3. Installation space

3-1. Models: AOYG09KXCA and AOYG12KXCA

¢

Space requirement

Provide sufficient installation space for product safety.

Single outdoor unit installation

When the upper space is open:

Unit: mm

When there are obstacles at the rear only.

When there are obstacles at the rear and
sides.

100 or more

250 or more

100 or more

100 or more

When there are obstacles at the front only.

When there are obstacles at the front and
rear.

600 or more

600 or more

100 or more

When there is an obstruction in the upper space:

Unit: mm

When there are obstacles at the rear and
above.

When there are obstacles at the rear, sides,
and above.

100 or more

Max. 200

600 or more

600 or more

100 or more

250 or more

100 or more

Max. 200

- 30 -

3-1. Models: AOYG09KXCA and AOYG12KXCA

3. Installation space

OUTDOOR UNIT

AOYG09, 12KXCA

OUTDOOR UNIT

AOYG09, 12KXCA

Содержание AOYG09KXCA

Страница 1: ...AIR CONDITIONER Wall mounted type DESIGN TECHNICAL MANUAL INDOOR ASYG09KXCA ASYG12KXCA OUTDOOR AOYG09KXCA AOYG12KXCA DR_AS027EF_02 2018 09 21 ...

Страница 2: ...uct specifications and design are subject to change without notice for future improvement For further details please check with our authorized dealer Copyright 2016 2018 Fujitsu General Limited All rights reserved ...

Страница 3: ...y 11 6 Fan performance 12 6 1 Air velocity distributions 12 6 2 Airflow 13 7 Operation noise sound pressure 14 7 1 Noise level curve 14 7 2 Noise level curve when DUAL FAN COMFORT is on 15 7 3 Sound level check point 16 8 Safety devices 17 9 Remote controller 18 9 1 Wireless remote controller 18 10 Function settings 20 10 1 Function settings by using remote controller 20 10 2 Custom code setting f...

Страница 4: ...s AOYG09KXCA and AOYG12KXCA 34 6 Capacity compensation rate for pipe length and height difference 35 6 1 Models AOYG09KXCA and AOYG12KXCA 35 7 Additional charge calculation 36 7 1 Models AOYG09KXCA and AOYG12KXCA 36 8 Airflow 37 8 1 Model AOYG09KXCA 37 8 2 Model AOYG12KXCA 37 9 Operation noise sound pressure 38 9 1 Noise level curve 38 9 2 Sound level check point 39 10 Electrical characteristics 4...

Страница 5: ...Part 1 INDOOR UNIT WALL MOUNTED TYPE ASYG09KXCA ASYG12KXCA ...

Страница 6: ... 590 LOW 520 QUIET 350 Heating HIGH 810 MED 690 LOW 570 QUIET 380 Type Q ty Cross flow fan 1 Motor output W 64 Sound pressure level 2 Cooling HIGH dB A 46 MED 42 LOW 38 QUIET 28 Heating HIGH 48 MED 43 LOW 39 QUIET 30 Sound pressure level when DUAL FAN COMFORT is on 2 Cooling HIGH dB A 46 MED 42 LOW 39 QUIET 29 Heating HIGH 48 MED 43 LOW 40 QUIET 31 Heat exchanger type Dimensions H W D mm Main 1 22...

Страница 7: ...rotective function might work when using it outside the operation range 1 Maximum current is maximum value when operated within the operation range 2 Sound pressure level Measured values in manufacturer s anechoic chamber Because of the surrounding sound environment the sound levels measured in actual installation conditions might be higher than the specified values here 3 Available on Google Play...

Страница 8: ...ing kW 2 5 35 C 3 4 35 C Heating Average 3 4 10 C 3 5 10 C SEER Cooling kWh kWh 8 5 8 5 SCOP Heating Average 5 1 5 1 Annual energy consumption QCE kWh a 103 140 QHE Average 934 961 Sound power level Cooling HIGH dB A 58 Heating 62 4 1 Specifications WALL MOUNTED ASYG09 12KXCA WALL MOUNTED ASYG09 12KXCA ...

Страница 9: ...eless router complies with the network security standards listed above refer to the operation manual Smartphone or Tablet PC App compliant operating system iOS Check the latest version of supported OS at Google Play store or App Store Android mobile application Mobile app is available on Google Play store or on App Store After installation of mobile app user registration is required For user regis...

Страница 10: ...ng 10 C HEAT operation setting 1 1 Additional function Human sensor for energy saving setting 1 1 Outdoor unit low noise operation setting 1 1 Room temperature indicator Demand control indicator App function Air conditioner error e mail notification 1 Not operable when wired remote controller is connected 2 Configurable functions of the weekly timer differs on wireless remote controller and on mob...

Страница 11: ...G12KXCA Unit mm 293 378 786 786 520 585 688 ø 6 5 293 70 73 320 323 Outline of unit 287 106 100 5 292 5 ø 6 5 172 1 262 5 23 7 50 5 47 47 7 3 1 Models ASYG09KXCA and ASYG12KXCA 3 Dimensions WALL MOUNTED ASYG09 12KXCA WALL MOUNTED ASYG09 12KXCA ...

Страница 12: ...re 100 or more 2 95 or more 1 Obstructions such as a curtain Lowest position of the dual fan NOTE Dual side fans rotate downward when the unit is operating as shown in the figure above If the depth of the obstruction is larger than 95 mm secure specified distance 2 in between the indoor unit and the obstruction 8 3 1 Models ASYG09KXCA and ASYG12KXCA 3 Dimensions WALL MOUNTED ASYG09 12KXCA WALL MOU...

Страница 13: ...4 Wiring diagrams 4 1 Models ASYG09KXCA and ASYG12KXCA Main PC board Sub PC board 9 4 1 Models ASYG09KXCA and ASYG12KXCA 4 Wiring diagrams WALL MOUNTED ASYG09 12KXCA WALL MOUNTED ASYG09 12KXCA ...

Страница 14: ... 40 1 99 1 75 0 60 2 19 1 83 0 60 2 32 1 88 0 60 2 45 1 93 0 60 2 58 2 01 0 60 2 71 2 02 0 60 2 91 2 08 0 60 46 1 88 1 70 0 71 2 06 1 78 0 72 2 19 1 83 0 72 2 31 1 88 0 72 2 43 1 95 0 72 2 56 1 97 0 72 2 74 2 02 0 72 Model ASYG12KXCA AFR m3 h 670 Indoor temperature CDB 18 21 23 25 27 29 32 CWB 12 15 16 18 19 21 23 Outdoor temperature CDB TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP ...

Страница 15: ...94 1 65 6 82 1 49 6 49 1 35 5 97 1 22 5 23 1 12 24 18 7 01 1 50 6 90 1 35 6 56 1 22 6 04 1 10 5 29 1 01 Model ASYG12KXCA AFR m3 h 810 Indoor temperature 16 18 20 22 24 Outdoor temperature CDB CWB TC IP TC IP TC IP TC IP TC IP kW kW kW kW kW 15 16 6 40 3 26 6 40 3 39 6 11 3 08 5 61 2 76 4 86 2 55 10 11 6 62 3 26 7 33 3 26 7 01 3 17 6 44 2 85 5 58 2 63 5 7 6 68 3 26 7 40 3 26 7 77 3 26 7 13 2 93 6 1...

Страница 16: ...ouver Up Horizontal airflow direction louver Left Right m m Unit m s 3 2 1 0 1 2 3 0 1 2 3 4 5 6 7 8 9 2 0 2 0 1 0 1 0 0 5 0 5 Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center m m Unit m s 0 1 2 3 0 1 2 3 4 5 6 7 8 9 2 0 1 0 0 5 Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center m m Unit m s 0 1 2 3 0 1 2 3 4 5 6 7 8...

Страница 17: ... 590 l s 164 CFM 347 LOW m3 h 520 l s 144 CFM 306 QUIET m3 h 350 l s 97 CFM 206 Heating Fan speed Airflow HIGH m3 h 810 l s 225 CFM 477 MED m3 h 690 l s 192 CFM 406 LOW m3 h 570 l s 158 CFM 336 QUIET m3 h 380 l s 106 CFM 224 13 6 2 Airflow 6 Fan performance WALL MOUNTED ASYG09 12KXCA WALL MOUNTED ASYG09 12KXCA ...

Страница 18: ... 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 HIGH QUIET Model ASYG12KXCA Cooling Octave band sound pressure level dB 0 dB 0 0002 µbar 80 70 60 50 40 30 20 10 0 Octave band center frequency Hz 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 HIGH QUIET Heating Octave band sound pressure level dB 0 dB 0 0002 µbar 80 70 60 50 ...

Страница 19: ...0 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 Model ASYG12KXCA Cooling HIGH QUIET Octave band sound pressure level dB 0 dB 0 0002 µbar 80 70 60 50 40 30 20 10 0 Octave band center frequency Hz 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 Heating HIGH QUIET NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 Octave ...

Страница 20: ...7 3 Sound level check point Microphone Microphone 0 8 m 1 m 16 7 3 Sound level check point 7 Operation noise sound pressure WALL MOUNTED ASYG09 12KXCA WALL MOUNTED ASYG09 12KXCA ...

Страница 21: ...2KXCA Circuit protection Current fuse PCB 250 V 4 A Fan motor protection Power IC thermal shutdown protection Activate 150 15 C Fan motor stop Reset 120 15 C Fan motor restart PCB Printed Circuit Board 17 8 Safety devices WALL MOUNTED ASYG09 12KXCA WALL MOUNTED ASYG09 12KXCA ...

Страница 22: ...ANCEL button NOTE Functions may differ by type of the indoor unit For details refer to the operation manual Display panel Mode indicator DUAL FAN indicator LOW NOISE mode indicator ENERGY SAVING mode indicator Turns on when the SENSOR button is operated Clock and Timer indicator Transmit indicator Temperature indicator Fan speed indicator Swing indicator To facilitate explanation the accompanying ...

Страница 23: ...05 61 17 Weight g 122 without batteries Holder Unit mm 48 5 5 5 26 2 69 3 6 5 Front View Side View Bottom View Ø 3 5 Hole 150 106 8 Hole 3 5 2 R Size H W D mm 150 69 3 26 2 Weight g 27 19 9 1 Wireless remote controller 9 Remote controller WALL MOUNTED ASYG09 12KXCA WALL MOUNTED ASYG09 12KXCA ...

Страница 24: ...NOTE Settings will not be changed if invalid numbers or setting values are selected Entering function setting mode While pressing the POWERFUL button and TEMP button simulta neously press the RESET button to enter the function setting mode Function number Setting value Selecting the function number and setting value 1 Press the TEMP buttons to select the function number To switch between the left ...

Страница 25: ...nance indicator switchover 1 Filter clean operation interval Select appropriate intervals for automatically cleaning the air filter according to environmental condi tions and the conditions of use Function number Setting value Setting description Factory setting 10 00 Standard Approximately once every 5 days 01 Long interval Approximately once every 8 days 02 Short interval Approximately once ever...

Страница 26: ...ore heating 11 1 0 C 12 1 5 C 13 2 0 C 14 2 5 C 15 3 0 C 16 3 5 C 17 4 0 C 4 Auto restart Enables or disables automatic restart after a power interruption Function number Setting value Setting description Factory setting 40 00 Enable 01 Disable NOTE Auto restart is an emergency function such as for power outage etc Do not attempt to use this function in normal operation Be sure to operate the unit...

Страница 27: ...remote controller has this setting refer to the operating manual of each remote controller 7 Dual fan airflow in COOL DRY and FAN modes Switches the dual fan vertical airflow in COOL DRY and FAN modes Set this when the dual fan airflow is too strong or week Function number Setting value Setting description Factory setting 92 00 Standard 01 Down 02 Up 8 Dual fan vertical airflow angle in COOL DRY a...

Страница 28: ...STOP button until only the clock is displayed on the remote controller display 2 Press the MODE button for at least 5 seconds to display the cur rent custom code Initially set to 3 Press the TEMP buttons to change the custom code be tween Match the code on the display to the air con ditioner custom code Initially set to 4 Press the MODE button again to return to the clock display The custom code w...

Страница 29: ...least 5 seconds to display the current temperature unit Factory setting C 2 Press the TEMP buttons to switch the temperature unit between C and F 3 With either of pressing the START STOP button or no additional button operation for 30 sec onds in step 2 the temperature unit currently selected will be set 25 10 3 Switching the temperature unit of remote controller 10 Function settings WALL MOUNTED ...

Страница 30: ...e controller 1 Setting manual for WLAN control 1 Remote controller holder 1 Wireless LAN adapter with cable with attached wireless LAN label 1 Battery 2 This product has a wireless LAN adapter as accessory Be sure to keep the wireless LAN label attached to the adapter by writing the details down or pasting it on the list in the last section of the setting manual for wireless LAN adapter 26 11 Acce...

Страница 31: ...Part 2 OUTDOOR UNIT SINGLE TYPE AOYG09KXCA AOYG12KXCA ...

Страница 32: ...pproximate color of Munsell 10YR 7 5 1 0 Dimensions H W D Net mm 704 820 315 Gross 786 965 426 Weight Net kg 41 Gross 46 Connection pipe Size Liquid mm Ø 6 35 Ø 1 4 Gas Ø 9 52 Ø 3 8 Method Flare Pre charge length m 15 Max length 15 Max height difference 10 Operation range Cooling C 10 to 43 Heating 15 to 24 Drain hose Material LDPE Size mm Ø 13 0 I D Ø 16 0 to Ø 16 7 O D NOTES Specifications are b...

Страница 33: ...G12KXCA 16 820 704 570 225 Ø30 mm hole 4 Ø12 mm hole 340 25 110 175 6 64 26 315 358 17 Side view Top view Front view Bottom view Unit mm 29 2 1 Models AOYG09KXCA and AOYG12KXCA 2 Dimensions OUTDOOR UNIT AOYG09 12KXCA OUTDOOR UNIT AOYG09 12KXCA ...

Страница 34: ...more 100 or more 100 or more When there are obstacles at the front only When there are obstacles at the front and rear 600 or more 600 or more 100 or more When there is an obstruction in the upper space Unit mm When there are obstacles at the rear and above When there are obstacles at the rear sides and above 100 or more Max 200 600 or more 600 or more 100 or more 250 or more 100 or more Max 200 3...

Страница 35: ...only 200 or more 1 000 or more When there are obstacles at the front and rear 200 or more 1 000 or more When there is an obstruction in the upper space Unit mm When there are obstacles at the rear and above 1 500 or more 200 or more Max 300 31 3 1 Models AOYG09KXCA and AOYG12KXCA 3 Installation space OUTDOOR UNIT AOYG09 12KXCA OUTDOOR UNIT AOYG09 12KXCA ...

Страница 36: ...tage where the drain water could freeze Otherwise the drainage from the upper unit may form ice and cause a malfunction of the lower unit When the outdoor temperature is 0 C or less do not use the accessory drain pipe and drain cap If the drain pipe and drain cap are used the drain water in the pipe may freeze in extremely cold climate For reverse cycle model only In area with heavy snowfall if th...

Страница 37: ...4 Refrigerant circuit 4 1 Models AOYG09KXCA and AOYG12KXCA 33 4 1 Models AOYG09KXCA and AOYG12KXCA 4 Refrigerant circuit OUTDOOR UNIT AOYG09 12KXCA OUTDOOR UNIT AOYG09 12KXCA ...

Страница 38: ...5 Wiring diagrams 5 1 Models AOYG09KXCA and AOYG12KXCA 34 5 1 Models AOYG09KXCA and AOYG12KXCA 5 Wiring diagrams OUTDOOR UNIT AOYG09 12KXCA OUTDOOR UNIT AOYG09 12KXCA ...

Страница 39: ...utdoor unit 1 10 0 929 0 872 7 5 0 960 0 933 0 876 5 0 992 0 964 0 937 0 879 0 1 000 0 972 0 944 0 887 Indoor unit is lower than outdoor unit 2 5 1 000 0 972 0 944 0 887 7 5 0 972 0 944 0 887 10 0 944 0 887 HEATING Pipe length m 5 7 5 10 15 Height difference H m Indoor unit is higher than outdoor unit 1 10 0 968 0 890 7 5 0 994 0 968 0 896 5 1 000 0 994 0 968 0 896 0 1 000 0 994 0 968 0 986 Indoor...

Страница 40: ...unt g 1 300 Refrigerant charge Total pipe length m 7 5 or less 15 Max 0 g m Additional charge g 0 0 NOTE There is no additional refrigerant charge in this product Chargeless system 36 7 1 Models AOYG09KXCA and AOYG12KXCA 7 Additional charge calculation OUTDOOR UNIT AOYG09 12KXCA OUTDOOR UNIT AOYG09 12KXCA ...

Страница 41: ... 1 975 l s 549 CFM 1 162 Heating m3 h 1 820 l s 506 CFM 1 071 8 2 Model AOYG12KXCA Cooling m3 h 2 230 l s 619 CFM 1 313 Heating m3 h 1 975 l s 549 CFM 1 162 37 8 1 Model AOYG09KXCA 8 Airflow OUTDOOR UNIT AOYG09 12KXCA OUTDOOR UNIT AOYG09 12KXCA ...

Страница 42: ... 8 000 NC 20 NC 40 NC 50 NC 60 NC 15 NC 25 NC 45 NC 55 NC 65 NC 30 NC 35 Model AOYG12KXCA Cooling Octave band sound pressure level dB 0 dB 0 0002 µbar 80 70 60 50 40 30 20 10 0 Octave band center frequency Hz 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 15 NC 25 NC 45 NC 55 NC 65 NC 30 NC 35 Heating Octave band sound pressure level dB 0 dB 0 0002 µbar 80 70 60 50 40 30 20 10 0...

Страница 43: ...Rear Airflow Rear view Side view NOTE Detailed shape of the actual outdoor unit might be slightly different from the one illustrated above 39 9 2 Sound level check point 9 Operation noise sound pressure OUTDOOR UNIT AOYG09 12KXCA OUTDOOR UNIT AOYG09 12KXCA ...

Страница 44: ...ximum operating current is the total current of the indoor unit and the outdoor unit 2 Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005 As the regulations of wire size and circuit breaker differ in each country or region select appropriate de vices complied to the regional standard 3 Limit voltage drop to less than 2 If voltage drop is 2 or more increase cable co...

Страница 45: ...motor restart Compressor protection Terminal protection program Compressor temp Activate 108 C Compressor stop Reset After 40 minutes Compressor restart Thermal protection program Discharge temp Activate 110 C Compressor stop Reset After 7 minutes Compressor restart High pressure protection Pressure switch Activate 4 2 0 1 MPa Compressor stop Reset 3 2 0 15 MPa Compressor restart 41 11 Safety devi...

Страница 46: ...12 Accessories Part name Exterior Q ty Part name Exterior Q ty Installation manual 1 Drain pipe 1 42 12 Accessories OUTDOOR UNIT AOYG09 12KXCA OUTDOOR UNIT AOYG09 12KXCA ...