8. Various protections
8-1. Discharge gas temperature over-rise prevention control
The discharge gas temperature sensor (discharge thermistor: outdoor unit side) detects the dis-
charge gas temperature.
• When the discharge temperature becomes higher than the trigger condition, the compressor fre-
quency is decreased as the table below, and it continues to decrease until the discharge tempera-
ture becomes lower than the trigger condition.
• When the discharge temperature becomes lower than the release condition, control of compressor
frequency is released.
• When the discharge temperature becomes higher than the compressor protection temperature,
the compressor is stopped and the indoor unit LED starts blinking.
Trigger condition
104°C
Compressor frequency
-14 rps/120 seconds
Release condition
101°C
Compressor protection temperature
110°C
8-2. Anti-freezing control (cooling and dry mode)
The compressor frequency is decrease in cooling and dry mode when the indoor unit heat exchang-
er temperature sensor detects the temperature lower than the trigger condition.
When the indoor unit heat exchanger temperature reaches release condition, the anti-freezing con-
trol is stopped.
Trigger condition
4°C
Release condition
Outdoor temp. ≥ 10°C*
1
Outdoor temp. ≥ 12°C*
2
7°C
Outdoor temp. < 10°C*
1
Outdoor temp. < 12°C*
2
13°C
*1: During the outdoor temperature dropping
*2: During the outdoor temperature rising
8-1. Discharge gas temperature over-rise prevention control
- (04-33) -
8. Various protections
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Содержание AUXG36KRLB
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 11 16 SR_CH01_AU015EF_02 ...
Страница 16: ...2 2 Outdoor unit 01 10 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 17: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AU015EF_02 ...
Страница 47: ...3 TROUBLESHOOTING 2020 06 04 SR_CH03_AU015EF_01 ...
Страница 50: ......
Страница 116: ...5 2 Outdoor unit 03 66 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Страница 117: ...4 CONTROL AND FUNCTIONS 2020 06 04 SR_CH04_AU015EF_01 ...
Страница 120: ......
Страница 157: ...5 FILED WORKING 2020 06 04 SR_CH05_AU015EF_01 ...