16

TROUBLESHOOTING

Instructions relating to heating (*) are applicable only to “HEAT & COOL MODEL” (Reverse Cycle).

In the event of a malfunction (burning smell, etc.), immediately stop operation, disconnect the
Power Supply Plug or turn off the circuit breaker, and consult authorized service personnel.
Merely turning off the unit’s power switch will not completely disconnect the unit from the power
source. Always be sure to turn off your circuit breaker to ensure that power is completely off.

Before requesting service, perform the following checks:

WARNING!

Symptom

Doesn’t operate immedi-
ately:

Noise is heard:

Smells:

Mist or steam are
emitted:

Airflow is weak or stops:

Water is produced from
the outdoor unit:

Problem

If the unit is stopped and then immediately started again, the com-
pressor will not operate for about 3 minutes, in order to prevent
fuse blowouts.

Whenever the power supply plug is disconnected and then recon-
nected to a power outlet, the protection circuit will operate for about
3 minutes, preventing unit operation during that period.

During operation and immediately after stopping the unit, the
sound of water flowing in the air conditioner’s piping may be
heard. Also, noise may be particularly noticeable for about 2 to 3
minutes after starting operation (sound of coolant flowing).

During operation, a slight squeaking sound may be heard. This is
the result of minute expansion and contraction of the front cover
due to temperature changes.

*

During Heating operation, a sizzling sound may be heard occa-
sionally. This sound is produced by the Automatic Defrosting op-
eration.

Some smell may be emitted from the indoor unit. This smell is
the result of room smells (furniture, tobacco, etc.) which have
been taken into the air conditioner.

During Cooling or Dry operation, a thin mist may be seen emitted
from the indoor unit. This results from the sudden Cooling of
room air by the air emitted from the air conditioner, resulting in
condensation and misting.

*

During Heating operation, the outdoor unit’s fan may stop, and
steam may be seen rising from the unit. This is due to the Auto-
matic Defrosting operation.

*

When Heating operation is started, fan speed is temporarily very
low, to allow internal parts to warm up.

*

During Heating operation, if the room temperature rises above
the thermostat setting, the outdoor unit will stop, and the indoor
unit will operate at very low fan speed. If you wish to warm the
room further, set the thermostat to a higher setting.

*

During Heating operation, the unit will temporarily stop opera-
tion (between 7 and 15 minutes) as the Automatic Defrosting mode
operates. During the Automatic Defrosting operation, the OPERA-
TION indicator lamp will flash.

The fan may operate at very low speed during Dry operation or
when the unit is monitoring the room’s temperature.

During SUPER QUIET operation, the fan will operate at very low speed.

In the monitor AUTO operation, the fan will operate at very low speed.

*

In case of Multi-type unit, if multiple units are operated in different
operation modes as shown below, the units operated afterward will
stop and the OPERATION indicator lamp (red) will flash.
Heating mode and cooling mode (or dry mode)
Heating mode and fan mode

*

During Heating operation, water may be produced from the out-
door unit due to the Automatic Defrosting operation.

See page

17

17

17

7

7

7

18

17

NORMAL

FUNCTION

Содержание AST12 SERIES

Страница 1: ...KEEP THIS MANUAL FOR FUTURE REFERENCE FUJITSU GENERAL LIMITED P N9373538035 Indoor Unit AST7 SERIES AST9 SERIES AST12 SERIES AIR CONDITIONER WALL MOUNTED TYPE OPERATING MANUAL ...

Страница 2: ...t hands Do not pull power supply cord Turn off power source when not using the unit for extended periods Check the condition of the installation stand for damage Do not place animals or plants in the direct path of the air flow Do not drink the water drained from the air conditioner Do not use in applications involving the storage of foods plants or animals precision equipment or art works Connect...

Страница 3: ...the set time is reached the unit automatically turns off COOLING MODEL When the SLEEP timer button is pressed during Cooling mode the thermostat setting is gradually raised during the period of operation When the set time is reached the unit automatically turns off WIRELESS REMOTE CONTROL UNIT The WIRELESS REMOTE CONTROL UNIT allows convenient control of air conditioner operation SWING OPERATION T...

Страница 4: ... tion has been drawn to show all possible indicators in actual operation however the display will only show those indicators appropriate to the current op eration Fig 6 Instructions relating to heating are applicable only to HEAT COOL MODEL Reverse Cycle HEAT COOL MODEL REVERSE CYCLE COOLING MODEL A 0 C 3 1 4 5 6 8 7 OPERATION TIMER SWING B 9 2 ...

Страница 5: ...ss the START STOP button to stop the air condi tioner P Remote Control Unit Display Fig 7 Q Transmit Indicator R Clock Display S Operating Mode Display T Timer Mode Display U Fan Speed Display V Temperature Set Display W Timer Set Indicator X Temperature Set Indicator Fig 1 Indoor Unit 1 Operating Control Panel Fig 2 2 MANUAL AUTO button 3 Remote Control Signal Receiver 4 Indicator Lamps Fig 3 5 O...

Страница 6: ...7 meters When a signal is properly received by the air conditioner a beeping sound will be heard If no beep is heard press the remote control unit button again Remote Control Unit Holder PREPARATION CAUTION Take care to prevent infants from accidentally swallowing batteries When not using the remote control unit for an extended period remove the batteries to avoid possible leakage and damage to th...

Страница 7: ...g the FAN mode the temperature will not appear on the remote control unit s display Thermostat setting range COOLING MODEL AUTO Standard temperature setting 2 C Cooling Dry 18 to 30 C FAN 17 to 30 C During use of FAN mode if the thermostat is set at 17 C or lower the display will show and the fan will operate continuously regardless of the room tempera ture About three seconds later the entire dis...

Страница 8: ... The OPERATION indicator lamp red Fig 3 5 will go out About Mode Operation AUTO AUTO CHANGEOVER HEAT COOL MODEL REVERSE CYCLE When AUTO CHANGEOVER operation is selected the air conditioner selects the appropriate operation mode Cooling or Heating in response to your room s temperature When AUTO CHANGEOVER operation first selected the fan will operate at very low speed for about one minute during w...

Страница 9: ...ettings are selected automatically when operation begins When automatic operation is initiated the fan will run at very low speed for about one minute while the unit detects and selects the proper operating mode Once the operating mode has been set the mode will not change even if the room temperature changes If the START STOP button is pressed to recommence operation within two hours after stoppi...

Страница 10: ...mer and ON timer operations in a single sequence The sequence can involve one transition from OFF timer to ON timer or from ON timer to OFF timer within a twenty four hour period The first timer function to operate will be the one set nearest to the current time The order of operation is indicated by the arrow in the Remote Control Unit s display OFF ON or OFF ON One example of PROGRAM timer use m...

Страница 11: ...al operation To Stop the Air Conditioner During Timer Operation Press the START STOP button About the SLEEP timer To prevent excessive warming or cooling during sleep the SLEEP timer function automatically modifies the thermostat set ting in accordance with the time setting When the set time has elapsed the air conditioner completely stops During Heating operation When the SLEEP timer is set the t...

Страница 12: ... let louvers and drops of water may drip from the air conditioner During the Cooling and Dry modes if the Air Flow Direction Louvers are left in the heat ing range for more than 30 minutes they will automatically return to posi tion 3 When used in a room with infants chil dren elderly or sick persons the air direction and room temperature should be considered carefully when making settings Vertica...

Страница 13: ... modes if SWING Operation is con tinued at the lowest downward range for more than 30 minutes the unit will automatically switch the swing range to the horizontal flow range to prevent the condensation of moisture on the outlet The SWING operation may stop temporarily when the air conditioner s fan is not operating or when operating at very low speeds MANUAL AUTO OPERATION Use the MANUAL AUTO oper...

Страница 14: ... remove the air filter Lift up the air filter s handle disconnect the two lower tabs and pull out 2 Remove dust with a vacuum cleaner or by washing After washing allow to dry thoroughly in a shaded place 3 Replace the air filter and close the intake grille 1 Align the sides of the air filter with the panel and push in fully making sure the two lower tabs are returned properly to their holes in the...

Страница 15: ... the air cleaning filter frame Take care that the air cleaning filter does not project be yond the frame 3 Engage the four fixing locations at the top and bot tom of the air cleaning filter frame with the hooks of the air filter 2 1 1 2 1 2 When air cleaning filters are used the effect will increased by setting the fan speed to High Intake Grille Intake Grille Mounting shaft Bearing Knob Mounting ...

Страница 16: ...air cleaning filters avoid places with high temperatures and high humidity and use the filters as soon as possible after the package has been opened The air cleaning effect decreases when the filters are left in the opened package POLYPHENOL CATECHIN AIR CLEANING FILTER white filter The Air Cleaning Filters are disposable filters They can not be washed and reused For storage of the Air Cleaning Fi...

Страница 17: ...rosting op eration Some smell may be emitted from the indoor unit This smell is the result of room smells furniture tobacco etc which have been taken into the air conditioner During Cooling or Dry operation a thin mist may be seen emitted from the indoor unit This results from the sudden Cooling of room air by the air emitted from the air conditioner resulting in condensation and misting During He...

Страница 18: ...s air conditioner in conjunction with another kind of heating appliance Heat pump air conditioners heat your entire room by recirculating air throughout the room with the result that some time may be required after first starting the air con ditioner until the room is heated When Indoor and Outdoor Temperatures are High When both indoor and outdoor temperatures are high dur ing use of the heating ...

Страница 19: ...aneously but when two or more indoor units of the same group are oper ated simultaneously the heating and cooling efficiency will be less than when a single indoor unit is used alone Accordingly when you wish to use more than one in door unit for cooling at the same time the use should be concentrated at night and other times when less out put is required In the same way when multiple units are us...

Страница 20: ...dinary dwellings When the outdoor temperature drops the outdoor unit s fans may switch to Low Speed If the unit is used for long periods under high humidity conditions condensation may form on the surface of the indoor unit and drip onto the floor or other objects underneath About 80 or more OPERATING TIPS Humidity About 80 or less If the unit is used for long peri ods under high humidity condi ti...

Отзывы: