TEST RUN
1. Pre-test run check items
2. Test operation method
OUTDOOR UNIT
2012.08.26
18
POWER
MODE
ERROR
TEST
RUN
PUMP
DOWN
LOW NOISE
PEAK CUT
(L1)
(L2)
(L3)
(L4)
(L5)
(L6)
(L7)
POWER
MODE
ERROR
TEST
RUN
PUMP
DOWN
LOW NOISE
PEAK CUT
(L1)
(L2)
(L3)
(L4)
(L5)
(L6)
(L7)
POWER
MODE
ERROR
TEST
RUN
PUMP
DOWN
LOW NOISE
PEAK CUT
(L1)
(L2)
(L3)
(L4)
(L5)
(L6)
(L7)
Before the test operation, refer to the figure and check the following items.
Is the outdoor unit securely installed?
Have you performed gas leakage inspection?
(Connection joints of various pipes (flang connection, brazing))
Is the heat insulation done completely?
(Gas pipe, liquid pipe, drain hose extension on indoor unit side, etc.)
Is the water discharging from drain without any problems?
Are the cables connected correctly?
Are the cables as per specifications?
Is the earth wire connected accurately?
Are there any obstacles blocking the suction gate, and outlet of
the indoor/outooor units?
Have you filled the specified amount of refrigerant?
Are the stop valves of gas pipe and liquid pipe fully open?
Has the power been supplied to crankcase heater for more than 6 hours?
After checking that the above items are all in order, refer
to “11.2. Test operation method” to test operation the unit.
If there are problems, adjust immediately and recheck.
Be sure to conf gure test run settings only when the outdoor unit has stopped
operating.
Test operation setting method (lt can be performed in the following two ways)
Set with test operation setting (refer to installation instructions manual of indoor unit
•
for further details) available in the remote controller.
“Cooling Operation” and “Heating Operation” can be set, using SELECT button and
•
ENTER button available on the board of display unit.
(*Make sure to perform the first test operation with cooling operation.)
Set as per the procedure given below.
LED display part
SW1
SW2
SW3
SW4
SW5
Button part
Depending on the communication status between the indoor and outdoor units,
•
it may take several minutes for the system to start operating after settings for the
test run are complete.
After the test run settings are complete, the outdoor units and the connected
•
indoor units will start operating. Room temperature control will not activate during
test operation (continuous operation).
If a knocking sound can be heard in the liquid compression of the compressor,
•
stop the unit immediately and then energize the crank case heater for a suff cient
length of time before restarting the operation.
2.1. Setting method on outdoor unit board
3. Check list
Turn on the power of the outdoor unit and enter standby mode.
“POWER/MODE” Lamp lights up.
POWER
ERROR
PUMP
DOWN
LOW
NOISE
PEAK
CUT
MODE
(L1)
(L2)
(L3)
(L4)
(L5)
(L6)
Press the ENTER button for more than 3 seconds.
POWER
ERROR
PUMP
DOWN
LOW
NOISE
PEAK
CUT
MODE
(L1)
(L2)
(L3)
(L4)
(L5)
(L6)
Blink
Blink
Press the SELECT button, LED of the test run mode switched between “COOL”
and “HEAT”.
Cooling test mode
POWER
ERROR
PUMP
DOWN
LOW
NOISE
PEAK
CUT
MODE
(L1)
(L2)
(L3)
(L4)
(L5)
(L6)
Blink
Blink
Heating test mode
POWER
ERROR
PUMP
DOWN
LOW
NOISE
PEAK
CUT
MODE
(L1)
(L2)
(L3)
(L4)
(L5)
(L6)
Blink
Blink
After confirming the operation mode, Press ENTER button
The display changes as follows, and air conditioner starts operation.
Cooling test mode
POWER
ERROR
PUMP
DOWN
LOW
NOISE
PEAK
CUT
MODE
(L1)
(L2)
(L3)
(L4)
(L5)
(L6)
Blink
Heating test mode
POWER
ERROR
PUMP
DOWN
LOW
NOISE
PEAK
CUT
MODE
(L1)
(L2)
(L3)
(L4)
(L5)
(L6)
Blink
Press [ENTER] button.
(5)
(4)
(3)
(2)
(1)
Air conditioner stopped operation.
POWER
ERROR
PUMP
DOWN
LOW
NOISE
PEAK
CUT
MODE
(L1)
(L2)
(L3)
(L4)
(L5)
(L6)
Sign “
”: Lights off, “
”: Lights on
Sign “
”: Lights off, “
”: Lights on
Sign “
”: Lights off, “
”: Lights on
Sign “
”: Lights off, “
”: Lights on
Sign “
”: Lights off, “
”: Lights on
Sign “
”: Lights off, “
”: Lights on
Sign “
”: Lights off, “
”: Lights on
Check items during test operation.
Is the outdoor unit making any abnormal noise or vibrating significantly?
Is the cold air or hot air blowing from indoor unit according to the operation
mode?
Check that the “ERROR” LED blinks.
If, it has displayed, check the error content as per 12.2. described later.
Operate the unit according to the operating manual provided with the indoor
unit, and check that it is operating normally.
(2)
(3)
(4)
(5)
(1)