2-26. E: 84. Current sensor error (Outdoor unit)
Indicator
Wired remote
controller
Error code
E: 84
Detective actuator
Outdoor unit
main PCB
When input current sensor has detected 0 A, while
inverter compressor is operating at higher than 56 rps,
after 1 minute upon starting the compressor. (Except
during the defrost operation)
Forecast of cause
Defective connection of electric components
External cause
Main PCB failure
Check point 1. Reset power supply and operate
Does error indication show again?
↓
Check point 2. Check connections of outdoor
unit electrical components
Upon correcting the removed connector or mis-
wiring, reset the power.
•
Check if the terminal connection is loose.
•
Check if connector is removed.
•
Check erroneous connection.
•
Check if cable is open.
↓
Check point 3. Replace main PCB
If Check point 1, 2 do not improve the symptom,
change main PCB.
↓
End
Check point 1-2. Check external cause at Indoor and Outdoor (Voltage drop or Noise)
•
Instant drop: Check if there is a large load electric apparatus in the same circuit.
•
Momentary power failure: Check if there is a defective contact or leak current in the power sup-
ply circuit.
•
Noise: Check if there is any equipment causing harmonic wave near electric line. (Neon bulb or
electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
↓
End
2-26. E: 84. Current sensor error (Outdoor unit)
- (03-31) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Содержание AUXG36KRLB
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 11 16 SR_CH01_AU015EF_02 ...
Страница 16: ...2 2 Outdoor unit 01 10 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 17: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AU015EF_02 ...
Страница 47: ...3 TROUBLESHOOTING 2020 06 04 SR_CH03_AU015EF_01 ...
Страница 50: ......
Страница 116: ...5 2 Outdoor unit 03 66 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Страница 117: ...4 CONTROL AND FUNCTIONS 2020 06 04 SR_CH04_AU015EF_01 ...
Страница 120: ......
Страница 157: ...5 FILED WORKING 2020 06 04 SR_CH05_AU015EF_01 ...