6. Capacity compensation rate for pipe length and height
difference
Height difference H
Indoor unit is higher than outdoor unit
*
1
Indoor unit is lower than outdoor unit
*
2
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
H
H
6-1. Models: AOUH18LPAS1 and AOUH24LPAS1
NOTE:
Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length
m
5
7.5
10
15
20
ft
16
25
33
49
66
Height difference H
Indoor unit is higher than outdoor
unit *1
15
49
-
-
-
0.951
0.950
10
33
-
-
0.979
0.967
0.966
7.5
25
-
0.988
0.983
0.971
0.970
5
16
0.994
0.992
0.987
0.975
0.974
0
0
1.002
1.000
0.995
0.983
0.982
Indoor unit is lower than outdoor
unit *2
-5
-16
1.002
1.000
0.995
0.983
0.982
-7.5
-25
-
1.000
0.995
0.983
0.982
-10
-33
-
-
0.995
0.983
0.982
-15
-49
-
-
-
0.983
0.982
HEATING
Pipe length
m
5
7.5
10
15
20
ft
16
25
33
49
66
Height difference H
Indoor unit is higher than outdoor
unit *1
15
49
-
-
-
0.994
0.979
10
33
-
-
1.012
0.994
0.979
7.5
25
-
1.000
1.012
0.994
0.979
5
16
0.969
1.000
1.012
0.994
0.979
0
0
0.969
1.000
1.012
0.994
0.979
Indoor unit is lower than outdoor
unit *2
-5
-16
0.964
0.995
1.007
0.989
0.974
-7.5
-25
-
0.993
1.004
0.986
0.972
-10
-33
-
-
1.002
0.984
0.969
-15
-49
-
-
-
0.974
0.959
- 71 -
6-1. Models: AOUH18LPAS1 and AOUH24LPAS1
6. Capacity compensation rate for pipe length and height difference
OUTDOOR UNIT
AOUH18-24LPAS1
OUTDOOR UNIT
AOUH18-24LPAS1