background image

• Insert drain hose and drain cap securely. Drain should slope down to avoid water leakage. 

• When inserting the drain hose, no other material than water should be applied. Application

  of other material than water will cause deterioration of the hose, and may cause water leakage.

• After you remove a drain hose, be sure to attach the drain cap.

• When you secure the piping and drain hose with tape, arrange the drain hose so that it 

  comes under bottom of piping.

• For drain hose piping in low temperature environment, you need to apply frozen protection

  to prevent a frozen drain hose. After cooling operation is performed in low temperature

  environment, (when outdoor temperature under 0 °C,) water in the drain hose could be 

  frozen. Frozen drain water will block the water flow in the hose, and may cause water 

  leakage at the indoor unit.

 

[Installing the indoor unit]

• Hang the indoor unit from the

  hooks at the top of the wall hook

  bracket. 

• Insert the spacer, etc. between the indoor unit and the

  wall hook bracket and separate the bottom of the indoor

  unit from the wall.

Top hooks

Bottom hooks

 Flare connection (Pipe connection)

Die

A

Pipe L

Check if [L] is

flared uniformly

and is not cracked

or scratched.

Flaring

(1) Cut the connection pipe to the necessary length with a pipe cutter.

(2) Hold the pipe downward so that cuttings will not enter the pipe and remove the burrs.

(3) Insert the flare nut onto the pipe and flare the pipe with a flaring tool.

Insert the flare nut (always use the flare nut attached 

to the indoor and outdoor units respectively) onto the 

pipe and perform the flare processing with a flare tool.

Use the special R410A flare tool, or the conventional 

(for R22) flare tool.

When using the conventional flare tool, always use

an allowance adjustment gauge and secure the A 

dimension shown in table below .

 

Flare nut size and tightening torque

Flare nut [mm (in.)]    Tightening torque [N•m (kgf•cm)]

6.35 (1/4) dia.                  16 to 18 (160 to 180)
9.52 (3/8) dia.                  32 to 42 (320 to 420)

Connection

(1) Install the outdoor unit wall cap (supplied with the 

     optional installation set or procured at the site) to

     the wall pipe.

(2) Connect the outdoor unit and indoor unit piping.

(3) After matching the center of the flare surface and

     tightening the nut hand tight, tighten the nut to the

     specified tightening torque below with a torque

     wrench. 

Pipe outside diameter

A

 

(mm)

Pipe outside

diameter

ø 6.35 mm (1/4”)
ø 9.52 mm (3/8”)

Flare tool for R410A

Clutch type

0 to 0.5
0 to 0.5

Conventional (R22) flare tool

Clutch type

1.0 to 1.5
1.0 to 1.5

Wing nut type

1.5 to 2.0
1.5 to 2.0

Tighten with two wrenches.

Torque

wrench

Wrench (fixed)

Flare nut

Indoor unit pipe Connection pipe

            To prevent gas 

            leakage, coat 

the flare surface with 

refrigerator oil.

• Fasten a flare nut with a torque wrench as instructed in this manual. If fastened too tight,

  the flare nut may be broken after a long period of time and cause a leakage of refrigerant.

Indoor unit

Wall hook bracket

(Spacer)

• After hooking the indoor unit to the top hook, hook the fittings of

  the indoor unit to the two bottom hooks while lowering the unit 

  and pushing it against the wall.  

Indoor unit wiring

Screw

• Match the terminal block numbers and connection cable colors with those of the outdoor

  unit. Incorrect wiring may cause a fire.

• When fixing the connection cable with the cable clamp, always fasten the cable at the

  plastic jacket portion, but not at the insulator portion. If the insulator is chafed, electric

  leakage may occur.

• Always connect the earth (ground) wire. Improper earthing (grounding) work can cause

  electric shocks.

• Connect the connection cables firmly to the terminal block. Imperfect installation may

  cause a fire.

• Do not use the ground screw for the indoor unit to the outdoor unit unless it is specified.

Cable 

clamp

(1) Remove the wire cover.

(2) Remove the cable clamp.

(3) Bend the end of the 

     connection cable as shown

     in the figure.

(4) Connect the end of the connection

      cable fully into the terminal block.

(5) Fasten the connection cable with a

      cable clamp.

(6) Fasten the wire cover.

7.   OUTDOOR UNIT INSTALLATION 

 

• Install the unit where it will not be tilted by more than 5°.

• When installing the outdoor unit where it may exposed to strong wind, fasten it securely. 

Air purge

Always use a vacuum pump to purge the air.

Refrigerant for purging the air is not charged in the outdoor unit at the factory.

Close the high pressure side valve of the gauge manifold fully and do not operate it during the 

following work. 

• Refrigerant must not be discharged into atmosphere.

• After connecting the piping , check the joints for gas leakage with gas leak detector.

Hooks

Screw

Switch cover

(1) Check if the piping connections are secure.
(2) Check that the stems of 2-way valve and 3-way valve are closed fully.
(3) Connect the gauge manifold charge hose to the charging port of the 3-way valve
     (side with the projection for pushing in the valve core).
(4) Open the low pressure side valve of the gauge manifold fully.
(5) Operate the vacuum pump and start pump down.
(6) Slowly loosen the flare nut of the 3-way valve and check if air enters, then retighten the flare nut.
     (When the flare nut is loosened the operating sound of the vacuum pump changes and the
      reading of the compound pressure gauge goes from minus to zero.)
(7) Pump down the system for at least 15 minutes, then check if the compound pressure gauge
     reads -0.1 MPa (-76 cmHg, -1 bar).
(8) At the end of pump down, close the low pressure side gauge of the gauge manifold fully and
     stop the vacuum pump.
(9) Slowly loosen the valve stem of the 3-way valve. When the compound pressure gauge     
     reading reaches 0.1-0.2 MPa, retighten the valve stem and disconnect the charge hose from
     the 3-way valve charging port.
     (If the stem of the 3-way valve is opened fully before the charge hose is disconnected, it may
      be difficult to disconnect the charge hose.)
(10) Fully open the valve stems of the 2-way valve and 3-way valve using a hexagon wrench. 
     (After the valve stem begins to turn, turn it with a torque of less than 2.9 N • m until it stops turning.)
(11) Firmly tighten the 2-way valve and 3-way valve blank cap and the charging port cap.

3-way valve

2-way valve

Charging

port cap

Vacuum pump

Charge hose 

Charge hose

Charging port

Blank cap

Valve stem

Flare nut

Compound pressure gauge

Gauge manifold

Pressure gauge

High pressure

side valve  (closed)

Low pressure 

side valve

-0.1 MPa (-76 cmHg -1 bar)  

LO

HI

Tightening torque [

N • m(kgf • cm)]

Blank cap

20.0 to 25.0 (200 to 250 )

Charging port cap

12.5 to 16.0  (125 to 160 )

Switch cover A, B removal

(1) Remove the tapping screws. 

(2) Push downward the Switch cover B. 

(3) Push upward the Switch cover A.

Installing the switch cover A, B

(1) After inserting the three hooks of Switch cover A, then 

     push upward.

(2) After inserting the three hooks of Switch cover B, then 

     push upward, and then tighten the tap ping screw. 

 WARNING

 CAUTION

 CAUTION

 CAUTION

 WARNING

 CAUTION

Additional charge

Refrigerant suitable for a piping length of 15 m is charged in the outdoor unit at the factory.

When the piping is longer than 15 m, additional charging is necessary.

For the additional amount, see the table below.

Pipe length

15 m

20 m 

Rate

Additional refrigerant

None

+100 g 

20 g/m

 

• When adding refrigerant, add the refrigerant from the charging port at the completion of work.

• The maximum length of the piping is 20 m. If the units are further apart than this, correct

  operation can not be guaranteed.

Between 15 m and 20m, when using a connection pipe other than that in the table, charge 

additional refrigerant with 20g/1 m as the criteria.

Connection cable wiring

(1) Remove the outdoor unit switch cover A, B.

(2) Remove the outdoor unit cable clamp.

(3) Bend the end of the cable as shown in the figure.

(4) Connect the end of the connection cable fully into 

      the terminal block.

(5) Fasten the sheath with a cable clamp.

(6) Install switch cover A, B.

A

HOLE

HOLE

Run the connection cable to the rear of the outdoor unit 

within the A range of the arrows shown in the figure.

(The switch cover becomes difficult to install.)

(1) Insulate between pipes.

      • For rear, right, and bottom piping, overlap the

        connection pipe insulation and indoor unit pipe

        insulation and bind them with vinyl tape so that there

        is no gap.

      • For left and left rear piping, butt the connection pipe 

        insulation and indoor unit pipe insulation together and 

        bind them with and vinyl tape so that there is no gap.

      • For left and left rear piping, wrap the area which 

        accommodates the rear piping storage section with

        cloth tape.

      • For left and left rear piping, bind the connection cord

        to the top of the pipe with vinyl tape.

      • For left and left rear piping, bundle the piping and

        drain hose together by wrapping them with cloth tape

        over within the range of which they fit into the rear

        piping storage section.

(2) Temporarily fasten the connection cord along the

      connection pipe with vinyl tape. (Wrap to about 1/3 the

      width of the tape from the bottom of the pipe with tape

      so that water does not enter.)

(3) Fasten the connection pipe to the outside wall with

      saddles,etc.

(4) Fill the gap between the outside wall pipe hole and the

      pipe with sealant so that rain water and wind cannot

      blow in.

(5) Fasten the drain hose to the outside wall, etc.

8.   FINISHING 

*Field supplied

Pipe

Saddle*

Outside

 wall cap*

(Outdoors)

Wall

Bind the pipes 

together so that 

there is no gap. 

Overlap the insulation

Vinyl tape

Wrap with

cloth tape 

Cloth tape

Drain hose

Connection cable

Pipe Drain hose

Check the following:

Good

Drain hose

Saddle

Lifted up

Wave End in water

Drain hose

Connection pipe

Wall pipe

Connection cable

Left piping

Prohibited

Pipe

Connection

pipe

(heat insulation) 

Prohibited Prohibited

Sealer 

putty*

b

a

Press 4 places on the 

intake grille to close it 

completely.

Open the intake 

grille. While gently 

pressing the left 

and right mounting 

shafts of the intake 

grille outward “a”, 

remove the intake 

grille in direction 

of the arrow “b”.

11.   FRONT PANEL REMOVAL AND INSTALLATION

 

Intake grill removal

c

Intake grill installation

While holding the grille 

horizontal, set the left

and right mounting 

shafts into the pillow 

blocks at the top of the 

panel “c”. 

To latch each shaft 

properly, insert the 

shaft until it snaps.

Front panel removal

Screws (3 position)

Screws (Wire cover) Wire cover

(1) Remove intake grille

     (Reference the intake grille removal.)

(2) Remove wire cover.

(3) Remove 3 screws.

(4) The front panel is pulled to the front, 

      raising the upper surface, and a front 

      panel is removed.

Front panel installation

(1) Firstly, fit the lower part of the front panel, 

      and insert top and bottom hooks. 

      ( 3 top sides, 6 bottom sides)

Bottom holes

Bottom hooks

Top holes

Top hooks

Front panel

Indoor unit

9.    TEST RUN

 

 

Transmitter 

section

Test run button

10.    CUSTOMER GUIDANCE 

12.PUMP DOWN OPERATION 

(FORCED COOLING OPERATION)

  

During the pump-down operation, make sure that the compressor is turned off before 

you remove the refrigerant piping.

Do not remove the connection pipe while the compressor is in operation with 2-way or 

3-way valve open. This may cause abnormal pressure in the refrigeration cycle that 

leads to breakage and even injury.

• Perform test operation and check items 1 and 2 below.

• For the test operation method, refer to the operating manual.

• The outdoor unit, may not operate, depending on the room

   temperature. In this case, press the TEST RUN button on the remote

   controller while the air conditioner is running. (Point the transmitter 

   section of the remote controller toward the air conditioner and press

   the test run button with the tip of a ball-point pen, etc.)

• To end test operation, press the remote controller START/STOP button.

  (When the air conditioner is run by pressing the test run button, the OPERATION indicator

   lamp and TIMER indicator lamp will simultaneously flash slowly.)

1. Indoor unit

(1) Is operation of each button on the remote control unit normal?

(2) Does each lamp light normally?

(3) Do the airflow direction louver operate normally?

(4) Is the drain normal?

2. Outdoor unit

(1) Is there any abnormal noise and vibration during operation?

(2) Will noise, wind, or drain water from the unit disturb the neighbors?

(3) Is there any gas leakage?

Explain the following to the customer in accordance with the operating manual.

(1) Starting and stopping method, operation switching, temperature adjustment, timer, 

      airflow switching, and other remote controller operations.

(2) Air filter removal and cleaning, and how to use the air louvers.

(3) Give the operating and installation manuals to the customer.

To avoid discharging refrigerant into the atmosphere at the time of relocation or disposal,

recover refrigerant by doing the cooling operation or forced cooling operation according to the 

following procedure. (When the cooling operation cannot start in winter, and so on, start the 

forced cooling operation.)

(1) Do the air purging of the charge hose by connecting the charging hose of gauge manifold

      to the charging port of 3-way valve and opening the low-pressure valve slightly.

(2) Close the valve stem of 2-way valve completely.

(3) Start the cooling operation or following forced cooling operation.

      Keep on pressing the MANUAL AUTO button of the indoor unit for more than 10 seconds.

      The operation indicator lamp and timer indicator lamp will begin to flash simultaneously

      during test run.  (The forced cooling operation cannot start if the MANUAL AUTO button

      is not kept on pressing for more than 10 seconds.)

(4) Close the valve stem of 3-way valve when the reading on the compound pressure gage

      becomes 0.05~0 Mpa (0.5~0 kg/cm2).

(5) Stop the operation.

    • Press the START/STOP button of the remote controller to stop the operation.

    • Press the MANUAL AUTO button when stopping the operation from indoor unit side.

      (It is not necessary to press on keeping for more than 10 seconds.)

(2) Three screws is attached.

(3) The wire cover is attached.

(4) The intake grille is attached.

For connection from the left rear

 CAUTION

 CAUTION

• Match the terminal block numbers and connection cable colors with those of the outdoor unit.

  Incorrect wiring may cause a fire.

• When fixing the connection cable with the cable clamp, always fasten the cable at the plastic

   jacket portion, but not at the insulator portion. If the insulator is chafed, electric leakage may

  occur.

• Always connect the earth(ground) wire. Improper earthing (grounding) work can cause electric

  shocks.

• Connect the connection cables firmly to the terminal block. Imperfect installation may cause a fire.

• Do not use the ground screw for the indoor unit to the outdoor unit  unless it is specified.

Cable clamp

Screw

Outdoor unit wiring

Outdoor unit terminal block

Indoor unit terminal block

Connection cable

Earth 

(Ground)

 screw

Earth 

(Ground) 

screw

Power supply cable

N

L

3

2

1

Cable clamp

Earth

(Ground)

screw 

Hooks

Hooks

Hooks
Switch cover

Connection cable

Wire cover

HOW TO CONNECT THE WIRE TO THE TERMINALS

(1)  Use crimp-type terminals with insulating sleeves as shown in the figure below to connect  

      to the terminal block.

(2)  Securely crimp the crimp-type terminals to the wires using an appropriate tool so that the 

      wires do not come loose.

(3)  Use the specified wires, connect them securely, and fasten them so that there is no 

      stress placed on the terminals.

(4)  Use an appropriate screwdriver to tighten the terminal screws. Do not use a screwdriver 

      that is too small, otherwise, the screw heads may be damaged and prevent the screws 

      from being properly tightened.

(5)  Do not tighten the terminal screws too much, otherwise, the screws may break.

(6)  See the table below for the terminal screw tightening torques. 

Tightening torque

M3.5 screw 

M4 screw
M5 screw

0.8 to 1.0 N • m ( 8 to 10 kgf • cm )
1.2 to 1.8 N • m (12 to 18 kgf • cm)
2.0 to 3.0 N • m (20 to 30 kgf • cm)

Strip

10 mm

Crimp-type terminal

Sleeve

Wire

Screw with special washer

Crimp-type terminal

Terminal board

Terminal block

Wire

40 mm

30 mm

12 mm

5 mm

12

 mm

5 mm

Insert the wire cover tab into the square hole 

of the indoor unit and fasten with a screw.   

Отзывы: