1-3. Error code table (Indoor unit and wired remote controller)
The operation, timer, and economy indicators operate according to the error contents.
For confirmation of the error contents, refer the flashing pattern as follows.
Error contents
Indoor unit display
Wired
remote
controller
display
Operation [ ]
(Green)
Timer [ ]
(Orange)
Economy [ ]
(Green)
E: 11. Serial communication error (Serial
reverse transfer error) (Outdoor unit)
1 times
1 times
Continuous
11
E: 11. Serial communication error (Serial
forward transfer error) (Indoor unit)
1 times
1 times
Continuous
11
E: 12. →ired remote controller
communication error (Indoor unit)
1 times
2 times
Continuous
12
E: 18. External communication error (Indoor
1 times
8 times
Continuous
18
E: 22. Indoor unit capacity error (Indoor
2 times
2 times
Continuous
22
E: 23. Combination error (Outdoor unit)
2 times
3 times
Continuous
23
E: 26. Address setting error in wired remote
2 times
6 times
Continuous
26
E: 29. Connected unit number error (Indoor
2 times
9 times
Continuous
29
E: 32. Indoor unit main PCB error (Indoor
3 times
2 times
Continuous
32
E: 33. Indoor unit motor electricity
consumption detection error (Indoor unit)
3 times
3 times
Continuous
33
E: 35. MANUAL AUTO button error (Indoor
3 times
5 times
Continuous
35
E: 39. Indoor unit power supply error for fan
3 times
9 times
Continuous
39
E: 3A. Indoor unit communication circuit
(wired remote controller) error
3 times
10 times
Continuous
3A
E: 41. Room temperature sensor error
4 times
1 times
Continuous
41
E: 42. Indoor unit heat exchanger sensor
4 times
2 times
Continuous
42
E: 51. Indoor unit fan motor error (Indoor
5 times
1 times
Continuous
51
E: 62. Outdoor unit main PCB error
6 times
2 times
Continuous
62
E: 63. Inverter error (Outdoor unit)
6 times
3 times
Continuous
63
E: 64. PFC circuit error (Outdoor unit)
6 times
4 times
Continuous
64
E: 65. Trip terminal L error (Outdoor unit)
6 times
5 times
Continuous
65
E: 71. Discharge thermistor error (Outdoor
7 times
1 times
Continuous
71
E: 72. Compressor thermistor error
7 times
2 times
Continuous
72
E: 73. Outdoor unit heat exchanger liquid
outlet thermistor error (Outdoor unit)
7 times
3 times
Continuous
73
E: 74. Outdoor temperature thermistor error
7 times
4 times
Continuous
74
E: 84. Current sensor error (Outdoor unit)
8 times
4 times
Continuous
84
E: 86. High pressure switch error (Outdoor
8 times
6 times
Continuous
86
E: 94. Trip detection (Outdoor unit)
9 times
4 times
Continuous
94
E: 95. Compressor motor control error
9 times
5 times
Continuous
95
1-3. Error code table (Indoor unit and wired remote controller)
- (03-2) -
1. Error code
TR
O
U
B
LESH
O
O
TI
N
G
TR
O
U
B
LESH
O
O
TI
N
G
Содержание GENERAL AOHG18KMTA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2022 03 11 SR_CH01_AS070EG_01 ...
Страница 15: ...2 TECHNICAL DATA AND PARTS LIST 2022 03 11 SR_CH02_AS070EG_02 ...
Страница 40: ...7 3 Model AOHG24KMTA 02 24 7 PC board diagrams TECHNICAL DATA AND PARTS LIST TECHNICAL DATA AND PARTS LIST ...
Страница 41: ...3 TROUBLESHOOTING 2022 03 25 SR_CH03_AS070EG_01 ...
Страница 44: ......
Страница 103: ...4 CONTROL AND FUNCTIONS 2022 03 25 SR_CH04_AS070EG_01 ...
Страница 105: ...8 8 High temperature and high pressure release control heating mode 04 29 CONTENTS continued ...
Страница 106: ......
Страница 137: ...5 FILED WORKING 2022 03 25 SR_CH05_AS070EG_01 ...