAL DATA AND PARTS LIST ...
Страница 41: ...3 TROUBLESHOOTING 2022 03 25 SR_CH03_AS070EG_01 ...
Страница 44: ......
Страница 103: ...4 CONTROL AND FUNCTIONS 2022 03 25 SR_CH04_AS070EG_01 ...
Страница 105: ...8 8 High temperature and high pressure release control heating mode 04 29 CONTENTS continued ...
Страница 106: ......
Страница 137: ...5 FILED WORKING 2022 03 25 SR_CH05_AS070EG_01 ...