70
(/(&7521,&(;3$16,219$/9(6FRQW
6<03720
3266,%/(&$86(
5(0('<
Moisture causing valve to stick open.
Recover refrigerant, replace filter-drier, evacuate
system, and recharge.
Dirt or foreign material causing valve to stick
open
Recover refrigerant, replace filter-drier, remove EXV
and purge with nitrogen, evacuate system, and recharge.
Valve feeds too much
refrigerant, with low
superheat, with low
superheat and
higher than normal
suction pressure.
If EXV is completely clogged use the VSODC to open the EXV,
and purge with nitrogen, replace filter drier, and recharge.
Oversized EXV
Install correct EXV.
Incorrect suction thermistor location
Install suction thermistor with the provided stainless
steel strap and an additional zip tie between the 10:00 and
2:00 position on suction line, with insulation.
Change the superheat offset dip switches to increase
superheat.
Verify suction thermistor resistance is correct and
properly attached and insulated to the vapor line.
Incorrectly sensing vapor line temperature
Replace suction thermistor assembly.
Suction thermistor incorrectly calibrated.
If harness has a short, replace harness.
If gauge pressure measurement and the converted
voltage readings at the control are the same, replace
the control.
Inoperable stator heat
After verifying lack of connectivity, replace the pressure
transducer or harness.
Vapor pressure measured incorrectly.
If gauge pressure measurement and the converted
voltage readings at the control are different replace
pressure transducer.
Install trap riser to the top of the evaporator coil.
Low superheat adjustment
Refrigerant drainage from flooded evaporator
Compressor flood
back upon
start-up
9.12 Service Analyzer Charts (cont.)
Diagnostics
9.0 DIAGNOSTICS & TROUBLESHOOTING