ERROR CONTENTS
(indoor unit)
SU MO TU WE TH FR SA
CAUTION
Supply power to the crankcase heater for at least 12 hours
before the start of operation in winter.
(1) Stop the air conditioner operation.
(2) Press the master control button and the fan control button simultane-
ously for 2 seconds or more to start the test run.
Fig. 48
Unit number (usually 0)
Error code
(3) Press the start/stop button to stop the test run.
[SELF-DIAGNOSIS]
When the error indication "E:EE" is displayed, follow the following items to
perform the self-diagnosis. "E:EE" indicates an error has occurred.
1. REMOTE CONTROLLER DISPLAY
(1) Stop the air conditioner operation.
(2) Press the set temperature buttons
simultaneously for 5 sec-
onds or more to start the self-diagnosis.
Refer to the following tables for the description of each error code.
Fig. 49
Test run display
(3) Press the set temperature buttons
simultaneously for 5 sec-
onds or more to stop the self-diagnosis.
Table 7
Ex. Self-diagnosis
2. CHECKING DRAINAGE
To check the drain, remove the water cover and fill with 2 to 3 of water as
shown in Fig. 50.
The drain pump operates when operating in the cooling mode.
Fig. 50
Water cover
Drain pipe
Watering pot
Error code
Error contents
Indoor unit doesn't accept the signal from
outdoor unit.
Room temperature sensor open
Room temperature sensor short-circuited
Indoor heat exchanger temperature sensor open
Indoor heat exchanger temperature sensor short-
circuited
Outdoor heat exchanger temperature sensor
Power source connection error
Float switch operated
Outdoor temperature sensor
Discharge pipe temperature sensor
Model abnormal
Indoor fan abnormal
01
02
03
04
05
06
08
09
0A
0c
11
12
Error code
Error contents
Outdoor unit doesn't accept the signal from
indoor unit.
Excessive outdoor pressure (permanent stop)
Compressor temperature sensor
Pressure switch error
IPM error
CT error
Active filter module (AFM) error
Compressor does not operate
Outdoor unit fan error
Communication error
(inverter multicontroller)
2 way valve sensor error
Expansion valve error
Connection indoor unit error
13
14
15
16
17
18
19
1A
1b
1c
1d
1E
1F
2005.11.18
16
1c, 1d, 1E, 1F errors are only for multi type.
Содержание AUY30LUAS
Страница 6: ... Unit mm OUTDOOR UNIT Model AOY45LJBYL 2005 06 06 5 31 77 900 330 12 9 21 1290 400 650 370 Air Flow ...
Страница 8: ...2005 06 23 7 CIRCUIT DIAGRAM Models AUY30LUAS AUY36LUAS AUY45LUAS Models AOY30LMAWL AOY36LMAWL ...
Страница 9: ...Model AOY45LJBYL 2005 06 22 8 ...
Страница 19: ...481 481 481 481 1 Models AUY30LUAS AUY36LUAS AUY45LUAS DISASSEMBLY ILLUSTRATION 2005 06 24 18 ...
Страница 21: ...146 1 184 1 146 2 47 1 138 187 235 564 735 896 Models AUY30LUAS AUY36LUAS 2005 06 27 20 ...
Страница 23: ...138 187 735 184 1 235 Model AUY45LUAS 2005 06 27 22 ...
Страница 24: ...Models AUY30LUAS AUY36LUAS AUY45LUAS 2005 06 27 23 ...
Страница 25: ...Models AOY30LMAWL AOY36LMAWL 2005 06 07 24 1 6 7 3 4 5 2 ...
Страница 26: ...17 18 10 13 11 9 15 14 8 Models AOY30LMAWL AOY36LMAWL 2005 06 07 25 ...
Страница 27: ...2005 06 07 26 22 23 31 18 20 29 12 28 12 19 24 26 27 25 30 Models AOY30LMAWL AOY36LMAWL ...
Страница 28: ...2005 06 07 27 37 38 33 34 Models AOY30LMAWL AOY36LMAWL 36 35 ...
Страница 29: ...1 6 7 5 2 3 4 3 Model AOY45LJBYL 2005 06 07 28 ...
Страница 30: ...13 12 11 10 9 15 14 Model AOY45LJBYL 2005 06 22 29 ...
Страница 31: ...22 20 21 23 24 19 17 18 26 25 Model AOY45LJBYL 2005 06 07 30 ...
Страница 32: ...31 38 27 34 35 36 28 39 40 41 30 32 29 33 37 Model AOY45LJBYL 2005 06 07 31 ...
Страница 38: ...0504G2853 ...