7) Cold air prevention
This setting is to disable the cold air prevention function during heating operation. When disabled,
the fan setting will always follow the setting on the remote controller. (Excluding defrost mode)
Function number
Setting value
Setting description
Factory setting
43
00
Enable
♦
01
Disable
NOTE:
The customer may feel the cold air at the time heating operation starts, and at the time out-
door unit recovers from defrosting operation if the “Cold air prevention control” is disabled
by the local function setting.
8) Remote controller custom code
(Only for wireless remote controller)
The indoor unit custom code can be changed. Select the appropriate custom code.
Function number
Setting value
Setting description
Factory setting
44
00
A
♦
01
B
02
C
03
D
9) External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
Function number
Setting value
Setting description
Factory setting
46
00
Operation/Stop mode 1
♦
01
(Setting prohibited)
02
Forced stop mode
03
Operation/Stop mode 2
NOTE:
If this function is necessary, the rotary switch on the External input and output PCB should
be set to 1.
10) Room temperature sensor switching (Aux.)
To use the temperature sensor on the wired remote controller only, change the setting to "Wired re-
mote controller" (01).
This function will only work if the function setting 42 is set at "Both" (01).
When the setting value is set to "Both" (00), more suitable control of the room temperature is possi-
ble by setting function setting 30 and 31 too.
Function number
Setting value
Setting description
Factory setting
48
00
Both
♦
01
Wired remote controller
- 34 -
11-1. Function settings by using remote controller
11. Function settings
WALL MOUNTED
ASYG09-14KMCDN
WALL MOUNTED
ASYG09-14KMCDN