Fujitsu AOYG18LBCA Скачать руководство пользователя страница 2

En-1

1. SAFETY PRECAUTIONS

•  Be sure to read this manual carefully before installation.
•  The warnings and precautions indicated in this manual contain important information 

pertaining to your safety. Be sure to observe them.

•  Hand this manual, together with the operating manual, to the customer. Request the 

customer to keep them on hand for future use, such as for relocating or repairing the 
unit.

 WARNING

This mark indicates procedures which, if improperly performed, 
might lead to the death or serious injury of the user.

 CAUTION

This mark indicates procedures which, if improperly performed, might 
possibly result in personal harm to the user, or damage to property.

 WARNING

Installation of this product must be done by experienced service technicians or 
professional installers only in accordance with this manual. Installation by nonprofessional 
or improper installation of the product may cause serious accidents such as injury, water 
leakage, electric shock, or 

fi

 re. If the product is installed in disregard of the instructions in 

this manual, it will void the manufacturer’s warranty

To avoid getting an electric shock, never touch the electrical components soon after the 
power supply has been turned off. After turning off the power, always wait 10 minutes or 
more before you touch the electrical components.

Do not turn ON the power until all work has been completed. Turning ON the power 
before the work is completed can cause serious accidents such as electric shock or 

fi

 re.

If refrigerant leaks while work is being carried out, ventilate the area. If the refrigerant 
comes in contact with a 

fl

 ame, it produces a toxic gas.

Installation must be performed in accordance with regulations, codes, or standards for 
electrical wiring and equipment in each country, region, or the installation place.

Do not use this equipment with air or any other unspeci

fi

 ed refrigerant in the refrigerant lines.

Excess pressure can cause a rupture.

During installation, make sure that the refrigerant pipe is attached 

fi

 rmly before you 

run the compressor. Do not operate the compressor under the condition of refrigerant 
piping not attached properly with 2-way or 3-way valve open. This may cause abnormal 
pressure in the refrigeration cycle that leads to rupture and even injury.

When installing and relocating the air conditioner, do not mix gases other than the 
speci

fi

 ed refrigerant (R410A) to enter the refrigerant cycle.

If air or other gas enters the refrigerant cycle, the pressure inside the cycle will rise to 
an abnormally high value and cause rupture, injury, etc.

To connect the indoor unit and outdoor unit, use air conditioner piping and cables 
available locally as standard parts. This manual describes proper connections using 
such installation set.

If the supply cord is damaged, it must be replaced by the manufacturer, its service agent 
or similarly quali

fi

 ed persons in order to avoid a hazard.

Do not modify power cable, use extension cable or branch wiring. Improper use may 
cause electric shock or 

fi

 re by poor connection, insuf

fi

 cient insulation or over current.

Do not purge the air with refrigerants but use a vacuum pump to vacuum the installation.

There is not extra refrigerant in the outdoor unit for air purging.

Using the same vacuum pump for different refrigerants may damage the vacuum pump 
or the unit.

Use a clean gauge manifold, vacuum pump and charging hose for R410A exclusively.

During the pump-down operation, make sure that the compressor is turned off before 
you remove the refrigerant piping.
Do not remove the connection pipe while the compressor is in operation with 2 way or 3 
way valve open. This may cause abnormal pressure in the refrigeration cycle that leads 
to rupture and even injury.

This appliance is not intended for use by persons (including children) with reduced 
physical, sensory or mental capabilities, or lack of experience and knowledge, unless 
they have been given supervision or instruction concerning use of the appliance by a 
person responsible for their safety. Children should be supervised to ensure that they 
do not play with the appliance.

To avoid danger of suffocation, keep the plastic bag or thin 

fi

 lm used as the packaging 

material away from young children.

Contents

1. SAFETY 

PRECAUTIONS 

.......................................................................................... 1

2. ABOUT 

THIS 

PRODUCT........................................................................................... 1

3.  SELECTING THE MOUNTING POSITION ............................................................... 2

4. INSTALLATION 

DIAGRAM 

........................................................................................ 2

5. INSTALLATION 

 

......................................................................................................... 4

6. PUMP 

DOWN 

............................................................................................................ 5

 CAUTION

Read carefully all safety information written in this manual before you install or use the 
air conditioner.

This unit must be installed by quali

fi

 ed personnel with a capacity certi

fi

 cate for handling 

refrigerant 

fl

 uids. Refer to regulation and laws in use on installation place.

Install the product by following local codes and regulations in force at the place of 
installation, and the instructions provided by the manufacturer.
This product is part of a set constituting an air conditioner. The product must not be 
installed alone or be installed with non-authorized device by the manufacturer.
Always use a separate power supply line protected by a circuit breaker operating on all 
wires with a distance between contact of 3 mm for this product.
To protect the persons, earth (ground) the product correctly, and use the power cable 
combined with an Earth Leakage Circuit Breaker (ELCB).
This product is not explosion proof, and therefore should not be installed in explosive 
atmosphere.
Do not touch the 

fi

 ns of the heat exchanger. Touching the heat exchanger 

fi

 ns  could 

result in damage to the 

fi

 ns or personal injury such as skin rupture.

This product contains no user-serviceable parts. Always consult experienced service 
technicians for repairing.
When moving or relocating the air conditioner, consult experienced service technicians 
for disconnection and reinstallation of the product.

Do not place any other electrical products or household belongings under indoor unit or 
outdoor unit. Dripping condensation from the unit might get them wet, and may cause 
damage or malfunction of your property.

2.  ABOUT THIS PRODUCT

2.1. Precautions for using R410A refrigerant

 WARNING

The basic installation work procedures are the same as conventional refrigerant (R22) 
models.
However, pay careful attention to the following points:

Since the working pressure is 1.6 times higher than that of conventional refrigerant 
(R22) models, some of the piping and installation and service tools are special. (See 
the table below.)
Especially, when replacing a conventional refrigerant (R22) model with a new refrigerant 
R410A model, always replace the conventional piping and flare nuts with the R410A piping 
and 

fl

 are nuts.

Models that use refrigerant R410A have a different charging port thread diameter to pre-
vent erroneous charging with conventional refrigerant (R22) and for safety. Therefore, 
check beforehand. [The charging port thread diameter for R410A is 1/2-20 UNF.]

Be more careful that foreign matter (oil, water, etc.) does not enter the piping than with 
refrigerant (R22) models. Also, when storing the piping, securely seal the opening by 
pinching, taping, etc.

When charging the refrigerant, take into account the slight change in the composition of 
the gas and liquid phases. And always charge from the liquid phase where refrigerant 
composition is stable.

2.2. Special tools for R410A

Tool name

Contents of change

Gauge manifold

Pressure is high and cannot be measured with a conven-
tional (R22) gauge. To prevent erroneous mixing of other 
refrigerants, the diameter of each port has been changed.
It is recommended the gauge with seals -0.1 to 5.3 MPa 
(-1 to 53 bar) for high pressure.
-0.1 to 3.8 MPa (-1 to 38 bar) for low pressure.

Charge hose

To increase pressure resistance, the hose material and base 
size were changed.

Vacuum pump

A conventional vacuum pump can be used by installing a 
vacuum pump adapter.

Gas leakage detector

Special gas leakage detector for HFC refrigerant R410A.

Copper pipes

It is necessary to use seamless copper pipes and it is desirable that the amount of residual 
oil is less than 40 mg/10 m. Do not use copper pipes having a collapsed, deformed or 
discolored portion (especially on the interior surface). Otherwise, the expansion value or 
capillary tube may become blocked with contaminants.
As an air conditioner using R410A incurs pressure higher than when using R22, it is neces-
sary to choose adequate materials. 
Thicknesses of copper pipes used with R410A are as shown in Table1. Never use copper 

pipes thinner than 0.8 mm even when it is available on the market.

AIR CONDITIONER
OUTDOOR UNIT

INSTALLATION MANUAL

PART No. 9332809107-02

9332809107-02_IM.indb   1

9332809107-02_IM.indb   1

11/27/2015   3:03:51 PM

11/27/2015   3:03:51 PM

Содержание AOYG18LBCA

Страница 1: ...INSTALACIÓN Solo para personal autorizado MANUALE D INSTALLAZIONE Ad uso esclusivo del personale autorizzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ Για εξουσιοδοτημένο προσωπικό σέρβις MANUAL DE INSTALAÇÃO Apenas para técnicos autorizados РУКОВОДСТВО ПО УСТАНОВКЕ Для уполномоченного персонала KURULUM KILAVUZU Yetkili servis personeli içindir AIR CONDITIONER OUTDOOR UNIT INSTALLATION MANUAL Português EλληvIkά Ita...

Страница 2: ...m used as the packaging material away from young children Contents 1 SAFETY PRECAUTIONS 1 2 ABOUT THIS PRODUCT 1 3 SELECTING THE MOUNTING POSITION 2 4 INSTALLATION DIAGRAM 2 5 INSTALLATION 4 6 PUMP DOWN 5 CAUTION Read carefully all safety information written in this manual before you install or use the air conditioner This unit must be installed by qualified personnel with a capacity certificate f...

Страница 3: ...en using a connection pipe other than that in the table charge additional refrigerant with 20 g 1 m as the criteria For the additional amount see the table below Pipe length 15 m 20 m 25 m 30 m Rate Additional refrigerant None 100 g 200 g 300 g 20 g m CAUTION When adding refrigerant add the refrigerant from the charging port at the completion of work 2 7 Accessories The following installation acce...

Страница 4: ...2 Obstacles at rear sides and above only 60 or more 10 or more 25 or more 10 or more Max 20 4 1 2 Multiple outdoor unit installation Provide at least 25 cm of space between the outdoor units if multiple units are installed When routing the piping from the side of an outdoor unit provide space for the piping No more than 3 units must be installed side by side When 3 units or more are arranged in a ...

Страница 5: ...4 Outdoor unit wiring 1 Remove the outdoor unit connector cover 2 Bend the end of the cable as shown in the figure 3 Connect the end of the connection cable fully into the terminal block 4 Fasten the sheath with a cable clamp 5 Install the connector cover Connection cable Cable clamp N L 3 2 1 Cable clamp Earth screw N L 3 2 1 1 2 3 Outdoor unit terminal block Indoor unit terminal block Connection...

Страница 6: ...2 MPa retighten the valve stem and disconnect the charge hose from the 3 way valve charging port If the stem of the 3 way valve is opened fully before the charge hose is disconnect ed it may be difficult to disconnect the charge hose 10 Fully open the valve stems of the 2 way valve and 3 way valve using a hexagon wrench After the valve stem begins to turn turn it with a torque of less than 2 9 N m...

Отзывы: