7. Additional charge calculation
7-1. Model: AOYG18KATA
Refrigerant type
R32
Refrigerant amount
g
900
¢
Refrigerant charge
Total pipe length
m
15 or less
20 (Max.)
20 g/m
Additional charge
g
0
100
7-2. Model: AOYG22KATA
Refrigerant type
R32
Refrigerant amount
g
1,100
¢
Refrigerant charge
Total pipe length
m
15 or less
20
25 (Max.)
20 g/m
Additional charge
g
0
100
200
- 58 -
7-1. Model: AOYG18KATA
7. Additional charge calculation
OUTDOOR UNIT
AOYG18, 22KATA
OUTDOOR UNIT