If you use a wireless remote control,
the lamp on the photo detector unit will output error
codes by way of blinking patterns.
If you use a wired remote control,
error codes will appear on the remote control display.
See the lamp blinking patterns and error codes in
the table.
An error display is displayed only during operation.
Error display
Wired
remote
control
Error code
Description
OPERATION
lamp
(green)
TIMER
lamp
(orange)
ECONOMY
lamp
(green)
●
(1)
●
(1)
◊
Serial communication error
●
(1)
●
(2)
◊
Wired remote control
Server room contol
communication error
communication error
●
(1)
●
(5)
◊
Check run unfinished
●
(1)
●
(6)
◊
Peripheral unit transmission PCB
connection error
●
(2)
●
(1)
◊
Unit number or Refrigerant circuit
address setting error
[Simultaneous Multi]
●
(2)
●
(2)
◊
Indoor unit capacity error
●
(2)
●
(3)
◊
Combination error
●
(2)
●
(4)
◊
•
•
•
Connection unit number error
(indoor slave unit)
[Simultaneous Multi]
•
Connection unit number error
(indoor unit or branch unit)
[Flexible Multi]
●
(2)
●
(6)
◊
Address setting error in wired
remote controller system
●
(2)
●
(7)
◊
Master unit, slave unit set-up error
[Simultaneous Multi]
●
(3)
●
(2)
◊
Indoor unit PCB model
information error
●
(3)
●
(5)
◊
Manual auto switch error
●
(4)
●
(1)
◊
Room temp. sensor error
●
(4)
●
(2)
◊
Indoor unit Heat Ex. Middle temp.
sensor error
●
(5)
●
(1)
◊
Indoor unit fan motor error
●
(5)
●
(3)
◊
Drain pump error
●
(5)
●
(7)
◊
Damper error
●
(5)
●
(8)
◊
Intake grille error
●
(5)
●
(15)
◊
Indoor unit error
●
(6)
●
(2)
◊
Outdoor unit main PCB model
information error or
communication error
●
(6)
●
(3)
◊
Inverter error
●
(6)
●
(4)
◊
Active filter error, PFC circuit error
●
(6)
●
(5)
◊
Trip terminal L error
●
(6)
●
(10)
◊
Display PCB microcomputers
communication error
●
(7)
●
(1)
◊
Discharge temp. sensor error
●
(7)
●
(2)
◊
Compressor temp. sensor error
●
(7)
●
(3)
◊
Outdoor unit Heat Ex. liquid temp.
sensor error
●
(7)
●
(4)
◊
Outdoor temp. sensor error
●
(7)
●
(5)
◊
Suction Gas temp. sensor error
●
(7)
●
(6)
◊
•
2-way valve temp. sensor error
•
3-way valve temp. sensor error
●
(7)
●
(7)
◊
Heat sink temp. sensor error
●
(8)
●
(2)
◊
•
Sub-cool Heat Ex. gas inlet
temp. sensor error
•
Sub-cool Heat Ex. gas outlet
temp. sensor error
●
(8)
●
(3)
◊
Liquid pipe temp. sensor error
●
(8)
●
(4)
◊
Current sensor error
●
(8)
●
(6)
◊
•
Discharge pressure sensor error
•
Suction pressure sensor error
•
High pressure switch error
●
(9)
●
(4)
◊
Trip detection
●
(9)
●
(5)
◊
Compressor rotor position
detection error
●
(9)
●
(7)
◊
Outdoor unit fan motor error
●
(9)
●
(9)
◊
4-way valve error
●
(10)
●
(1)
◊
Discharge temp. error
●
(10)
●
(3)
◊
Compressor temp. error
●
(10)
●
(4)
◊
High pressure error
●
(10)
●
(5)
◊
Low pressure error
●
(13)
●
(2)
◊
Branch boxes error
[Flexible Multi]
Display mode
●
: 0.5s ON / 0.5s OFF
◊
: 0.1s ON / 0.1s OFF
( ) : Number of flashing
Troubleshooting with the indoor unit display
OPERATION indicator (green)
TIMER indicator (orange)
ECONOMY indicator (green)
Troubleshooting with the wired
remote controller display (Option)
If an error occurs, the following display will be shown.
(“Er” will appear in the set room temperature display.)
Error code
2015.11.10
8
ERROR DETECTION
Содержание AOYG30LMTA
Страница 3: ...DIMENSIONS INDOOR UNIT 1 150 mm 280 mm 340 mm 2015 07 31 3 ...
Страница 4: ...2015 09 28 3 OUTDOOR UNIT 77 900 mm 830 mm 21 9 400 mm 330 mm 31 12 370 mm 650 mm ...
Страница 13: ......
Страница 23: ...1510G4459 ...
Страница 26: ...DIMENSIONS INDOOR UNIT 1 150 mm 280 mm 340 mm 2015 07 07 2 ...
Страница 27: ...2015 10 20 3 OUTDOOR UNIT 31 77 900 mm 330 mm 9 21 1 290 mm 400 mm 650 mm 370 mm Air Flow ...
Страница 44: ...1511G4462 ...